Fig. 29 — controls expansion board (cem) – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 118

Advertising
background image

118

Table 91 — Control Expansion Module (CEM) Inputs and Outputs

POINT

NAME

POINT DESCRIPTION

I/O

POINT

NAME

PLUG AND PIN

REFERENCE

SIGNAL PIN(S)

PORT STATE

INPUTS
DHDISCIN

Dehumidify Switch Input

DI 1

J7, 1-2

2

0 = 24vac, 1= 0vac

DMD_SW1

Demand Limit Switch 1

DI 2

J7, 3-4

4

0 = 24vac, 1= 0vac

DMD_SW2

Demand Limit Switch 2

DI 3

J7, 5-6

6

0 = 24vac, 1= 0vac

PRES

Pressurization

DI 4

J7, 7-8

8

0 = 24vac, 1= 0vac

EVAC

Evacuation

DI 5

J7, 9-10

10

0 = 24vac, 1= 0vac

PURG

Smoke Purge

DI 6

J7, 11-12

12

0 = 24vac, 1= 0vac

IAQIN

IAQ - Discrete Input

DI 7

J7, 13-14

14

0 = 24vac, 1= 0vac

OACFM

Outside Air CFM

AN7

J6, 1-3

2 (1 = loop power)

(0-20mA input)

OARH

Outside Air Rel.Humidity

AN8

J6, 4-6

5 (4 = loop power)

(0-20mA input)

SPRH

Space Relative Humidity

AN9

J6, 7-9

8 (7 = loop power)

(0-20mA input)

RARH

Return Air Rel.Humidity

AN10

J6, 10-12

11 (10 = loop power)

(0-20mA input)

DMDLMTMA

4-20ma Demand Signal

AN1

J5, 1-2

1

(thermistor, ohms)

EDTRESMA

EDT Reset milliampere

AN2

J5, 3-4

3

(thermistor, ohms)

OAQ

OAQ - PPM Return CO2

AN3

J5, 5-6

5

(thermistor, ohms)

SPRESET

SP Reset milliamps

AN3

J5, 5-6

5

(thermistor, ohms)

AN4

J5, 7-8

7

(thermistor, ohms)

AN5

J5, 9-10

9

(thermistor, ohms)

AN6

J5, 11-12

11

(thermistor, ohms)

CEBD430351

TEST

1

CEPL130351-01

PWR

TEST 2

J1

J2

J4

J3

J5

J6

J7

LEN

STATUS

RED LED - STATUS

GREEN LED -
LEN (LOCAL EQUIPMENT NETWORK)

ADDRESS
DIP SWITCH (ALL ON)

Fig. 29 — Controls Expansion Board (CEM)

Advertising