Display configuration – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 82

Advertising
background image

82

Table 65 — Sensor Trim Configuration

The defaults for this switch logic section will not normally

need changing. However, if a field-installed switch is used that

is different from the Carrier switch, these settings may need

adjustment.

Settings for switch logic are found at the local displays

under the Configuration

SW.LG submenu. See Table 66.

Filter Status Input — Clean (FTS.L) — The filter status in-

put for clean filters is set for normally open. If a field-supplied

filter status switch is used that is normally closed for a clean

filter, change this variable to closed.
IGC Feedback — Off (IGC.L) — The input for IGC feed-

back is set for normally open for off. If a field-supplied IGC

feedback switch is used that is normally closed for feedback

off, change this variable to closed.
Remote Switch — Off (RMI.L) — The remote switch is set

for normally open when off. If a field-supplied control switch

is used that is normally closed for an off signal, change this

variable to closed.
Enthaply Input — Low (ENT.L) — The enthalpy input is set

for normally closed when low. If a field-supplied enthalpy

switch is used that is normally open when low, change this

variable to open.
Fan Status Switch — Off (SFS.L) — The fan status switch

input is set for normally open for off. If a field-supplied fan

status switch is used that is normally closed, change this

variable to closed.
Demand Limit Switch 1 — Off (DL1.L) — The demand

limit switch no. 1 input is set for normally open for off. If a

field-supplied demand limit switch is used that is normally

closed, change this variable to closed.
Demand Limit Switch 2 — Off (DL2.L) — The demand

limit switch no. 2 input is set for normally open for off. If a

field-supplied demand limit switch is used that is normally

closed, change this variable to closed.

IAQ Discrete Input — Low (IAQ.L) — The IAQ discrete in-

put is set for normally open when low. If a field-supplied IAQ

discrete input is used that is normally closed, change this vari-

able to closed.
Fire Shutdown — Off (FSD.L) — The fire shutdown input is

set for normally open when off. If a field-supplied fire shut-

down input is used that is normally closed, change this variable

to closed.
Pressurization Switch — Off (PRS.L) — The pressurization

input is set for normally open when off. If a field-supplied pres-

surization input is used that is normally closed, change this

variable to closed.
Evacuation Switch — Off (EVC.L) — The evacuation input

is set for normally open when off. If a field-supplied evacua-

tion input is used that is normally closed, change this variable

to closed.
Smoke Purge — Off (PRG.L) — The smoke purge input is

set for normally open when off. If a field-supplied smoke purge

input is used that is normally closed, change this variable to

closed.
Dehumidify Switch — Off (DH.LG) — The dehumidify in-

put is set for normally open when off. If a field-supplied

dehumidify input is used that is normally closed, change this

variable to closed.

Display Configuration —

The DISP submenu is used

to configure the local display settings. A list is shown in

Table 67.
Test Display LEDs (TEST) — This is used to test the opera-

tion of the ComfortLink™ display.
Metric Display (METR) — This variable is used to change

the display from English units to Metric units.
Language Selection (LANG) — This variable is used to

change the language of the ComfortLink display. At this time,

only English is available.
Password Enable (PAS.E) — This variable enables or dis-

ables the use of a password. The password is used to restrict

use of the control to change configurations.
Service Password (PASS) — This variable is the 4-digit nu-

meric password that is required if enabled.

Table 66 — Switch Logic Configuration

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

TRIM

SENSOR TRIM CONFIG.

SAT.T

Air Temp Lvg SF Trim

-10 - 10

^F

SAT_TRIM

0

RAT.T

RAT Trim

-10 - 10

^F

RAT_TRIM

0

OAT.T

OAT Trim

-10 - 10

^F

OAT_TRIM

0

SPT.T

SPT Trim

-10 - 10

^F

SPT_TRIM

0

L.SW.T

Limit Switch Trim

-10 - 10

^F

LSW_TRIM

0

CCT.T

Air Temp Lvg Evap Trim

-10 - 10

^F

CCT_TRIM

0

SP.A.T

Suct.Press.Circ.A Trim

-50 - 50

PSIG

SPA_TRIM

0

SP.B.T

Suct.Press.Circ.B Trim

-50 - 50

PSIG

SPB_TRIM

0

DP.A.T

Dis.Press.Circ.A Trim

-50 - 50

PSIG

DPA_TRIM

0

DP.B.T

Dis.Press.Circ.B Trim

-50 - 50

PSIG

DPB_TRIM

0

IMPORTANT: Many of the switch inputs to the control

can be configured to operate as normally open or nor-

mally closed.

ITEM

EXPANSION

RANGE

CCN POINT

DEFAULT

SW.LG

SWITCH LOGIC: NO / NC

FTS.L

Filter Status Inpt-Clean

Open/Close

FLTSLOGC

Open

IGC.L

IGC Feedback - Off

Open/Close

GASFANLG

Open

RMI.L

RemSw Off-Unoc-Strt-NoOv

Open/Close

RMTINLOG

Open

ENT.L

Enthalpy Input - Low

Open/Close

ENTHLOGC

Close

SFS.L

Fan Status Sw. - Off

Open/Close

SFSLOGIC

Open

DL1.L

Dmd.Lmt.Sw.1 - Off

Open/Close

DMD_SW1L

Open

DL2.L

Dmd.Lmt.Sw.2 - Off

Open/Close

DMD_SW2L

Open

IAQ.L

IAQ Disc.Input - Low

Open/Close

IAQINLOG

Open

FSD.L

Fire Shutdown - Off

Open/Close

FSDLOGIC

Open

PRS.L

Pressurization Sw. - Off

Open/Close

PRESLOGC

Open

EVC.L

Evacuation Sw. - Off

Open/Close

EVACLOGC

Open

PRG.L

Smoke Purge Sw. - Off

Open/Close

PURGLOGC

Open

DH.LG

Dehumidify Sw. - Off

Open/Close

DHDISCLG

Open