137

APPENDIX A — LOCAL DISPLAY TABLES (cont)

MODE — OUTPUTS

MODE — CONFIGURATION

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

WRITE STATUS

FANS

FANS

S.FAN

Supply Fan Relay

ON/OFF

SFAN

S.VFD

Supply Fan VFD Speed

0-100

%

SFAN_VFD

E.VFD

Exhaust Fan VFD Speed

0-100

%

EFAN_VFD

P.E.1

Power Exhaust Relay 1

ON/OFF

PE1

P.E.2

Power Exhaust Relay 2

ON/OFF

PE2

CD.F.A

Condenser Fan Circuit A

ON/OFF

CONDFANA

CD.F.B

Condenser Fan Circuit B

ON/OFF

CONDFANB

CD.MM

Motormaster Condensr Fan

ON/OFF

PULSCFAB

COOL

COOLING

A1

Compressor A1 Relay

ON/OFF

CMPA1

U1.A1

Unloader 1 - Comp A1

ON/OFF

UNL_1_A1

U2.A1

Unloader 2 - Comp A1

ON/OFF

UNL_2_A1

A2

Compressor A2 Relay

ON/OFF

CMPA2

B1

Compressor B1 Relay

ON/OFF

CMPB1

U1.B1

Unloader 1 - Comp B1

ON/OFF

UNL_1_B1

U2.B1

Unloader 2 - Comp B1

ON/OFF

UNL_2_B1

B2

Compressor B2 Relay

ON/OFF

CMPB2

HEAT

HEATING

HT.1

Heat Relay 1

ON/OFF

HS1

HT.2

Heat Relay 2

ON/OFF

HS2

HT.3

Relay 3 W1 Gas Valve 2

ON/OFF

HS3

HT.4

Relay 4 W2 Gas Valve 2

ON/OFF

HS4

HT.5

Relay 5 W1 Gas Valve 3

ON/OFF

HS5

HT.6

Relay 6 W2 Gas Valve 3

ON/OFF

HS6

H.I.R

Heat Interlock Relay

ON/OFF

HIR

forcible

HTC.P

Ht.Coil Act.Current Pos.

0-100

%

HTCLRPOS

ACTU

ACTUATORS

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONRPOS

EC2.P

Economzr 2 Act.Curr.Pos.

0-100

%

ECON2POS

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

IGV.P

IGV Actuator Current Pos

0-100

%

IGV_RPOS

IGV.C

IGV Actuator Command Pos

0-100

%

IGV_CPOS

BP1.P

BP 1 Actuator Curr.Pos.

0-100

%

BP1_RPOS

BP1.C

BP 1 Command Position

0-100

%

BP1_CPOS

BP2.P

BP 2 Actuator Curr.Pos.

0-100

%

BP2_RPOS

BP2.C

BP 2 Command Position

0-100

%

BP2_CPOS

HTC.P

Ht.Coil Act.Current Pos.

0-100

%

HTCLRPOS

HTC.C

Ht.Coil Command Position

0-100

%

HTCLCPOS

HMD.P

Humidifier Act.Curr.Pos.

0-100

%

HUMDRPOS

HMD.C

Humidifier Command Pos.

0-100

%

HUMDCPOS

GEN.O

GENERAL OUTPUTS

HUM.R

Humidifier Relay

ON/OFF

HUMIDRLY

ALRM

Remote Alarm / Aux Relay

ON/OFF

ALRM

forcible

ITEM

EXPANSION

RANGE

UNITS

CCN POINT

DEFAULT

PAGE NO.

UNIT

UNIT CONFIGURATION

C.TYP

Machine Control Type

1 - 6 (multi-text strings)

CTRLTYPE

4

42,44

CV.FN

Fan Mode (0=Auto, 1=Cont)

0 - 1 (multi-text strings)

FAN_MODE

1

44

RM.CF

Remote Switch Config

0 - 3 (multi-text strings)

RMTINCFG

0

44

CEM

CEM Module Installed

Yes/No

CEM_BRD

No

44

TCS.C

Temp.Cmp.Strt.Cool Factr

0 - 60

min

TCSTCOOL

0

44

TCS.H

Temp.Cmp.Strt.Heat Factr

0 - 60

min

TCSTHEAT

0

44

SFS.S

Fan Fail Shuts Down Unit

Yes/No

SFS_SHUT

No

44

SFS.M

Fan Stat Monitoring Type

0 - 2 (multi-text strings)

SFS_MON

0

44

VAV.S

VAV Unocc.Fan Retry Time

0 - 720

min

SAMPMINS

50

44

SIZE

Unit Size (30-105)

30 - 105

UNITSIZE

30

44

50.HZ

50 Hertz Unit ?

Yes/No

UNIT_HZ

No

44,45

MAT.S

MAT Calc Config

0 - 2 (multi-text strings)

MAT_SEL

1

44,45

MAT.R

Reset MAT Table Entries?

Yes/No

MATRESET

No

44,45

MAT.D

MAT Outside Air Default

0 -100

%

MATOAPOS

20

44,45

ALTI

Altitude……..in feet:

0 - 60000

ALTITUDE

0

44,45

DLAY

Startup Delay Time

0 -900

secs

DELAY

0

AUX.R

Auxiliary Relay Config

0 - 3 (multi-text strings)

AUXRELAY

0

SENS

INPUT SENSOR CONFIG

SENS

SPT.S

Space Temp Sensor

Enable/Disable

SPTSENS

Disable

44,45

SENS

SP.O.S

Space Temp Offset Sensor

Enable/Disable

SPTOSENS

Disable

44,45

SENS

SP.O.R

Space Temp Offset Range

1 - 10

SPTO_RNG

5

44,45

SENS

SRH.S

Space Air RH Sensor

Enable/Disable

SPRHSENS

Disable

44,45

SENS

RRH.S

Return Air RH Sensor

Enable/Disable

RARHSENS

Disable

44,45

SENS

FLT.S

Filter Stat.Sw.Enabled ?

Enable/Disable

FLTS_ENA

Disable

44,45

COOL

COOLING CONFIGURATION

Z.GN

Capacity Threshold Adjst

-10 - 10

Z_GAIN

1

46,47

MC.LO

Compressor Lockout Temp

-25 - 55

dF

OATLCOMP

40

46,47

L.L.EN

Lead/Lag Operation ?

Yes/No

LLENABLE

No

46,47

M.M.

Motor Master Control ?

Yes/No

MOTRMAST

No

46,47

HPSP

Head Pressure Setpoint

80 - 150

dF

HPSP

113

46,47

A1.EN

Enable Compressor A1

Enable/Disable

CMPA1ENA

Enable

46,47

A2.EN

Enable Compressor A2

Enable/Disable

CMPA2ENA

Enable

46,47

B1.EN

Enable Compressor B1

Enable/Disable

CMPB1ENA

Enable

46,47

B2.EN

Enable Compressor B2

Enable/Disable

CMPB2ENA

Enable

46,47

CS.A1

CSB A1 Feedback Alarm

Enable/Disable

CSB_A1EN

Enable

46,47

CS.A2

CSB A2 Feedback Alarm

Enable/Disable

CSB_A2EN

Enable

47

CS.B1

CSB B1 Feedback Alarm

Enable/Disable

CSB_B1EN

Enable

47

CS.B2

CSB B2 Feedback Alarm

Enable/Disable

CSB_B2EN

Enable

47

HPS.A

CMPA1 Hi.Pr.Sw. Trip

365 - 415

PSIG

HPSATRIP

415

47

HPS.B

CMPB1 Hi.Pr.Sw. Trip

365 - 415

PSIG

HPSBTRIP

415

47

H.SST

Hi SST Alert Delay Time

5 - 30

min

HSSTTIME

10

47