Appendix a — local display tables (cont) – Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 135

135
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — TEMPERATURES
MODE — PRESSURES
MODE — SETPOINTS
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.T
AIR TEMPERATURES
→
CTRL
CONTROL TEMPS
→
CTRL
→
EDT
Evaporator Discharge Tmp
dF
EDT
→
CTRL
→
LAT
Leaving Air Temperature
dF
LAT
→
CTRL
→
MAT
Mixed Air Temperature
dF
MAT
→
CTRL
→
R.TMP
Controlling Return Temp
dF
RETURN_T
forcible
→
CTRL
→
S.TMP
Controlling Space Temp
dF
SPACE_T
forcible
→
SAT
Air Tmp Lvg Supply Fan
dF
SAT
→
OAT
Outside Air Temperature
-40 - 240
dF
OAT
forcible
→
RAT
Return Air Temperature
dF
RAT
forcible
→
SPT
Space Temperature
-40 - 240
dF
SPT
forcible
→
SPTO
Space Temperature Offset
^F
SPTO
forcible
→
CCT
Air Temp Lvg Evap Coil
dF
CCT
→
S.G.LS
Staged Gas LAT Sum
dF
LAT_SGAS
→
S.G.L1
Staged Gas LAT 1
dF
LAT1SGAS
→
S.G.L2
Staged Gas LAT 2
dF
LAT2SGAS
→
S.G.L3
Staged Gas LAT 3
dF
LAT3SGAS
→
S.G.LM
Staged Gas Limit Sw.Temp
dF
LIMSWTMP
REF.T
REFRIGERANT TEMPERATURES
→
SCT.A
Cir A Sat.Condensing Tmp
dF
SCTA
→
SST.A
Cir A Sat.Suction Temp.
dF
SSTA
→
SCT.B
Cir B Sat.Condensing Tmp
dF
SCTB
→
SST.B
Cir B Sat.Suction Temp.
dF
SSTB
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
WRITE STATUS
AIR.P
AIR PRESSURES
→
SP
Static Pressure
"H2O
SP
→
BP
Building Pressure
"H2O
BP
REF.P
REFRIGERANT PRESSURES
→
DP.A
Cir A Discharge Pressure
PSIG
DP_A
→
SP.A
Cir A Suction Pressure
PSIG
SP_A
→
DP.B
Cir B Discharge Pressure
PSIG
DP_B
→
SP.B
Cit B Suction Pressure
PSIG
SP_B
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
OHSP
Occupied Heat Setpoint
40-99
dF
OHSP
68
OCSP
Occupied Cool Setpoint
40-99
dF
OCSP
75
UHSP
Unoccupied Heat Setpoint
40-99
dF
UHSP
55
UCSP
Unoccupied Cool Setpoint
40-110
dF
UCSP
90
GAP
Heat-Cool Setpoint Gap
2-10
deltaF
HCSP_GAP
5
V.C.ON
VAV Occ. Cool On Delta
0-25
deltaF
VAVOCON
3.5
V.C.OF
VAV Occ. Cool Off Delta
1-25
deltaF
VAVOCOFF
2
SASP
Supply Air Setpoint
45-75
dF
SASP
55
SA.HI
Supply Air Setpoint Hi
45-75
dF
SASP_HI
55
SA.LO
Supply Air Setpoint Lo
45-75
dF
SASP_LO
60
SA.HT
Heating Supply Air Setpt
80-120
dF
SASPHEAT
85
T.PRG
Tempering Purge SASP
-20-80
dF
TEMPPURG
50
T.CL
Tempering in Cool SASP
5-75
dF
TEMPCOOL
5
T.V.OC
Tempering Vent Occ SASP
-20-80
dF
TEMPVOCC
65
T.V.UN
Tempering Vent Unocc. SASP
-20-80
dF
TEMPVUNC
50