Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 7

Advertising
background image

7

START-UP

Unit Preparation —

Check that unit has been installed in

accordance with the installation instructions and applicable

codes.

Unit Setup —

Make sure that the economizer hood has

been installed and that the outdoor filters are properly installed.

Internal Wiring —

Ensure that all electrical connections

in the control box are tightened as required. If the unit has

staged gas heat make sure that the LAT sensors have been

routed to the supply ducts as required.

Accessory Installation —

Check to make sure that all

accessories including space thermostats and sensors have been

installed and wired as required by the instructions and unit

wiring diagrams.

Crankcase Heaters —

Crankcase heaters are energized

as long as there is power to the unit, except when the compres-

sors are running.

Evaporator Fan —

Fan belt and fixed pulleys are factory-

installed. See Tables 3-25 for fan performance. Remove tape

from fan pulley, and be sure that fans rotate in the proper

direction. See Tables 26-28 for motor limitations. See Table 29

for air quantity limits. Static pressure drop is shown in

Tables 30A-30C.
FIELD-SUPPLIED FAN DRIVES — Supply fan and power

exhaust fan drives are fixed-pitch, non-adjustable selections, for

maximum reliability and long belt life. If the factory drive sets

must be changed to obtain other fan speeds, consult the nearest

Browning Manufacturing Co. sales office with the required new

wheel speed and the data from Physical Data and Supply Fan

Drive Data tables (center distances, motor and fan shaft diame-

ters, motor horsepower) in Installation Instructions for a modi-

fied drive set selection. For minor speed changes, the fan sheave

size should be changed. (Do not reduce the size of the motor

sheave; this will result in reduced belt horsepower ratings and

reduced belt life.) See page 128 for belt installation procedure.

Controls —

Use the following steps for the controls:

1. Set any control configurations that are required (field-

installed accessories, etc.). The unit is factory configured

for all appropriate factory-installed options.

2. Enter unit set points. The unit is shipped with the set point

default values. If a different set point is required, use the

scrolling marquee, Navigator display, ComfortVIEW™

software or Service Tool to change the configuration

values.

3. If the internal time schedules are going to be used, config-

ure the Occupancy schedule.

4. Verify that the control time periods programmed meet

current requirements.

5. Start unit using Service Test mode to verify operation of

all major components.

6. If the unit is a VAV unit make sure to configure the static

pressure set point. To check out the VFD, use the VFD in-

structions shipped with the unit.

Gas Heat —

Verify gas pressure before turning on gas heat

as follows:

1. Turn off field-supplied manual gas stop, located external

to the unit.

2. Connect pressure gages to supply gas tap, located at field-

supplied manual shutoff valves.

3. Connect pressure gages to manifold pressure tap on unit

gas valve.

4. Supply gas pressure must not exceed 13.5 in. wg. Check

pressure at field-supplied shut-off valve.

5. Turn on manual gas stop and initiate a heating demand.

Jumper R to W1 in the control box to initiate heat.

6. Use the Service Test procedure to verify heat operation.
7. After the unit has run for several minutes, verify that

incoming pressure is 5.0 in. wg or greater and that the

manifold pressure is 3.5 in wg. If manifold pressure must

be adjusted refer to Gas Valve Adjustment section.

IMPORTANT: The computer system software

(ComfortVIEW™, Service Tool, etc.) that is used to

interact with CCN controls always saves a template of

items it considers as static (e.g., limits, units, forcibil-

ity, 24-character text strings, and point names) after

the software uploads the tables from a control. There-

after, the software is only concerned with run time

data like value and hardware/force status. With this in

mind, it is important that anytime a change is made to

the Service-Config table “generics” (which in turn

changes the points contained in the GENERIC point

table), that a complete new upload be performed. This

requires that any previous table database be

completely removed first. Failure to do this will not

allow the user to display the new points that have been

created and the software will have a different table

database than the unit control.

IMPORTANT: Do not attempt to start unit, even

momentarily, until all items on the Start-Up Checklist

(in installation instructions) and the following steps

have been completed.

IMPORTANT: Unit power must be on for 24 hours

prior to start-up of compressors. Otherwise damage to

compressors may result.

Advertising