Appendix a — local display tables (cont), Mode — configuration (cont) – Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 138

138
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN POINT
DEFAULT
PAGE NO.
EDT.R
EVAP.DISCHRGE TEMP RESET
→
RS.CF
EDT Reset Configuration
0 - 3 (multi-text strings)
EDRSTCFG
2
46,47
→
RTIO
Reset Ratio
0 - 10
RTIO
3
46,47
→
LIMT
Reset Limit
0 - 20
deltaF
LIMT
10
46,47
→
RES.S
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
46,47
HEAT
HEATING CONFIGURATION
→
HT.CF
Heating Control Type
0 - 4
HEATTYPE
0
54,55
→
HT.SP
Heating Supply Air Setpt
80 - 120
dF
SASPHEAT
85
54,55
→
OC.EN
Occupied Heating Enabled
Yes/No
HTOCCENA
No
54,55
→
LAT.M
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
54,55
→
SG.CF
STAGED GAS CONFIGS
→
SG.CF
→
HT.ST
Staged Gas Heat Type
0 - 4
HTSTGTYP
0
54,57,58
→
SG.CF
→
CAP.M
Max Cap Change per Cycle
5 - 45
HTCAPMAX
45
54,57,58
→
SG.CF
→
M.R.DB
S.Gas DB min.dF/PID Rate
0 - 5
HT_MR_DB
0.5
54,57,58
→
SG.CF
→
S.G.DB
St.Gas Temp. Dead Band
0 - 5
^F
HT_SG_DB
2
54,57,58
→
SG.CF
→
RISE
Heat Rise dF/sec Clamp
0.05 - 0.2
HTSGRISE
0.06
54,57,58
→
SG.CF
→
LAT.L
LAT Limit Config
0 - 20
^F
HTLATLIM
10
54,57,58
→
SG.CF
→
LIM.M
Limit Switch Monitoring?
Yes/No
HTLIMMON
Yes
54,57,58
→
SG.CF
→
SW.H.T
Limit Switch High Temp
110 - 180
dF
HT_LIMHI
170
54,57,58
→
SG.CF
→
SW.L.T
Limit Switch Low Temp
100 - 170
dF
HT_LIMLO
160
54,57,58
→
SG.CF
→
HT.P
Heat Control Prop. Gain
0 - 1.5
HT_PGAIN
1
54,57,58
→
SG.CF
→
HT.D
Heat Control Derv. Gain
0 - 1.5
HT_DGAIN
1
54,58
→
SG.CF
→
HT.TM
Heat PID Rate Config
60 - 300
sec
HTSGPIDR
90
54,58
→
HH.CF
HYDRONIC HEAT CONFIGS
→
HH.CF
→
HW.P
Hydronic Ctl.Prop. Gain
0 - 1.5
HW_PGAIN
1
54,57
→
HH.CF
→
HW.I
Hydronic Ctl.Integ. Gain
0 - 1.5
HW_IGAIN
1
54,57
→
HH.CF
→
HW.D
Hydronic Ctl.Derv. Gain
0 - 1.5
HW_DGAIN
1
54,57
→
HH.CF
→
HW.TM
Hydronic PID Rate Config
15 - 300
sec
HOTWPIDR
90
54,57
→
HH.CF
→
ACT.C
HYDR.HEAT ACTUATOR CFGS.
→
HH.CF
→
ACTC
→
SN.1
Hydronic Ht.Serial Num.1
0 - 255
HTCL_SN1
0
54,57
→
HH.CF
→
ACTC
→
SN.2
Hydronic Ht.Serial Num.2
0 - 255
HTCL_SN2
0
54,57
→
HH.CF
→
ACTC
→
SN.3
Hydronic Ht.Serial Num.3
0 - 255
HTCL_SN3
0
54,57
→
HH.CF
→
ACTC
→
SN.4
Hydronic Ht.Serial Num.4
0 - 255
HTCL_SN4
0
54,57
→
HH.CF
→
ACTC
→
SN.5
Hydronic Ht.Serial Num.5
0 - 255
HTCL_SN5
0
54,57
→
HH.CF
→
ACTC
→
C.A.LM
Hydr.Ht.Ctl.Ang.Lo Limit
0-90
HTCLCALM
85
54,57
SP
SUPPLY STATIC PRESS.CFG.
→
SP.CF
Static Pressure Config
0-2 (multi-text strings)
STATICFG
0
62
→
SP.S
Static Pressure Sensor
Enable/Disable
SPSENS
Disable
62
→
SP.LO
Static Press. Low Range
-10 - 0
SP_LOW
0
62
→
SP.HI
Static Press. High Range
0 - 10
SP_HIGH
5
62
→
SP.SP
Static Pressure Setpoint
0 - 5
SPSP
1.5
62
→
SP.MN
VFD-IGV Minimum Speed
0 - 100
STATPMIN
20
62
→
SP.MX
VFD-IGV Maximum Speed
0 - 100
STATPMAX
100
62
→
SP.FS
VFD-IGV Fire Speed Over.
0 - 100
STATPFSO
100
62
→
SP.RS
Stat. Pres. Reset Config
0 - 4
(multi-text strings)
SPRSTCFG
0
62
→
SP.RT
SP Reset Ratio
0.00 - 2.00
SPRRATIO
0.20
62
→
SP.LM
SP Reset Limit
0.00 - 2.00
SPRLIMIT
0.75
62
→
SP.EC
SP Reset Econo. Position
0 - 100
%
ECONOSPR
5
62,63
→
S.PID
STAT.PRESS.PID CONFIGS
→
S.PID
→
SP.TM
Stat.Pres.PID Run Rate
5 - 120
SPIDRATE
15
62,63
→
S.PID
→
SP.P
Static Press. Prop. Gain
0 - 5
STATP_PG
0.5
62,63
→
S.PID
→
SP.I
Static Pressure Intg. Gain
0 - 2
STATP_IG
0.5
62,63
→
S.PID
→
SP.D
Static Pressure Derv. Gain
0 - 5
STATP_DG
0.3
62,63
→
ACT.C
IGV ACTUATOR CONFIGS
→
ACTC
→
SN.1
IGV Serial Number 1
0 - 255
IGV_SN1
0
62,63
→
ACTC
→
SN.2
IGV Serial Number 2
0 - 255
IGV_SN2
0
62,63
→
ACTC
→
SN.3
IGV Serial Number 3
0 - 255
IGV_SN3
0
62,63
→
ACTC
→
SN.4
IGV Serial Number 4
0 - 255
IGV_SN4
0
62,63
→
ACTC
→
SN.5
IGV Serial Number 5
0 - 255
IGV_SN5
0
62,63
→
ACTC
→
C.A.LM
IGV Cntrl Angle Lo Limit
0-90
IGV_CALM
25
62,63
ECON
ECONOMIZER CONFIGURATION
→
EC.EN
Economizer Installed?
Yes/No
ECON_ENA
Yes
65,66
→
EC2.E
Econ.Act.2 Installed?
Yes/No
ECON_TWO
No
65,66
→
EC.MN
Economizer Min.Position
0 - 100
%
ECONOMIN
5
65,66
→
EC.MX
Economizer Max.Position
0 - 100
%
ECONOMAX
98
65,66
→
E.TRM
Economzr Trim For SumZ ?
Yes/No
ECONTRIM
Yes
65,66
→
E.SEL
Econ ChangeOver Select
0 - 3 (multi-text strings)
ECON_SEL
0
66
→
OA.E.C
OA Enthalpy ChgOvr Selct
1 - 5 (multi-text strings)
OAEC_SEL
4
66
→
OA.EN
Outdr.Enth Compare Value
18 - 28
OAEN_CFG
24
66
→
OAT.L
High OAT Lockout Temp
-40 - 120
dF
OAT_LOCK
60
66
→
O.DEW
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
66,67
→
ORH.S
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
66
→
CFM.C
OUTDOOR AIR CFM CONTROL
→
CFM.C
→
OCF.S
Outdoor Air CFM Sensor
Enable/Disable
OCFMSENS
Disable
66,68
→
CFM.C
→
O.C.MX
Economizer Min.Flow
0 - 20000
CFM
OACFMMAX
2000
66,68
→
CFM.C
→
O.C.MN
IAQ Demand Vent Min.Flow
0 - 20000
CFM
OACFMMIN
0
66,68
→
CFM.C
→
O.C.DB
Econ.Min.Flow Deadband
200 - 1000
CFM
OACFM_DB
400
66,68
→
E.CFG
ECON.OPERATION CONFIGS
→
E.CFG
→
E.P.GN
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
66
→
E.CFG
→
E.RNG
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
66
→
E.CFG
→
E.SPD
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
66
→
E.CFG
→
E.DBD
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
66
→
UEFC
UNOCC.ECON.FREE COOLING
→
UEFC
→
FC.CF
Unoc Econ Free Cool Cfg
0-2 (multi-text strings)
UEFC_CFG
0
66,68
→
UEFC
→
FC.TM
Unoc Econ Free Cool Time
0 - 720
min
UEFCTIME
120
66,68
→
UEFC
→
FC.L.O
Un.Ec.Free Cool OAT Lock
40 - 70
dF
UEFCNTLO
50
66,68
→
ACT.C
ECON.ACTUATOR CONFIGS
→
ACTC
→
SN.1.1
Econ Serial Number 1
0 - 255
ECON_SN1
0
66,67
→
ACTC
→
SN.1.2
Econ Serial Number 2
0 - 255
ECON_SN2
0
66,67
→
ACTC
→
SN.1.3
Econ Serial Number 3
0 - 255
ECON_SN3
0
66,67
→
ACTC
→
SN.1.4
Econ Serial Number 4
0 - 255
ECON_SN4
0
66,67
→
ACTC
→
SN.1.5
Econ Serial Number 5
0 - 255
ECON_SN5
0
66,67
→
ACTC
→
C.A.L1
Econ Ctrl Angle Lo Limit
0 - 90
ECONCALM
85
66
→
ACTC
→
SN.2.1
Econ 2 Serial Number 1
0 - 255
ECN2_SN1
0
66,67
→
ACTC
→
SN.2.2
Econ 2 Serial Number 2
0 - 255
ECN2_SN2
0
66,67
→
ACTC
→
SN.2.3
Econ 2 Serial Number 3
0 - 255
ECN2_SN3
0
66,67
→
ACTC
→
SN.2.4
Econ 2 Serial Number 4
0 - 255
ECN2_SN4
0
66,67
→
ACTC
→
SN.2.5
Econ 2 Serial Number 5
0 - 255
ECN2_SN5
0
66,67
→
ACTC
→
C.A.L2
Ecn2 Ctrl Angle Lo Limit
0 - 90
ECN2CALM
85
66