VAV Cool Mode Selection during the Occupied Period

(C.TYP = 1,2 and Operating Modes

MODE

OCC =ON)

— There is no difference in the selection of a cooling mode for

either VAV-RAT or VAV-SPT in the occupied period. The actual

selection of a cool mode, for both control types, is based upon

the controlling return-air temperature (Temperatures

AIR.T

CTRL

R.TMP). Typically this is the same as the re-

turn air temperature thermistor (Temperatures

AIR.T

RAT)

except when under CCN Linkage.
VAV Occupied Cool Mode Evaluation Configuration — There

are VAV occupied cooling offsets under Setpoints.

Cool Mode Determination — If the machine control type

(Configuration

UNIT

C.TYP) = 1 (VAV-RAT) or 2 (VAV-

SPT) and the control is occupied (Operating Modes

MODE

OCC=ON), then the unit will not follow the occu-

pied cooling set point (OCSP). Instead, the control will follow

two offsets in the determination of an occupied VAV cooling

mode (Setpoints

V.C.ON and Setpoints

V.C.OF), applying

them to the low-heat off trip point and comparing the resulting

temperature to the return-air temperature.

The Setpoints

V.C.ON (VAV cool mode on offset) and

Setpoints

V.C.OF (VAV cool mode off offset) offsets are

used in conjunction with the low heat mode off trip point to

determine when to bring cooling on and off and in enforcing a

true “vent” mode between heating and cooling. See Fig. 5. The

occupied cooling set point is not used in the determination of

the cool mode. The occupied cooling set point is used for sup-

ply air reset only.

The advantage of this offset technique is that the control can

safely enforce a vent mode without worrying about crossing set

points. Even more importantly, under CCN linkage, the

occupied heating set point may drift up and down and as such

this technique of using offsets ensures a guaranteed separation

in degrees F between the calling out of a heating or cooling

mode at all times.
NOTE: There is a sub-menu at the local display (Run Status

TRIP) that allows the user to see the exact trip points for

both the heating and cooling modes without having to calcu-

late them. Refer to the Cool Mode Diagnostic Help section on

page 50 for more information.

To enter into a VAV Occupied Cool mode, the controlling

temperature must rise above [OHSP minus L.H.ON plus

L.H.OF plus V.C.ON].

To exit out of a VAV Occupied Cool Mode, the controlling

temperature must fall below [OHSP minus L.H.ON plus

L.H.OF plus V.C.ON minus V.C.OF].

NOTE: With vent mode, it is possible to exit out of a cooling

mode during the occupied period if the return-air temperature

drops low enough. When supply-air temperature reset is not

configured, this capability will work to prevent over-cooling

the space during the occupied period.
Supply Air Set Point Control and the Staging of Compressors

— Once the control has determined that a cooling mode is in

effect, the cooling control point (Run Status

VIEW

CL.C.P) is calculated and is based upon the supply air set

point (Setpoints

SASP) plus any supply air reset being

applied (Inputs

RSET

SA.S.R).

Refer to the SumZ Cooling Algorithm section on page 50

for a discussion of how the Z Series ComfortLink™ controls

manage the staging of compressors to maintain supply-air

temperature.
VAV Cool Mode Selection during the Unoccupied Period

(C.TYP = 1,2; Operating Modes

MODE

OCC=OFF)

and Space Sensor Cool Mode Selection (C.TYP=5 & 6) —

The machine control types that utilize this technique of mode

selection are:
C.TYP = 1 (VAV-RAT) in the unoccupied period

C.TYP = 2 (VAV-SPT) in the unoccupied period

C.TYP = 5 (SPT-MULTI) in both the occupied and

unoccupied period

C.TYP = 6 (SPT- 2 STG) in both the occupied and

unoccupied period
These particular control types operate differently than the

VAV types in the occupied mode in that there is both a LOW

COOL and a HIGH COOL mode. For both of these modes, the

control offers two independent set points, Setpoints

SA.LO

(for LOW COOL mode) and Setpoints

SA.HI (for HIGH

COOL mode). The occupied and unoccupied cooling set points

can be found under Setpoints.

The heat/cool set point offsets are found under Configura-

tion

D.LV.T. See Table 38.

Table 38 — Cool/Heat Set Point Offsets Configuration

ITEM

EXPANSION RANGE UNITS

CCN

POINT

DEFAULT

V.C.ON

VAV Occ.
Cool On Delta

0-25

deltaF VAVOCON 3.5

V.C.OF

VAV Occ.
Cool Off Delta

1-25

deltaF VAVOCOFF 2

ITEM

EXPANSION RANGE UNITS

CCN

POINT

DEFAULT

OCSP

Occupied
Cool Setpoint

55-80

dF

OCSP

75

UCSP

Unoccupied
Cool Setpoint

75-95

dF

UCSP

90

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

DEFAULT

D.LV.T

COOL/HEAT SETPT. OFFSETS

L.H.ON

Dmd Level Lo Heat On

-1 - 2

^F

DMDLHON

1.5

H.H.ON

Dmd Level(+) Hi Heat On

0.5 - 20.0

^F

DMDHHON

0.5

L.H.OF

Dmd Level(-) Lo Heat Off

0.5 - 2.0

^F

DMDLHOFF

1

L.C.ON

Dmd Level Lo Cool On

-1 - 2

^F

DMDLCON

1.5

H.C.ON

Dmd Level(+) Hi Cool On

0.5 - 20.0

^F

DMDHCON

0.5

L.C.OF

Dmd Level(-) Lo Cool Off

0.5 - 2

^F

DMDLCOFF

1

C.T.LV

Cool Trend Demand Level

0.1 - 5

^F

CTRENDLV

0.1

H.T.LV

Heat Trend Demand Level

0.1 - 5

^F

HTRENDLV

0.1

C.T.TM

Cool Trend Time

30 - 600

sec

CTRENDTM

120

H.T.TM

Heat Trend Time

30 - 600

sec

HTRENDTM

120

L.H.OF
DMDLHOFF

L.H.ON
DMDLHON

V.C. ON
VAVOCON

V.C. OF
VAVOCOFF

OHSP

Fig. 5 — VAV Occupied Period Trip Logic

a48-8414