APPENDIX C — UNIT STAGING TABLES (cont)
STAGING SEQUENCE — SIZE 070 AND 075 UNITS
LEGEND
STAGING SEQUENCE — SIZE 090 UNITS
LEGEND
STAGING SEQUENCE — SIZE 105 UNITS
LEGEND
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
1
0
0
0
0
0
14%
2
1
1
0
0
0
0
0
0
29%
3
1
0
0
0
0
0
0
0
43%
4
1
1
1
0
1
1
0
0
51%
5
1
1
0
0
1
1
0
0
66%
6
1
1
1
0
1
0
0
0
71%
7
1
1
0
0
1
0
0
0
86%
8
1
0
0
0
1
0
0
0
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
1
0
19%
2
1
1
1
0
1
1
1
0
33%
3
1
1
0
0
1
1
1
0
48%
4
1
1
1
0
1
1
0
0
51%
5
1
1
0
0
1
1
0
0
66%
6
1
1
1
0
1
0
0
0
71%
7
1
1
0
0
1
0
0
0
86%
8
1
0
0
0
1
0
0
0
100%
0 — Off
a,b — Compressor Circuit Designation
1 — On
u
— Unloader
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
1
0
0
0
0
0
17%
2
1
1
0
0
0
0
0
0
33%
3
1
0
0
0
0
0
0
0
50%
4
1
0
0
0
1
1
1
0
67%
5
1
0
0
0
1
1
0
0
83%
6
1
0
0
0
1
0
0
0
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
1
0
17%
2
0
0
0
0
1
1
0
0
33%
3
0
0
0
0
1
0
0
0
50%
4
1
1
1
0
1
0
0
0
67%
5
1
1
0
0
1
0
0
0
83%
6
1
0
0
0
1
0
0
0
100%
0 — Off
a,b — Compressor Circuit Designation
1 — On
u
— Unloader
CIRCUIT A
STAGE
COMPRESSOR OR UNLOADER
PERCENT
a1
u1
u2
a2
b1
u3
u4
b2
Lead
0
0
0
0
0
0
0
0
0
0%
1
1
1
0
0
0
0
0
0
20%
2
1
0
0
0
0
0
0
0
30%
3
1
1
0
1
0
0
0
0
40%
4
1
0
0
1
0
0
0
0
50%
5
1
1
0
1
1
1
0
0
60%
6
1
0
0
1
1
1
0
0
70%
7
1
0
0
1
1
0
0
0
80%
8
1
0
0
1
1
1
0
1
90%
9
1
0
0
1
1
0
0
1
100%
Lag
0
0
0
0
0
0
0
0
0
0%
1
0
0
0
0
1
1
0
0
20%
2
0
0
0
0
1
0
0
0
30%
3
0
0
0
0
1
1
0
1
40%
4
0
0
0
0
1
0
0
1
50%
5
1
1
0
0
1
1
0
1
60%
6
1
1
0
0
1
0
0
1
70%
7
1
0
0
0
1
0
0
1
80%
8
1
1
0
1
1
0
0
1
90%
9
1
0
0
1
1
0
0
1
100%
0 — Off
a,b — Compressor Circuit Designation
1 — On
u
— Unloader