Sensor trim configuration, Discrete switch logic configuration – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 81

Advertising
background image

81

Table 64 — Alert Limit Configuration

Supply Duct Pressure High Alert Limit (SP.H) — If the unit

is a VAV unit with a supply duct pressure sensor and the mea-

sured supply duct static pressure is above the configurable SP

High Alert Limit (SP.H), then Alert 311 will occur. The unit

will continue to run and the alert will automatically reset.
Building Pressure Low Alert Limit (BP.L) — If the unit is

configured to use modulating power exhaust then a building

static pressure limit can be configured using the BP Low Alert

Limit (BP.L). If the measured pressure is below the limit then

Alert 312 will occur.
Building Pressure High Alert Limit (BP.H) — If the unit is

configured to use modulating power exhaust then a building

static pressure limit can be configured using the BP Hi Alert

Limit (BP.H). If the measured pressure is above the limit, then

Alert 313 will occur.
Indoor Air Quality High Alert Limit (IAQ.H) — If the unit

is configured to use a CO

2

sensor and the level is above the

configurable IAQ High Alert Limit (IAQ.H) then the alert will

occur. The unit will continue to run and the alert will automati-

cally reset.

Sensor Trim Configuration —

The TRIM submenu

is used to calibrate the sensor trim settings. The trim settings

are used when the actual measured reading does not match the

sensor output. The sensor can be adjusted to match the actual

measured reading with the trim function. A list is shown in

Table 65.

Air Temperature Leaving Supply Fan Sensor (SAT.T) — This

variable is used to adjust the supply fan temperature sensor

reading. The sensor reading can be adjusted ± 10° F to match

the actual measured temperature.
Return Air Temperature Sensor Trim (RAT.T) — This vari-

able is used to adjust the return air temperature sensor reading.

The sensor reading can be adjusted ± 10° F to match the actual

measured temperature.
Outdoor Air Temperature Sensor Trim (OAT.T) — This vari-

able is used to adjust the outdoor air temperature sensor read-

ing. The sensor reading can be adjusted ± 10° F to match the

actual measured temperature.

Space Temperature Sensor Trim (SPT.T) — This variable is

used to adjust the space temperature sensor reading. The sensor

reading can be adjusted ± 10° F to match the actual measured

temperature.
Limit Switch Trim (L.SW.T) — This variable is used to ad-

just the limit switch temperature sensor reading. The sensor

reading can be adjusted ± 10° F to match the actual measured

temperature.
Air Temperature Leaving Evaporator Trim (CCT.T) — This

variable is used to adjust the leaving evaporator temperature

sensor reading. The sensor reading can be adjusted ± 10° F to

match the actual measured temperature.
Suction Pressure Circuit A Trim (SP.A.T) — This variable is

used to adjust the suction pressure sensor reading for circuit A.

The sensor reading can be adjusted ± 50 psig to match the actu-

al measured pressure.
Suction Pressure Circuit B Trim (SP.B.T) — This variable is

used to adjust the suction pressure sensor reading for circuit B.

The sensor reading can be adjusted ± 50 psig to match the actu-

al measured pressure.
Discharge Pressure Circuit A Trim (DP.A.T) — This vari-

able is used to adjust the discharge pressure sensor reading for

circuit A. The sensor reading can be adjusted ± 50 psig to

match the actual measured pressure.
Discharge Pressure Circuit B Trim (DP.B.T) — This vari-

able is used to adjust the discharge pressure sensor reading for

circuit B. The sensor reading can be adjusted ±50 psig to match

the actual measured pressure.
4 to 20 mA Inputs — There are a number of 4 to 20 mA in-

puts which may be calibrated. These inputs are located in

Inputs

4-20. They are:

SP.M.T — static pressure milliamp trim

BP.M.T — building pressure milliamp trim

OA.M.T — outside air cfm milliamp trim

RA.M.T — return air cfm milliamp trim

SA.M.T — supply air cfm milliamp trim

Discrete Switch Logic Configuration —

The SW.LG

submenu is used to configure the normally open/normally closed

settings of switches and inputs. This is used when field-supplied

switches or input devices are used instead of Carrier devices. The

normally open or normally closed setting may be different on a

field-supplied device. These points are used to match the control

logic to the field-supplied device.

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

SP.L.O

SPT lo alert limit/occ

-10-245

dF

SPLO

60

SP.H.O

SPT hi alert limit/occ

-10-245

dF

SPHO

85

SP.L.U

SPT lo alert limit/unocc

-10-245

dF

SPLU

45

SP.H.U

SPT hi alert limit/unocc

-10-245

dF

SPHU

100

SA.L.O

EDT lo alert limit/occ

-40-245

dF

SALO

40

SA.H.O

EDT hi alert limit/occ

-40-245

dF

SAHO

100

SA.L.U

EDT lo alert limit/unocc

-40-245

dF

SALU

40

SA.H.U

EDT hi alert limit/unocc

-40-245

dF

SAHU

100

RA.L.O

RAT lo alert limit/occ

-40-245

dF

RALO

60

RA.H.O

RAT hi alert limit/occ

-40-245

dF

RAHO

90

RA.L.U

RAT lo alert limit/unocc

-40-245

dF

RALU

40

RA.H.U

RAT hi alert limit/unocc

-40-245

dF

RAHU

100

OAT.L

OAT lo alert limit

-40-245

dF

OATL

-40

OAT.H

OAT hi alert limit

-40-245

dF

OATH

150

R.RH.L

RARH low alert limit

0-100

%

RRHL

0

R.RH.H

RARH high alert limit

0-100

%

RRHH

100

O.RH.L

OARH low alert limit

0-100

%

ORHL

0

O.RH.H

OARH high alert limit

0-100

%

ORHH

100

SP.L

SP low alert limit

0-5

"H2O

SPL

0

SP.H

SP high alert limit

0-5

"H2O

SPH

2

BP.L

BP lo alert limit

-0.25-0.25

"H2O

BPL

-0.25

BP.H

BP high alert limit

-0.25-0.25

"H2O

BPH

0.25

IAQ.H

IAQ high alert limit

0-5000

IAQH

1200

IMPORTANT: Sensor trim must not be used to extend

unit operation past the allowable operating range.

Doing so may void the warranty.