Table 82 — CCN/Linkage Display Table

Table 83 — Compressor Run Hours Display Table

Table 84 — Compressor Starts Display Table

Table 85 — Software Version Numbers Display Table

Alarms and Alerts —

There are a variety of different

alerts and alarms in the system.

T — Alert: Part of the unit is down, but the unit is still par-

tially able to provide cooling or heating.

A — Alarm: The unit is down and is unable to provide cool-

ing or heating.

All alarms are displayed with a code of AXXX or TXXX

where XXX is the alarm/alert number. All alerts start with “T”

and all alarms start with “A”. The response of the control sys-

tem to various alerts and alarms depends on the seriousness of

the particular alert or alarm. In the mildest case, an alert does

not affect the operation of the unit in any manner.

In addition, the compressors have several diagnostics

monitoring the safety of the system which may cause a

number of attempts to be re-tried before locking out the system

from operation. This feature reduces the likelihood of false

alarms causing a properly working system to be shutdown in-

correctly.

For the compressor and circuit diagnostics, some of these

alerts/alarms will not broadcast an initial failure to the CCN

network until all attempts to recover have occurred and failed.

These alerts will be accessible in the alarm history of the

control (Alarms

HIST).

All the alarms and alerts are summarized in Table 86.

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

LINK

CCN - LINKAGE

MODE

Linkage Active - CCN

ON/OFF

MODELINK

L.Z.T

Linkage Zone Control Tmp

dF

LZT

L.C.SP

Linkage Curr. Cool Setpt

dF

LCSP

L.H.SP

Linkage Curr. Heat Setpt

dF

LHSP

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

HRS

COMPRESSOR RUN HOURS

HR.A1

Compressor A1 Run Hours

0-999999

HRS

HOURS_A1 config

HR.A2

Compressor A2 Run Hours

0-999999

HRS

HOURS_A2 config

HR.B1

Compressor B1 Run Hours

0-999999

HRS

HOURS_B1 config

HR.B2

Compressor B2 Run Hours

0-999999

HRS

HOURS_B2 config

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

STRT

COMPRESSOR STARTS

ST.A1

Compressor A1 Starts

0-999999

CY_A1

config

ST.A2

Compressor A2 Starts

0-999999

CY_A2

config

ST.B1

Compressor B1 Starts

0-999999

CY_B1

config

ST.B2

Compressor B2 Starts

0-999999

CY_B2

config

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

VERS

SOFTWARE VERSION NUMBERS

MBB

CESR131292-xx-xx

string

RCB

CESR131249-xx-xx

string

ECB

CESR131249-xx-xx

string

SCB

CESR131226-xx-xx

string

CEM

CESR131174-xx-xx

string

ECON

xx-xx-xxx-xxx-xx

string

IGV

xx-xx-xxx-xxx-xx

string

HUMD

xx-xx-xxx-xxx-xx

string

HEAT

xx-xx-xxx-xxx-xx

string

BP1

xx-xx-xxx-xxx-xx

string

BP2

xx-xx-xxx-xxx-xx

string

MARQ

CESR131171-xx-xx

string

NAVI

CESR130227-xx-xx

string