Appendix b — ccn tables (cont), Appendix c — unit staging tables, Time schedule config table – Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 156: Staging sequence — size 035 units

Advertising
background image

156

APPENDIX B — CCN TABLES (cont)

TIME SCHEDULE CONFIG TABLE

Allowable Entries: Day not selected = 0 Day selected = 1

APPENDIX C — UNIT STAGING TABLES

STAGING SEQUENCE — SIZE 030 UNITS — 60 Hz

LEGEND

STAGING SEQUENCE — SIZE 030 UNITS — 50 Hz

LEGEND

STAGING SEQUENCE — SIZE 035 UNITS

LEGEND

DAY FLAGS

MTWTFSSH

OCCUPIED

TIME

UNOCCUPIED

TIME

Period 1:

00000000

00:00

00:00

Period 2:

00000000

00:00

00:00

Period 3:

00000000

00:00

00:00

Period 4:

00000000

00:00

00:00

Period 5:

00000000

00:00

00:00

Period 6:

00000000

00:00

00:00

Period 7:

00000000

00:00

00:00

Period 8:

00000000

00:00

00:00

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

1

0

0

0

0

0

16%

2

1

1

0

0

0

0

0

0

32%

3

1

0

0

0

0

0

0

0

50%

4

1

0

0

0

1

1

1

0

66%

5

1

0

0

0

1

1

0

0

82%

6

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

1

0

16%

2

0

0

0

0

1

1

0

0

32%

3

0

0

0

0

1

0

0

0

50%

4

1

1

1

0

1

0

0

0

66%

5

1

1

0

0

1

0

0

0

82%

6

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

0

0

0

0

0

0

29%

2

1

1

0

0

1

1

1

0

43%

3

1

1

0

0

1

1

0

0

57%

4

1

0

0

0

1

1

1

0

71%

5

1

0

0

0

1

1

0

0

85%

6

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

1

0

14%

2

0

0

0

0

1

1

0

0

28%

3

1

1

0

0

1

1

1

0

43%

4

1

1

0

0

1

1

0

0

57%

5

1

0

0

0

1

1

1

0

71%

6

1

0

0

0

1

1

0

0

85%

7

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

CIRCUIT A

STAGE

COMPRESSOR OR UNLOADER

PERCENT

a1

u1

u2

a2

b1

u3

u4

b2

Lead

0

0

0

0

0

0

0

0

0

0%

1

1

1

1

0

0

0

0

0

14%

2

1

1

0

0

0

0

0

0

28%

3

1

1

1

0

1

1

0

0

43%

4

1

1

0

0

1

1

0

0

57%

5

1

1

1

0

1

0

0

0

71%

6

1

1

0

0

1

0

0

0

85%

7

1

0

0

0

1

0

0

0

100%

Lag

0

0

0

0

0

0

0

0

0

0%

1

0

0

0

0

1

1

0

0

29%

2

1

1

1

0

1

1

0

0

43%

3

1

1

0

0

1

1

0

0

57%

4

1

1

1

0

1

0

0

0

71%

5

1

1

0

0

1

0

0

0

85%

6

1

0

0

0

1

0

0

0

100%

0 — Off

a,b — Compressor Circuit Designation

1 — On

u

Unloader

Advertising