APPENDIX B — CCN TABLES

All Z series units with ComtfortLink™ controls have a port

for interface with the Carrier Comfort Network

®

(CCN) sys-

tem. On TB3 there is a J11 jack which can be used for tempo-

rary connection to the CCN network or to computers equipped

with CCN software like the Service Tool. Also on TB3 there

are screw connections that can be used for more permanent

CCN connections.

In the following tables the structure of the tables which are

used with the Service Tool as well as the names and data that are

included in each table are shown. There are several CCN vari-

ables that are not displayed through the scrolling marquee and

are used for more extensive diagnostics and system evaluations.

STATUS DISPLAY TABLES

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

COOLING

HVAC Mode…………..:

ascii text strings

Control Mode………..:

ascii text strings

Current Running Capacity

%

CAPTOTAL

Curr.Calc. Cool Capacity

%

COOLCALC

Current Cool Stage

COOL_STG

Requested Cool Stage

CL_STAGE

Maximum Cool Stages

CLMAXSTG

Cooling Control Point

dF

COOLCPNT

Evaporator Discharge Tmp

dF

EDT

Mixed Air Temperature

dF

MAT

Next capacity step down

%

CAPNXTDN

Next capacity step up

%

CAPNXTUP

COOL_A

Current Cool Stage

COOL_STG

Current Cool Stage A

CLSTAGEA

Cir A Discharge Pressure

PSIG

DP_A

Cir A Suction Pressure

PSIG

SP_A

Cir A Sat.Condensing Tmp

dF

SCTA

Cir A Sat.Suction Temp.

dF

SSTA

Compressor A1 Relay

CMPA1

Unloader 1 - Comp A1

UNL_1_A1

Unloader 2 - Comp A1

UNL_2_A1

Compressor A2 Relay

CMPA2

Compressor A1 Feedback

CSB_A1

Compressor A2 Feedback

CSB_A2

Circ A High Press.Switch

CIRCAHPS

Circuit A Stage Inhibit

CIRAFAIL

COOL_B

Current Cool Stage

COOL_STG

Current Cool Stage B

CLSTAGEB

Cir B Discharge Pressure

PSIG

DP_B

Cir B Suction Pressure

PSIG

SP_B

Cir B Sat.Condensing Tmp

dF

SCTB

Cir B Sat.Suction Temp.

dF

SSTB

Compressor B1 Relay

CMPB1

Unloader 1 - Comp B1

UNL_1_B1

Unloader 2 - Comp B1

UNL_2_B1

Compressor B2 Relay

CMPB2

Compressor B1 Feedback

CSB_B1

Compressor B2 Feedback

CSB_B2

Circ B High Press.Switch

CIRCBHPS

Circuit B Stage Inhibit

CIRBFAIL

ECONDIAG

Economizer Active ?

Yes/No

ECACTIVE

Conditions which prevent
economizer being active:
Econ Act. Unavailable?

Yes/No

ECONUNAV

Econ2 Act. Unavailable

Yes/No

ECN2UNAV

Enth.Switch Read High ?

Yes/No

ENTH

DBC - OAT lockout?

Yes/No

DBC_STAT

DEW - OA Dewpt. lockout?

Yes/No

DEW_STAT

DDBC- OAT > RAT lockout?

Yes/No

DDBCSTAT

OAEC- OA Enth Lockout?

Yes/No

OAECSTAT

DEC - Diff.Enth.Lockout?

Yes/No

DEC_STAT

EDT Sensor Bad ?

Yes/No

EDT_STAT

OAT Sensor Bad ?

Yes/No

OAT_STAT

Economizer forced ?

Yes/No

ECONFORC

Supply Fan not on 30s ?

Yes/No

SFONSTAT

Cool Mode not in effect?

Yes/No

COOL_OFF

OAQ lockout in effect ?

Yes/No

OAQLOCKD

Econ recovery hold off?

Yes/No

ECONHELD

Dehumid. Disabled Econ.?

Yes/No

DHDISABL