Carrier WEATHERMASTER 48/50Z030-105 User Manual

Page 38

Advertising
background image

38

Service Test Mode Logic —

Operation in the Service

Test mode is sub-menu specific except for the INDP sub-

menu. Leaving the sub-menu while a test is being performed

and attempting to start a different test in the new sub-menu will

cause the previous test to terminate. When this happens, the

new request will be delayed for 5 seconds. For example, if

compressors were turned on under the COOL sub-menu, any

attempt to turn on heating stages within the HEAT sub-menu

would immediately turn off the compressors and 5 seconds lat-

er the controller would honor the requested heat stages.

However, it is important to note that the user can leave a

Service Test mode to view any of the local display menus (Run

Status, Temperatures, Pressures, Setpoints, Inputs, Outputs,

Configuration, Time Clock, Operating Modes, and Alarms)

and the control will remain in the Service Test mode.

Independent Outputs —

The INDP sub-menu items

can be turned on and off regardless of the other category states.

For example, the humidifier relay or remote alarm/auxiliary re-

lay can be forced on in the INDP sub-menu and will remain on

if compressor stages were requested in the COOL sub-menu.

Fans —

Upon entering the FANS sub-menu, the user will be

able to enact either a manual or automatic style of test opera-

tion. The first item in the sub-menu, Fan Test Mode Automatic

(Service Test

FANS

F.MOD), allows the fan and the con-

figured static pressure or building pressure control to begin as

in the application run mode. During this automatic mode, it is

possible to manually control condenser fans A and B.

If Fan Test Mode Automatic (Service Test

FANS

F.MOD), is set to NO, then the user will have individual con-

trol over duct static pressure (VFD speed or IGV position),

building pressure and condenser fan control. Additionally, the

controller will protect the system from developing too much

static pressure. If the static pressure during manual control

rises above 3 in. wg or if the Static Pressure Set Point

(Setpoints

SPSP) is greater than 2.5 in. wg and static pres-

sure is 0.5 in. wg higher than SPSP, then all options in the

FANS menu will be cleared back to their default OFF states.

The power exhaust dampers can be individually energized

or together and their damper positions can be forced to any

position.

Actuators —

In the ACT.C sub-menu, it will be possible to

control and calibrate actuators. Calibration is a mode in which

the actuator moves from 0% to the point at which the actuator

stalls, and it will then use this angular travel range as its

“control angle”. It will also be possible to view the “control

angle” adopted by the actuator after a calibration.

Within this sub-menu, the user may calibrate and control

economizer actuators 1 and 2, the inlet guide vane actuator, the

building pressure actuators 1 and 2, the hydronic heating coil

actuator, and the humidifier steam valve control actuator.
NOTE: Once a calibration has been started, the user cannot

exit test mode or select any other test mode operation until

complete.

Cooling —

The cooling sub-menu offers many different

service tests.
Service Test

Cool

E.POS (Econo Damper Command

Pos). It is possible to manually move the actuator during

the cooling test mode at all times, regardless if econo-

mizer cooling is suitable or not.

Service Test

COOL

SP.SP (Static Pressure Setpoint).

Upon entering the cooling sub-menu, the static pressure

control item will default to the unit's static pressure set

point. Thereafter, as mechanical cooling commences and

the fan starts, the static pressure can be manually

adjusted during the cool mode without affecting the con-

figured set point for normal runtime operation. By

adjusting the static pressure set point, the user can

increase or decrease the supply airflow. Do not use a

static pressure that will exceed the system limits.

Service Test

COOL

CL.ST (Requested Cool Stage).

If this item is set to a non-zero value, the current

assigned compression stage for this unit will be selected

and enacted. Thereafter, the individual compressor and

unloaders items will be “read-only” and reflect the cur-

rent staging state. In addition, this item will automati-

cally clamp the cooling stages to its pre-configured

maximum.

Service Test

COOL

LD.LG (Lead/Lag Select Test).

This item may only be adjusted when the cooling stage

pattern request item is set to zero. If the request pattern is

zero, then the user may select whether the cooling stage

request is based on lead or lag staging.

• Manual relay control of individual compressors and

unloaders. If the cooling stage pattern request is set to

zero, the user will have the ability to manually control

compressors and unloaders. If the user energizes

mechanical cooling, the supply fan and the outdoor fans

will be started automatically. During mechanical cooling,

the unit will protect itself. Compressor diagnostics are

active, monitoring for high discharge pressure, low suc-

tion pressure, etc.

Heating —

If unit has a thermostat connected (C.TYP = 3

or 4), install the RED jumper wires between TB202, terminals

R (1), W2 (3) and W1 (4). Terminal block TB202 is located in

the unit control box. Remember to disconnect these jumpers

when Test Mode is completed. The Heat Test Mode sub-menu

will offer automatic fan start-up if not a gas fired heat unit. On

gas heat units, the IGC feedback from the gas control units will

bring the fan on as required.
Within this sub-menu, control of the following is possible:
Service Test

HEAT

HT.ST (Requested Heat Stage).

When this item is non-zero, the currently configured heat

type will energize the corresponding heat relay pattern

that reflects the requested stage. In addition the upper

limit will be clamped to reflect the maximum configured

number of stages. When non-zero, the heat relays will be

“read-only” and reflect the currently selected pattern.

Service Test

HEAT

HT.1-6, Service Test

HEAT

H.I.R (Manual Heat Relay Control). If the “Heat Stage

Request” item is set to zero, it will be possible to individ-

ually control the heat relays, including the heat interlock

relay.

Service Test

HEAT

HTC.C (Ht Coil Command Posi-

tion). If configured for this heat type, the user will be

able to manually control the positioning of the actuator

which controls hot water (0 to 100%).

NOTE: When service test has been completed, if unit has a

thermostat connected (C.TYP = 3 or 4), remove the RED

jumper wires at TB202, terminals R (1), W2 (3) and W1 (4).

Terminal block TB202 is located in the unit control box. Store

these jumpers in the unit control box for future use.

Advertising