Table 67 — Display Configuration

Remote Control Switch Input —

The remote switch

input is located on the RCB board and connected to TB201

terminals 1 and 2. The switch can be used for several remote

control functions. See Table 68.

Table 68 — Remote Switch Configuration

Remote Input State (Inputs

GEN.I

REMT) — This is

the actual real time state of the remote input.
Remote Switch Config (Configuration

UNIT

RM.CF)

— This is the configuration that allows the user to assign dif-

ferent types of functionality to the remote discrete input.
• 0 — NO REMOTE SW — The remote switch will not be

used.

• 1 — OCC-UNOCC SW — The remote switch input will

control the occupancy state. When the remote switch

input is ON, the unit will forced into the occupied mode.

When the remote switch is OFF, the unit will be forced

into the unoccupied mode.

• 2 — STRT/STOP — The remote switch input will start

and stop the unit. When the unit is commanded to stop,

any timeguards in place on compressors will be honored

first. When the remote switch is ON, the unit will be

commanded to stop. When the remote switch is OFF the

unit will be enabled to operate.

• 3 — OVERRIDE SW — The remote switch can be used

to override any internal or external time schedule being

used by the control and force the unit into an occupied

mode when the remote input state is ON. When the

remote switch is ON, the unit will be forced into an occu-

pied state. When the remote switch is OFF, the unit will

use its internal or external time schedules.

Remote Switch Logic Configuration (Configuration

SW.LG

RMI.L) — The control allows for the configuration

of a normally open/closed status of the remote input switch via

RMI.L. If this variable is configured OPEN, then when the

switch is open, the remote input switch perceives the logic state

as OFF. Correspondingly, if RMI.L is set to CLOSED, the re-

mote input switch will perceive a closed switch as meaning

OFF. See Table 69.

Hot Gas Bypass —

Hot gas bypass is an automatically

operating system used to limit evaporator suction pressure

during periods of low evaporator loading. This system is not

controlled by the ComfortLink™ control system and it is

available to operate whenever circuit A is running.

The hot gas bypass option consists of a pressure regulating

valve, a manual service valve and tubing connecting the circuit

A hot gas refrigerant line to the circuit A evaporator distribu-

tors (one distributor on sizes 030-035, two distributors on sizes

040-105). The pressure regulating valve opens the bypass

circuit as the evaporator suction pressure decreases into a range

that might generate frost formation on the evaporator surface

if sustained compressor operation occurs. The hot gas refriger-

ant enters the evaporator coil and adds refrigeration load to the

compressor circuit to offset a low load situation in the mixed

air temperature condition. Total bypass capacity is approxi-

mately 5 tons.

The hot gas bypass system is a factory-installed option,

installed on circuit A only. When this option is provided, the

control function for Lead-Lag sequencing must be disabled

(Configuration

Cool

L.L.EN is set to No).

Space Temperature Offset —

Space Temperature Off-

set corresponds to a slider on a T56 sensor that allows the occu-

pant to adjust the space temperature by a configured range

during an occupied period. This sensor is only applicable to

units that are configured as either 2-Stage SPT or Multi-Stage

SPT control (Configuration

UNIT

C.TYP = 5 and 6).

Space Temperature Offset Sensor (Configuration

UNIT

SENS

SP.O.S) — This configuration disables the reading

of the offset slider.
Space Temperature Offset Range (Configuration

UNIT

SENS

SP.O.R) — This configuration establishes

the range, in degrees F, that the T56 slider can affect SPTO

when adjusting the slider from the far left (-SP.O.R) to the far

right (+SP.O.R). The default is 5° F.
Space Temperature Offset Value (Temperatures

AIR.T

SPTO) — The Space Temperature Offset Value is the read-

ing of the slider potentiometer in the T56 that is resolved to

delta degrees based on SP.O.R.

Table 69 — Remote Switch Logic Configuration

ITEM

EXPANSION

RANGE

UNITS

POINT

DEFAULT

TEST

Test Display LEDs

ON/OFF

TEST

Off

METR

Metric Display

ON/OFF

DISPUNIT

Off

LANG

Language Selection

0-1(multi-text strings)

LANGUAGE

0

PAS.E

Password Enable

ENABLE/DISABLE

PASS_EBL

Enable

PASS

Service Password

0000-9999

PASSWORD

1111

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

REMT

Remote
Input State

ON/OFF

RMTIN

RM.CF

Remote Switch
Config

0 - 3

RMTINCFG

RMI.L

RemSw
Off-Unoc-Strt-NoOv

Open/Close

RMTINLOG

ITEM

EXPANSION

RANGE

UNITS

CCN

POINT

SP.O.S

Space Temp
Offset Sensor

Enable/
Disable

SPTOSENS

SP.O.R

Space Temp
Offset Range

1 - 10

SPTO_RNG

SPTO

Space Temperature
Offset

+- SP.O.R ^F

SPTO

REMOTE

SWITCH LOGIC

CONFIGURATION

(RMI.L)

SWITCH

STATUS

REMOTE INPUT STATE

(REMT)

REMOTE SWITCH CONFIGURATION (RM.CF)

0

1

2

3

No Remote Switch

Occ-Unocc Switch

Start/Stop

Override

OPEN

OPEN

OFF (0)

xxxxx

Unoccupied

Start

No Override

CLOSED

ON (1)

xxxxx

Occupied

Stop

Override

CLOSED

OPEN

ON (0)

xxxxx

Occupied

Stop

Override

CLOSED

OFF (1)

xxxxx

Unoccupied

Start

No Override