Multi-Stage Constant Volume Units with
Space Sensor —

To configure the unit, perform the

following:

1. Under Configuration

UNIT

C.TYP, set C.TYP to 5

(SPT MULTI).

2. Install jumpers between R-W2 and W2-W1.
3. Under the Setpoints menu, the following configurations

should be set:

4. Under the Setpoints submenu, the heating and cooling set

points must be configured:

5. Under Configuration

UNIT

SENS

SPT.S, enable

the space sensor by setting SPT.S to ENBL.

6. Under Configuration

UNIT

CV.FN, set CV.FN to 1

for continuous fan or 0 for automatic fan.

7. To program time schedules, set SCH.N=1 under Config-

uration

CCN

SC.OV

SCH.N to configure the con-

trol to use local schedules.

8. Under the Timeclock

SCH.L submenu, enter the de-

sired schedule. See Time Clock section for further

descriptions of these configurations.

9. See the Economizer Options section below for addition

economizer option configurations.

10. See the Exhaust Options section below for addition

exhaust option configurations.

Economizer Options —

Under the Configuration

ECON submenu, the following set points should be configured:

Configuration

ECON

EC.MN should always be set for

the minimum damper position.

If the unit is equipped with an outdoor air flow station, the

following points in Configuration

ECON

CFM.C need to

be set.

If equipped with an outdoor flow station, make sure

Configuration

ECON

OCF.S is enabled. If an outdoor

air cfm station is used, then the economizer will control to

cfm, not a position, as long as the sensor is valid. Therefore,

Configuration

ECON

O.C.MX supersedes Configura-

tion

ECON

EC.MN.

Indoor Air Quality Options

DEMAND CONTROL VENTILATION — Under Configu-

ration

IAQ

DCV.C, the following configuration parame-

ters should be set to establish the minimum and maximum

points for outdoor air damper position during demand control

ventilation (DCV):

EC.MN

Economizer Min.Position

IAQ.M

IAQ Demand Vent Min.Pos.

O.C.MX

Economizer Min.Flow

O.C.MN

IAQ Demand Vent Min.Flow

Configuration

IAQ

DCV.C

IAQ.M is used to set the

absolute minimum vent position (or maximum reset) under

DCV.

Configuration

IAQ

DCV.C

EC.MN is used to set the

minimum damper position (or with no DCV reset). This is also

referenced in the economizer section.

Configuration

IAQ

DCV.C

O.C.MX is used only

with the outdoor air flow station and will supersede Configura-

tion

IAQ

DCV.C

EC.MN as long as the outdoor air cfm

sensor is valid.

Configuration

IAQ

DCV.C

O.C.MN is used only

with the outdoor air flow station and will supersede Configura-

tion

IAQ

DCV.C

IAQ.M as long as the outdoor air cfm

sensor is valid.

Exhaust Options —

The following exhaust options

should be configured.

LEGEND

*Single VFD controlling both fan motors.

†Single VFD controlling one fan motor and staging the second fan

motor.

Configuration

BP

BF.CF=1

(Two-Stage Exhaust

Option) — For two-stage exhaust, under the Configuration-

BP submenu, configure the following:

SA.HI

Supply Air Set Point Hi

SA.LO

Supply Air Set Point Lo

OHSP

Occupied Heat Setpoint

OCSP

Occupied Cool Setpoint

UHSP

Unoccupied Heat Setpoint

UCSP

Unoccupied Cool Setpoint

GAP

Heat-Cool Setpoint Gap

D.LV.T Cool/Heat Set Point Offsets

EC.EN

Economizer Enabled?

EC2.E

Econ Act.2 Installed?

EC.MN

Economizer Min.Position

EC.MX

Economizer Maximum Position

E.TRM

Economizer Trim for SumZ?

E.SEL

Econ Changeover Select

OA.E.C

OA Enthalpy Change Over Select

OA.EN

Outdoor Enthalpy Compare Value

OAT.L

High OAT Lockout Temp

O.DEW

OA Dew Point Temp Limit

ORH.S

Outside Air RH Sensor

OCF.S

Outdoor Air CFM Sensor

O.C.MX Economizer Minimum Flow
O.C.DB Economizer Minimum Flow Deadband

UNIT

EXHAUST TYPE

Constant

Volume

2-Stage

Modulating

Power

Exhaust

S.O.

VFD*

High-

Capacity

Power

Exhaust†

Return

Exhaust†

48ZG
50ZG,Z2

X

X

S.O.

NA

NA

48ZN
50ZN,Z3

NA

X

S.O.

NA

NA

48ZT,ZW
50ZT,ZW,ZX,ZZ

NA

NA

NA

STD

NA

48Z6,Z8
50Z6,Z7,Z8,Z9

NA

NA

NA

NA

STD

X

Available as Factory Option

S.O. — Available as Special Order
NA

Not Available on this Unit

STD — Standard Feature on this Unit

BP.P1

Power Exhaust On Setp.1

BP.P2

Power Exhaust On Setp.2