93

Table 79 — Economizer Run Status Display Table

Table 80 — Cooling Information Display Table

Table 81 — Mode Trip Helper Display Table

CCN/LINKAGE DISPLAY TABLE — The CCN/Linkage

display table provides information on unit linkage. See Table 82.
COMPRESSOR RUN HOURS DISPLAY TABLE — The

Compressor Run Hours Display Table displays the number of

run time hours for each compressor. See Table 83.

COMPRESSOR STARTS DISPLAY TABLE — The Com-

pressor Starts Display Table displays the number of starts for

each compressor. See Table 84.
SOFTWARE VERSION NUMBERS DISPLAY TABLE —

The Software Version Numbers Display Table displays the

software version numbers of the unit boards and devices. See

Table 85.

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

ECON

ECONOMIZER RUN STATUS

ECN.P

Economizer Act.Curr.Pos.

0-100

%

ECONOPOS

EC2.P

Economzr2 Act.Curr.Pos.

0-100

%

ECON2POS

ECN.C

Economizer Act.Cmd.Pos.

0-100

%

ECONOCMD

forcible

ACTV

Economizer Active ?

YES/NO

ECACTIVE

DISA

ECON DISABLING CONDITIONS

DISAUNV.1

Econ Act. Unavailable?

YES/NO

ECONUNAV

DISAUNV.2

Econ2 Act. Unavailable?

YES/NO

ECN2UNAV

DISAENTH

Enth. Switch Read High ?

YES/NO

ENTH

DISADBC

DBC - OAT Lockout?

YES/NO

DBC_STAT

DISADEW

DEW - OA Dewpt.Lockout?

YES/NO

DEW_STAT

DISADDBC

DDBD- OAT > RAT Lockout?

YES/NO

DDBCSTAT

DISAOAEC

OAEC- OA Enth Lockout?

YES/NO

OAECSTAT

DISADEC

DEC - Diff.Enth.Lockout?

YES/NO

DEC_STAT

DISAEDT

EDT Sensor Bad?

YES/NO

EDT_STAT

DISAOAT

OAT Sensor Bad ?

YES/NO

OAT_STAT

DISAFORC

Economizer Forced ?

YES/NO

ECONFORC

DISASFON

Supply Fan Not On 30s ?

YES/NO

SFONSTAT

DISACLOF

Cool Mode Not In Effect?

YES/NO

COOL_OFF

DISAOAQL

OAQ Lockout in Effect ?

YES/NO

OAQLOCKD

DISAHELD

Econ Recovery Hold Off?

YES/NO

ECONHELD

DISADH.DS

Dehumid. Disabled Econ.?

YES/NO

DHDISABL

O.AIR

OUTSIDE AIR INFORMATION

O.AIROAT

Outside Air Temperature

dF

OAT

forcible

O.AIROA.RH

Outside Air Rel. Humidity

%

OARH

forcible

O.AIROA.E

Outside Air Enthalpy

OAE

O.AIROA.D.T

OutsideAir Dewpoint Temp

dF

OADEWTMP

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

COOL

COOLING INFORMATION

C.CAP

Current Running Capacity

%

CAPTOTAL

CUR.S

Current Cool Stage

COOL_STG

REQ.S

Requested Cool Stage

CL_STAGE

MAX.S

Maximum Cool Stages

CLMAXSTG

DEM.L

Active Demand Limit

%

DEM_LIM

forcible

SUMZ

COOL CAP. STAGE CONTROL

SUMZSMZ

Capacity Load Factor

-100

→ +100

SMZ

SUMZADD.R

Next Stage EDT Decrease

^F

ADDRISE

SUMZSUB.R

Next Stage EDT Increase

^F

SUBRISE

SUMZR.PCT

Rise Per Percent Capacity

RISE_PCT

SUMZY.MIN

Cap Deadband Subtracting

Y_MINUS

SUMZY.PLU

Cap Deadband Adding

Y_PLUS

SUMZZ.MIN

Cap Threshold Subtracting

Z_MINUS

SUMZZ.PLU

Cap Threshold Adding

Z_PLUS

SUMZH.TMP

High Temp Cap Override

HI_TEMP

SUMZL.TMP

Low Temp Cap Override

LOW_TEMP

SUMZPULL

Pull Down Cap Override

PULLDOWN

SUMZSLOW

Slow Change Cap Override

SLO_CHNG

ITEM

EXPANSION

RANGE

UNITS

POINT

WRITE STATUS

TRIP

MODE TRIP HELPER

UN.C.S

Unoccup. Cool Mode Start

UCCLSTRT

UN.C.E

Unoccup. Cool Mode End

UCCL_END

OC.C.S

Occupied Cool Mode Start

OCCLSTRT

OC.C.E

Occupied Cool Mode End

OCCL_END

TEMP

Ctl.Temp RAT,SPT or Zone

CTRLTEMP

OC.H.E

Occupied Heat Mode End

OCHT_END

OC.H.S

Occupied Heat Mode Start

OCHTSTRT

UN.H.E

Unoccup. Heat Mode End

UCHT_END

UN.H.S

Unoccup. Heat Mode Start

UCHTSTRT

HVAC

ascii string spelling out the hvac modes

string