Carrier WEATHERMASTER 48/50Z030-105 User Manual
Page 37

37
Table 31 — Service Test
ITEM
EXPANSION
RANGE
UNITS
POINT
WRITE STATUS
TEST
Service Test Mode
ON/OFF
MAN_CTRL
STOP
Local Machine Disable
YES/NO
UNITSTOP
config
S.STP
Soft Stop Request
YES/NO
SOFTSTOP
forcible
FAN.F
Supply Fan Request
YES/NO
SFANFORC
forcible
INDP
TEST INDEPENDENT OUTPUTS
→HUM.R
Humidifier Relay
ON/OFF
HUMR_TST
→ALRM
Remote Alarm/Aux Relay
ON/OFF
ALRM_TST
FANS
TEST FANS
→F.MOD
Fan Test Automatic?
YES/NO
FANAUTO
→E.POS
Econo Damper Command Pos
%
ECONFANS
→S.FAN
Supply Fan Relay
ON/OFF
SFAN_TST
→I.POS
IGV Actuator Command Pos
0-100
%
IGVFNTST
→S.VFD
Supply Fan VFD Speed
0-100
%
SGVFDTST
→P.E.1
Power Exhaust Relay 1
ON/OFF
PE1_TST
→P.E.2
Power Exhaust Relay 2
ON/OFF
PE2_TST
→BP1.P
BP 1 Command Position
0-100
%
BLDPTST1
→BP2.P
BP 2 Command Position
0-100
%
BLDPTST2
→E.VFD
Exhaust Fan VFD Speed
0-100
%
EFVFDTST
→CD.F.A
Condenser Fan Circuit A
ON/OFF
CNDA_TST
→CD.F.B
Condenser Fan Circuit B
ON/OFF
CNDB_TST
→CD.MM
Motormaster Condenser Fan
ON/OFF
PCFABTST
ACT.C
CALIBRATE TEST-ACTUATORS
→ECN.C
Economizer Act.Cmd.Pos.
0-100
%
ECONOTST
→E.CAL
Economizer Calibrate Cmd
YES/NO
ECONOCAL
→ECN.A
Econ Act. Control Angle
read only
ECONCANG
→EC2.C
Economzr 2 Act.Cmd.Pos.
0-100
%
ECON2TST
→E2.CL
Economzr 2 Calibrate Cmd
YES/NO
ECON2CAL
→EC2.A
Econ2 Act.Control Angle
read only
ECN2CANG
→IGV.C
IGV Actuator Command Pos
0-100
%
SPIGVTST
→I.CAL
IGV Act. Calibrate Cnd
YES/NO
IGV_CAL
→IGV.A
IGV Act. Control Angle
read only
IGC_CANG
→IGV.M
VFD-IGV Maximum Speed
0-100
%
STATPMAX
→BP1.C
BP 1 Command Position
0-100
%
BLDG1TST
→B1.CL
BP 1 Actuator Cal Cmd
YES/NO
BLDG1CAL
→BP1.A
BP Act.1 Control Angle
read only
BP1_CANG
→BP1.M
BP 1 Actuator Max Pos.
0-100
%
BP1SETMX
→BP2.C
BP 2 Command Position
0-100
%
BLDG2TST
→B2.CL
BP 2 Actuator Cal Cmd
YES/NO
BLDG2CAL
→BP2.A
BP Act.2 Control Angle
read only
BP2_CANG
→BP2.M
BP 2 Actuator Max Pos.
0-100
%
BP2SETMX
→HTC.C
Ht.Coil Command Position
0-100
%
HTCLACTC
→HT.CL
Heating Coil Act. Cal.Cmd
YES/NO
HCOILCAL
→HTC.A
Heat Coil Act.Ctl.Angle
read only
HTCLCANG
→HMD.C
Humidifier Command Pos.
0-100
%
HUMD_TST
→HM.CL
Humidifier Act. Cal.Cmd
YES/NO
HUMIDCAL
→HMD.A
Humidifier Act.Ctrl.Ang.
read only
HUMDCANG
COOL
TEST COOLING
→E.POS
Econo Damper Command Pos
0-100
%
ECONCOOL
→SP.SP
Static Pressure Setpoint
0-5
"H2O
SPSP_TST
→CL.ST
Requested Cool Stage
0-n
CLST_TST
→LD.LG
Lead/Lag Select Test
LEAD/LAG
LL_TST
→A1
Compressor A1 Relay
ON/OFF
CMPA1TST
→U1.A1
Unloader 1 - Comp A1
ON/OFF
UNL1_TST
→U2.A1
Unloader 2 - Comp A1
ON/OFF
UNL2_TST
→A2
Compressor A2 Relay
ON/OFF
CMPA2TST
→B1
Compressor B1 Relay
ON/OFF
CMPB1TST
→U1.B1
Unloader 1 - Comp B1
ON/OFF
UNL3_TST
→U2.B1
Unloader 2 - Comp B1
ON/OFF
UNL4_TST
→B2
Compressor B2 Relay
ON/OFF
CMPB2TST
HEAT
TEST HEATING
→HT.ST
Requested Heat Stage
0-n
HTST_TST
→HT.1
Heat Relay 1
ON/OFF
HS1_TST
→HT.2
Heat Relay 2
ON/OFF
HS2_TST
→HT.3
Relay 3 W1 Gas Valve 2
ON/OFF
HS3_TST
→HT.4
Relay 4 W2 Gas Valve 2
ON/OFF
HS4_TST
→HT.5
Relay 5 W1 Gas Valve 3
ON/OFF
HS5_TST
→HT.6
Relay 6 W2 Gas Valve 3
ON/OFF
HS6_TST
→H.I.R
Heat Interlock Relay
ON/OFF
HIR_TST
→HTC.C
Ht.Coil Command Position
0-100
%
HTCLHEAT