Table 3 — Main Base Board Inputs and Outputs

LEGEND

Compressor Protection Module (CPM) —

T

here

is one CPM per compressor. See Fig. 9. The device controls the

compressor contactors, oil solenoid, and loading/unloading the

solenoid. The CPM also monitors the compressor motor tem-

perature, high pressure switch, oil level switch, discharge gas

temperature, oil pressure transducer, motor current, MTA

(must trip amps) setting and economizer pressure transducer

(sizes 175,200,350,400 only). The CPM responds to com-

mands from the MBB (Main Base Board) and sends the MBB

the results of the channels it monitors via the LEN (Local

Equipment Network). The CPM has three DIP switch input

banks, Switch 1 (S1), Switch 2 (S2), and Switch 3 (S3). The

CPM board DIP switch (S1) configures the board for the type

of starter, the location and type of the current transformers and

contactor failure instructions. See Table 4 for description of

DIP switch 1 (S1) inputs. See Appendix D for DIP switch

settings.

DESCRIPTION

INPUT/OUTPUT

I/O TYPE

DISPLAY MODULE POINT NAME

CONNECTION POINT

Pin

Notation

Power (24 vac supply)

MBB-J1, MBB-J1A,

MBB-J1B

11

24 vac

12

Ground

Local Equipment Network

MBB-J9A, MBB-J9B,

MBB-J9C, MBBJ9D

+

RS485 Port (D+)

G

RS485 Port (Gnd)

-

RS485 Port (D-)

Carrier Communication

Network

MBB-J12

+

RS485 Port (D+)

G

RS485 Port (Gnd)

-

RS485 Port (D-)

Chilled Water Flow Switch

CWFS

Switch

Cooler Flow Switch, LOCK

MBB-J5B-CH17

17

Demand Limit Switch No. 1

Demand Limit SW1

Switch

Limit Switch 1 Status, DLS1

MBB-J4-CH13

Condenser Flow Switch

CDFS

Switch

Condenser Flow Switch, COND

16A

MBB-J5A-CH16A

Circuit A Discharge

Pressure Transducer

DPTA

Pressure Transducer

Discharge Pressure, DP.A

MBB-J7A-CH6

5V

+5 vdc Ref.

S

Signal

R

Return

Circuit B Discharge

Pressure Transducer

DPTB

Pressure Transducer

Discharge Pressure, DP.B

MBB-J7C-CH8

5V

+5 vdc Ref.

S

Signal

R

Return

Dual Chiller

LWT Thermistor

DUAL

5k Thermistor

CHWS Temperature, CHWS

MBB-J6-CH3

Dual Set Point Input

Dual Set Point

Switch

Remote Setpoint Switch, DUAL

MBB-J4-CH12

Heat/Cool Switch

HC_SW

Switch

Heat/Cool Select Contact, HC_SW

MBB-J4-CH14

Entering Water Thermistor

EWT

5k Thermistor

Cooler Entering Fluid, EWT

MBB-J6-CH2

Leaving Water Thermistor

LWT

5k Thermistor

Cooler Leaving Fluid, LWT

MBB-J6-CH1

Condenser Entering Water

Thermistor

CEWT

5k Thermistor

Condenser Entering Fluid, CEWT

MBB-J6-CH5

Condenser Leaving Water

Thermistor

CLWT

5k Thermistor

Condenser Leaving Fluid, CLWT

MBB-J6-CH4

External Chilled

Water Pump Interlock

PMPI

Switch

Electrical Box Interlock, ELEC

MBB-J4-CH15A

Circuit A Suction

Pressure Transducer

SPTA

Pressure Transducer

Suction Pressure, SP.A

MBB-J7B-CH7

5V

+5 vdc Ref.

S

Signal

R

Return

Circuit B Suction

Pressure Transducer

SPTB

Pressure Transducer

Suction Pressure, SP.B

MBB-J7D-CH9

5V

+5 vdc Ref.

S

Signal

R

Return

Unit Status

Remote Contact-Off-Enable

Switch

On/Off Remote Switch, ONOF

MBB-J4-CH11

Alarm Relay

ALM R

Relay

Alarm Relay Output, ALRM

MBB-J3-CH24

Alert Relay

ALT R

Relay

Alert Relay Output, ALRT

MBB-J3-CH25

Cooler Pump Relay 1

PMP1

Contactor

Cooler Pump 1, CPUMP_1

MBB-J2A-CH19

Cooler Pump Relay 2

PMP2

Contactor

Cooler Pump 2, CPUMP_2

MBB-J2A-CH20

Condenser Pump Relay

CPMP

Contactor

Condenser Pump, COND_PMP

MBB-J2C-CH22

Pump #1 Interlock
Pump #2 Interlock

PMP_1
PMP_2

Switch

Cooler Pump Run Status, PUMP

MBB-J5C-CH18

I/O

Input or Output

LWT — Leaving Water Temperature

Advertising