APPENDIX C — CCN TABLES (cont)

CONFIGURATION TABLES (cont)

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

CFG_TABn
(n = 1 to 8)

Display x table number 1

85

tab_nb_1

Display n var number 1

4

var_nb_1

Display n table number 2

85

tab_nb_2

Display n var number 2

20

var_nb_2

Display n table number 3

85

tab_nb_3

Display n var number 3

21

var_nb_3

Display n table number 4

85

tab_nb_4

Display n var number 4

28

var_nb_4

Display n table number 5

85

tab_nb_5

Display n var number 5

29

var_nb_5

Display n table number 6

85

tab_nb_6

Display n var number 6

30

var_nb_6

Display n table number 7

92

tab_nb_7

Display n var number 7

33

var_nb_7

Display n table number 8

92

tab_nb_8

Display n var number 8

34

var_nb_8

Display n table number 9

0

tab_nb_9

Display n var number 9

0

var_nb_9

DISPCONF

Metric Display on STDU

Yes/No

No

DISPUNIT

Language Selection

0=English
1=Espanol
2=Francais
3=Portugues
4=Translated

0

LANGUAGE

MST_SLV

MASTER SLAVE CONTROL
Master/Slave Select

0=Disable
1=Master
2=Slave

0

ms_sel

Master Control Type

1=Local Control
2=Remote Control
3=CCN Control

1

ms_ctrl

Slave Address

1 to 236

2

slv_addr

Lead Lag Select

0=Always Lead
1=Lag Once
Failed Only
2=Lead/Lag
Runtime Sel

0

lead_sel

Lead/Lag Balance Delta

40 to 400

168

hours

ll_bal_d

Lag Start Timer

2 to 30

10

min

lstr_tim

Lead Pulldown Time

0 to 60

0

min

lead_pul

Start if Error Higher

4

^F

start_dt

Lag Minimum Running Time

0

min

lag_mini

Lag Unit Pump Control

0=Stop if Unit Stops
1=Run if Unit Stops

0

lag_pump

Chiller in Series

Yes/No

No

II_serie