Carrier comfort network, Ccn) interface, Remote alarm and alert relays – Carrier AQUAFORCE 30XW150-400 User Manual

Page 18

Advertising
background image

18

Carrier Comfort Network

®

(CCN) Interface —

All 30XW units can be connected to a CCN system, if desired.

The communication bus wiring is a shielded, 3-conductor cable

with drain wire and is field supplied and installed. The system

elements are connected to the communication bus in a daisy

chain arrangement. The positive pin of each system element

communication connector must be wired to the positive pins of

the system elements on either side of it. The negative and sig-

nal ground pins of each system element must also be wired in

the same manner. Wiring connections for CCN should be made

at TB3. Consult the CCN Contractor’s Manual for further in-

formation. See Fig. 14.
NOTE: Conductors and drain wire must be 20 AWG (Ameri-

can Wire Gage) minimum stranded, tinned copper. Individual

conductors must be insulated with PVC, PVC/nylon, vinyl,

Teflon, or polyethylene. An aluminum/polyester 100% foil

shield and an outer jacket of PVC, PVC/nylon, chrome vinyl,

or Teflon with a minimum operating temperature range of

–20 C to 60 C is required. See Table 11 for recommended wire

manufacturers and part numbers.

Table 11 — CCN Communication Bus Wiring

It is important when connecting to a CCN communication

bus that a color-coding scheme be used for the entire network

to simplify the installation. It is recommended that red be used

for the signal positive, black for the signal negative, and white

for the signal ground. Use a similar scheme for cables contain-

ing different colored wires.

At each system element, the shields of its communication

bus cables must be tied together. If the communication bus is

entirely within one building, the resulting continuous shield

must be connected to a ground at one point only. If the commu-

nication bus cable exits from one building and enters another,

the shields must be connected to grounds at the lightning

suppressor in each building where the cable enters or exits the

building (one point per building only). To connect the unit to

the network:

1. Turn off power to the control box.
2. Cut the CCN wire and strip the ends of the red (+), white

(ground), and black (–) conductors. (Substitute appropri-

ate colors for different colored cables.)

3. Connect the red wire to (+) terminal on TB3 of the plug,

the white wire to COM terminal, and the black wire to the

(–) terminal.

4. The RJ14 CCN connector on TB3 can also be used, but is

only intended for temporary connection (for example, a

laptop computer running Service Tool).

Remote Alarm and Alert Relays —

The 30XW

chiller can be equipped with a remote alert and remote alarm

annunciator contacts. Both relays connected to these contacts

must be rated for a maximum power draw of 10 va sealed,

25 va inrush at 24 volts. The alarm relay, indicating that the

complete unit has been shut down, can be connected to TB5-12

and TB5-13. Refer to unit wiring diagrams. For an alert relay,

indicating that at least 1 circuit is off due to the alert, a field-

supplied and installed relay must be connected between MBB-

J3-CH25-3 and TB5-13. The action of the alarm and alert re-

lays can be reversed from normally open to normally closed by

using the Reverse Alarms Relay configuration (Reverse

Alarms Relay, RV.AL).

CONFIGURATION

Touch Pilot™ Operation Configuration
Tables —

The Touch Pilot display operation is controlled by

configuration information entered in the following configura-

tion tables. These tables are accessible by using Network Ser-

vice Tool or ComfortVIEW™ software. The tables are the

CtrlID (Controller Identification) configuration table and the

USERCONF (User Configuration) table. See Tables 12 and 13.
NOTE: Always perform an Upload to obtain the latest config-

uration before making configuration table changes.

MANUFACTURER

PART NUMBER

Regular Wiring

Plenum Wiring

Alpha

1895

American

A21451

A48301

Belden

8205

884421

Columbia

D6451

Manhattan

M13402

M64430

Quabik

6130

IMPORTANT: A shorted CCN bus cable will prevent

some routines from running and may prevent the unit

from starting. If abnormal conditions occur, discon-

nect the CCN bus. If conditions return to normal,

check the CCN connector and cable. Run new cable if

necessary. A short in one section of the bus can cause

problems with all system elements on the bus.

Fig. 14 — ComfortLink™ CCN Communication Wiring

(+) (COM) (-) SHIELD

CCN

RED

WHT

BLK

CCN

LEN

(+) (COM) (-) SHIELD

CCN

RED

WHT

BLK

CCN

LEN

TO NEXT
DEVICE

(+) (COM) (-) SHIELD

CCN

RED

WHT

BLK

CCN

LEN

SHIELD

LEGEND

CCN

Carrier Comfort Network

®

LEN

Local Equipment Network

a30-4706