APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — OUTPUTS
MODE — CONFIGURATION
ITEM
EXPANSION
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
CIR.A
CIRCUIT A OUTPUTS
CP.A
Compressor A Relay
OFF/ON
CIRCA_D
CP_A
HT.A
Oil Heater Circuit A
OFF/ON
OIL_HT_A
SL1.A
Slide Valve 1 Cir A
OFF/ON
SLID1_A
SL2.A
Slide Valve 2 Cir A
OFF/ON
SLID2_A
OLS.A
Oil Solenoid Cir A
OFF/ON
OIL_SL_A
HGB.A
Hot Gas Bypass Cir A
OFF/ON
FAN.A
Circuit A Fan Stages
X
0-6
CIRCA_D
FAN_ST_A
SPD.A
Circ A Varifan Position
XXX (%)
0-100
CIRCA_AN
hd_pos_a
EXV.A
Circuit A EXV % Open
XXX (%)
0-100
CIRCA_AN
EXV_A
61
ECO.A
Circ A EXV ECO % Open
XXX (%)
0-100
EXV_EC_A
DGT.A
DGT Cool Solenoid A
OFF/ON
dgt_gascool_a
CIR.B
CIRCUIT B OUTPUTS
CP.B
Compressor B Relay
OFF/ON
CIRCB_D
CP_B
HT.B
Oil Heater Circuit B
OFF/ON
CIRCB_D
OIL_HT_B
SL1.B
Slide Valve 1 Cir B
OFF/ON
SLID1_B
SL2.B
Slide Valve 2 Cir B
OFF/ON
SLID2_B
OLS.B
Oil Solenoid Cir B
OFF/ON
OIL_SL_B
HGB.B
Hot Gas Bypass Cir B
OFF/ON
FAN.B
Circuit B Fan Stages
X
0-6
CIRCB_D
FAN_ST_B
SPD.B
Circ B Varifan Position
XXX (%)
0-100
CIRCB_AN
hd_pos_b
EXV.B
Circuit B EXV % Open
XXX (%)
0-100
CIRCB_AN
EXV_B
61
ECO.B
Circ B EXV ECO % Open
XXX (%)
0-100
EXV_EC_B
DGT.B
DGT Cool Solenoid B
OFF/ON
dgt_gascool_b
CIR.C
CIRCUIT C OUTPUTS
CP.C
Compressor C Relay
OFF/ON
CIRCC_D
CP_C
HT.C
Oil Heater Circuit C
OFF/ON
CIRCC_D
OIL_HT_C
SL1.C
Slide Valve 1 Cir C
OFF/ON
SLID1_C
SL2.C
Slide Valve 2 Cir C
OFF/ON
SLID2_C
OLS.C
Oil Solenoid Cir C
OFF/ON
OIL_SL_C
HGB.C
Hot Gas Bypass Cir C
OFF/ON
FAN.C
Circuit C Fan Stages
X
0-6
CIRCC_D
FAN_ST_C
SPD.C
Circ C Varifan Position
XXX (%)
0-100
CIRCC_AN
hd_pos_c
EXV.C
Circuit C EXV % Open
XXX (%)
0-100
CIRCC_AN
EXV_C
ECO.C
Circ C EXV ECO % Open
XXX (%)
0-100
EXV_EC_C
DGT.C
DGT Cool Solenoid C
OFF/ON
dgt_gascool_c
GEN.O
GENERAL OUTPUTS
PMP.1
Water Exchanger Pump 1
OFF/ON
STATEGEN
CPUMP_1
PMP.2
Water Exchanger Pump 2
OFF/ON
STATEGEN
CPUMP_2
PMP.3
Condenser Pump 1
OFF/ON
STATEGEN
HPUMP_1
CO.HT
Cooler Heater Output
OFF/ON
STATEGEN
COOLHEAT
BVL.A
Ball Valve Position A
OPEN/CLOSE
ref_iso_a
BVL.B
Ball Valve Position B
OPEN/CLOSE
ref_iso_b
BVL.C
Ball Valve Position C
OPEN/CLOSE
ref_iso_c
CN.HT
Condenser Heat Output
OFF/ON
Not supported.
RECLAIM
cond_htr
REDY
Chiller Ready Status
OFF/ON
forcible
RECLAIM
READY
RUN
Chiller Running Status
OFF/ON
forcible
STATEGEN
RUNNING
SHUT
Customer Shutdown Stat
OFF/ON
forcible
STATEGEN
SHUTDOWN
CATO
Chiller Capacity 0-10 v
XX.X
forcible
STATEGEN
CAPT_010
ALRM
Alarm Relay
OFF/ON
STATEGEN
ALARM
ALRT
Alert Relay
OFF/ON
STATEGEN
ALERT
ITEM
EXPANSION
UNITS
RANGE
COMMENT
DEFAULT
CCN
TABLE
CCN
POINT
PAGE NO.
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs
OFF/ON
OFF
N/A
display_test
METR
Metric Display
US/METR
US
DISPCONF
DISPUNIT
LANG
Language Selection
English
Espanol
Francais
Portugues
Translated
English
DISPCONF
LANGUAGE 8