70 table 49 — alarm codes (cont) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 70

Advertising
background image

70

Table 49 — Alarm Codes (cont)

LEGEND

PREFIX

CODE

SUFFIX

CODE

ALARM

NUMBER

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

BY CONTROL

RESET

TYPE

PROBABLE CAUSE

Co

A1

53

Loss of communication with
Compressor Board A

No communication

with CPM board

Affected

compressor shut

down

Automatic

Wrong CPM address,

wrong unit configura-

tion, wiring error, power

loss, failed

CPM board

B1

54

Loss of communication with
Compressor Board B

E1

56

Loss of communication with
EXV Board 1

No communication with

EXV board

Affected

compressor

shut down

Automatic

Wrong EXV board

address, wrong unit

configuration, wiring

error, power loss,

failed EXV board

E2

57

Loss of communication with
EXV Board 2

03

64

Loss of communication with
Energy Management Board

No communication with

EMM board

Disable or not allow

EMM functions

3 step and 4-20 mA

and space tempera-

ture reset, occu-

pancy override and

ice build)

Automatic

Wrong board

address, wrong unit

configuration, wiring

error, power loss to

module, failed module

05

66

Loss of communication with
AUX Board 6

No communication

with MLV/COND Board

Unit shut down or

not allowed to start

Automatic

Wrong board

address, wrong unit

configuration, wiring

error, power loss to

module, failed module

P

01

67

Cooler Freeze Protection

Entering or leaving therm-

istor sensed a tempera-

ture at or below freeze

point

Unit shut down or

not allowed to start

Automatic, first

occurrence in

24 hours;

manual if

multiple alarms
within 24 hours

Faulty thermistor, faulty

wiring, low water flow,

low loop volume, fouled

cooler, or freeze

conditions

02

68

Condenser Freeze Protection
Circuit A

None

Automatic

Configuration error

03

69

Condenser Freeze Protection
Circuit B

05

71

Circuit A Low Suction
Temperature

Low saturated suction

temperatures detected for

a period of time

Circuit shut down

Automatic, first

occurrence in

24 hours;

manual if

multiple alarms
within 24 hours

Faulty thermistor, faulty

wiring, low water flow,

low loop volume, fouled

cooler, or freeze

conditions

06

72

Circuit B Low Suction
Temperature

08

74

Circuit A High Suction
Superheat

EXV>98%,

suction superheat > 30 F,

and SST<MOP for more

than 5 minutes

Circuit shut down

Manual

Faulty transducer,

faulty wiring, faulty

thermistor, faulty EXV,

low refrigerant charge,

plugged or restricted

liquid line

09

75

Circuit B High Suction
Superheat

CCN

Carrier Comfort Network

®

MLV

Minimum Load Valve

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

EMM

Energy Management Module

MTA

Must Trip Amps

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

HPS

High Pressure Switch