73 table 49 — alarm codes (cont) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 73

Advertising
background image

73

Table 49 — Alarm Codes (cont)

LEGEND

DIAGNOSTIC ALARM CODES AND POSSIBLE

CAUSES
Thermistor Failure
Alarm 1 — Cooler Fluid Entering (th.01)

Alarm 2 — Cooler Fluid Leaving (th.02)
Criteria for Trip — This alarm criterion is tested whether the

unit is on or off if the temperature as measured by the thermis-

tor is outside of the range –40 to 245 F (–40 to 118.3 C).
Action to be Taken — The unit shuts down normally, or is not

allowed to start.
Reset Method — Automatic, the alarm will reset once the

thermistor reading is within the expected range.
Possible Causes — If this condition is encountered, check the

following items:

• sensor wiring to the Main Base Board

• sensor accuracy

See the Thermistors section on page 56 for thermistor de-

scription, identifiers and connections.

Defrost Thermistor Failure
Alarm 3 — Circuit A (th.03)

Alarm 4 — Circuit B (th.04)
NOTE: Alarms 3 and 4 are not used or supported. If this condi-

tion is encountered, confirm machine configuration.
Thermistor Failure
Alarm 5 — Condenser Entering Fluid (th.06)
Alarm 6 — Condenser Leaving Fluid (th.07)
NOTE: Alarms 5 and 6 are not used or supported. If this condi-

tion is encountered, confirm machine configuration.
Condenser Reclaim Thermistor
Alarm 7— Reclaim Entering Fluid (th.08)
Alarm 8 — Reclaim Leaving Fluid (th.09)
NOTE: Alarms 7 and 8 are not used or supported. If this condi-

tion is encountered, confirm machine configuration.

PREFIX

CODE

SUFFIX

CODE

ALARM

NUMBER

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

BY CONTROL

RESET

TYPE

PROBABLE CAUSE

A1, B1

10

132-10,

133-10

Compressor Y delta starter
current increase failure alarm

If the delta mode current

is not 25% greater than

the current in Y mode

Circuit shut down

Manual

Power supply to delta

contactor not

connected, faulty delta

contactor or wiring,

faulty CPM board

11

132-11,

133-11

Compressor Contactor failure

CPM board detects

greater than 15% of MTA

current for 10 seconds

after shutting off the com-

pressor contactor. Oil

solenoid is energized.

Circuit shut down

Manual

Faulty contactor, con-

tactor welded, wiring

error

12

132-12,

133-12

Compressor Unable to stop
motor

CPM board detects

greater than 15% of MTA

current for 10 seconds

after three attempts

Circuit shut down

Manual

Faulty contactor,

contactor welded,

wiring error

13

132-13,

133-13

Compressor Phase reversal

CPM board detects phase

reversal from current

toroid

Circuit shut down

Manual

Terminal block power

supply lead not in

correct phase. Power

supply leads going

through toroid crossed

14

132-14,

133-14

Compressor MTA configura-
tion fault

MTA setting is out of the

allowed MTA range

Circuit shut down

Manual

Incorrect MTA setting,

faulty CPM board

15

132-15,

133-15

Compressor Configuration
switch mismatch

CPM board MTA setting

do not match factory

configuration

Circuit shut down

Manual

Incorrect CPM dip-

switch setting,

incorrect factory MTA

setting, faulty CPM

board

16

132-16,

133-16

Compressor Unexpected
switch setting change

CPM board dipswitch S1

setting changed

Circuit shut down

Manual

Incorrect CPM dip-

switch setting, faulty

CPM board

17

132-17,

133-17

Compressor Power on reset

CPM board detects a

power failure

Circuit shut down

Manual

Power supply

interruption

18

132-18,

133-18

Compressor UL 1998 critical
section software error

Software error

Circuit shut down

Manual

Electric noise, faulty

CPM board

19

132-19,

133-19

Compressor UL 1998 current
measure dual channel
mismatch

Software error

Circuit shut down

Manual

Electric noise, faulty

CPM board

CCN

Carrier Comfort Network

®

MLV

Minimum Load Valve

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

EMM

Energy Management Module

MTA

Must Trip Amps

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

HPS

High Pressure Switch

Advertising