APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — SET POINTS

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

STATUS

CCN TABLE

CCN POINT

PAGE

NO.

COOL

COOLING SETPOINTS

CSP.1

Cooling Setpoint 1

XXXX.X
(deg F/deg C)

–20-70 F
(–29-21 C),
Default = 44.0

forcible

SETPOINT

csp1

25, 41,
55

CSP.2

Cooing Setpoint 2

XXXX.X
(deg F/deg C)

–20-70 F
(–29-21 C),
Default = 44.0

forcible

SETPOINT

csp2

25, 41,
55

CSP.3

Ice Setpoint

XXXX.X
(deg F/deg C)

–20-70 F
(–29-21 C),
Default = 44.0

forcible

SETPOINT

ice_sp

25, 41,
55

CRV1

Current No Reset Val

XX.X (mA)

0-20,
Default = 0

forcible

SETPOINT

v_cr_no

36

CRV2

Current Full Reset Val

XX.X (mA)

0-20,
Default = 0

forcible

SETPOINT

v_cr_fu

36

CRT1

Delta T No Reset Temp

XXX.X (

F/C)

0-125 F
(0-69.4 C),
Default = 0

forcible

SETPOINT

dt_cr_no

35, 36

CRT2

Delta T Full Reset Temp

XXX.X (

F/C)

0-125 F
(0-69.4 C),
Default = 0

forcible

SETPOINT

dt_cr_fu

35, 36

CRO1

OAT No Reset Temp

XXX.X
(deg F/deg C)

0-125 F
(–18-52 C),
Default = 14.0

forcible

SETPOINT

oatcr_no

CRO2

OAT Full Reset Temp

XXX.X
(deg F/deg C)

0-25 F
(–18-52 C),
Default = 14.0

forcible

SETPOINT

oatcr_fu

CRS1

Space T No Reset Temp

XXX.X
(deg F/deg C)

0-125 F
(–18-52 C),
Default = 14.0

forcible

SETPOINT

spacr_no

36

CRS2

Space T Full Reset Temp

XXX.X
(deg F/deg C)

0-125 F
(–18-52 C),
Default = 14.0

forcible

SETPOINT

spacr_fu

36

DGRC

Degrees Cool Reset

XX.X (

F/C)

–30-30 F
(–16.7-16.7 C),
Default = 0

forcible

SETPOINT

cr_deg

35, 36

CAUT

Cool Changeover Setpt

XX.X
(deg F/deg C)

Default = 75.0

Not supported.

forcible

SETPOINT

cauto_sp

CRMP

Cool Ramp Loading

X.X

0.2-2.0

F

(0.1-1.1

C),

Default = 1.0

forcible

SETPOINT

cramp_sp

35

HEAT

HEATING SETPOINTS

HSP.1

Heating Setpoint 1

XXX.X
(deg F/deg C)

Default = 100

Not supported.

forcible

SETPOINT

HSP.1

HSP.2

Heating Setpoint 2

XXX.X
(deg F/deg C)

Default = 100

Not supported.

forcible

SETPOINT

HSP.2

HRV1

Current to Reset Val

XX.X (mA)

Default = 0

Not supported.

forcible

SETPOINT

v_hr_no

HRV2

Current Full Reset Val

XX.X (mA)

Default = 0

Not supported.

forcible

SETPOINT

v_hr_fu

HRT1

Delta T No Reset Temp

XXX.X (

F/C)

Default = 0

Not supported.

forcible

SETPOINT

dt_hr_no

HRT2

Delta T Full Reset Temp

XXX.X (

F/C)

Default = 0

Not supported.

forcible

SETPOINT

dt_hr_fu

HRO1

OAT No Reset Temp

XXX.X
(deg F/deg C)

Default = 14.0

Not supported.

forcible

SETPOINT

oathr_no

HRO2

OAT Full Reset Temp

XXX.X
(deg F/deg C)

Default = 14.0

Not supported.

forcible

SETPOINT

oathr_fu

DGRH

Degrees Heat Reset

XX.X (

F/C)

Default = 0

Not supported.

forcible

SETPOINT

DGRH

HAUT

Heat Changeover Setpt

XX.X
(deg F/deg C)

Default = 64

Not supported.

forcible

SETPOINT

hauto_sp

HRMP

Heat Ramp Loading

X.X

Default = 1.0

Not supported.

forcible

SETPOINT

hramp_sp

MISC

MISC SETPOINTS

DLS1

Switch Limit Setpoint 1

XXX (%)

0-100,
Default = 100

forcible

SETPOINT

lim_sp1

39, 40

DLS2

Switch Limit Setpoint 2

XXX (%)

0-100,
Default = 100

forcible

SETPOINT

lim_sp2

39, 40

DLS3

Switch Limit Setpoint 3

XXX (%)

0-100,
Default = 100

forcible

SETPOINT

lim_sp3

W.SCT

Water Val Cond Stp

XXX.X
(deg F/deg C)

80-140 F
(26.7-60 C)

Not supported.

SETPOINT

w_sct_sp

46