Appendix c — ccn tables (cont), Setpoint configuration tables, Maintenance display tables – Carrier AQUAFORCE 30XW150-400 User Manual

Page 127

Advertising
background image

127

APPENDIX C — CCN TABLES (cont)

SETPOINT CONFIGURATION TABLES

*Not supported.

MAINTENANCE DISPLAY TABLES

*Not supported.
NOTES: Tables for display only. Forcing shall not be supported on this maintenance screen.

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

SETPOINT

COOLING
Cooling Setpoint 1

–20-70

44.0

°F

csp1

Cooling Setpoint 2

–20-70

44.0

°F

csp2

Cooling Ice Setpoint

–20-70

44.0

°F

ice_sp

OAT No Reset Value

14-125

14.0

°F

oatcr_no

OAT Full Reset Value

14-125

14.0

°F

oatcr_fu

Delta T No Reset Value

0-25

0.0

^F

dt_cr_no

Delta T Full Reset Value

0-25

0.0

^F

dt_cr_fu

Current No Reset Value

0-20

0.0

ma

v_cr_no

Current Full Reset Value

0-20

0.0

ma

v_cr_fu

Space T No Reset Value

14-125

14.0

°F

spacr_no

SpaceT Full Reset Value

14-125

14.0

°F

spacr_fu

Cooling Reset Deg. Value

–30-30

0.0

^F

cr_deg

Cooling Ramp Loading

0.2-2.0

1.0

^F

cramp_sp

HEATING*
Heating Setpoint 1

80-140

100.0

°F

hsp1

Heating Setpoint 2

80-140

100.0

°F

hsp2

OAT No Reset Value

14-125

14.0

°F

oathr_no

OAT Full Reset Value

14-125

14.0

°F

oathr_fu

Delta T No Reset Value

0-25

0.0

^F

dt_hr_no

Delta T Full Reset Value

0- 25

0.0

^F

dt_hr_fu

Current No Reset Value

0-20

0.0

ma

v_hr_no

Current Full Reset Value

0-20

0.0

ma

v_hr_fu

Heating Reset Deg. Value

–30-30

0.0

^F

hr_deg

Heating Ramp Loading

0.2-2.0

1.0

^F

hramp_sp

AUTO CHANGEOVER*
Cool Changeover Setpt

39-122

75.0

°F

cauto_sp

Heat Changeover Setpt

32-115

64.0

°F

hauto_sp

MISCELLANEOUS
Switch Limit Setpoint 1

0-100

100

%

lim_sp1

Switch Limit Setpoint 2

0-100

100

%

lim_sp2

Switch Limit Setpoint 3

0-100

100

%

lim_sp3

Reclaim Setpoint*

95-140

122.0

°F

rsp

Reclaim Deadband*

5-27

9.0

°F

hr_deadb

Water Val Condensing Stp

80 to 120

86

°F

w_sct_sp

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

BOARD_PN

EXV Board Circuit A

XXXXXXXX

exv_brda

EXV Board Circuit B

XXXXXXXX

exv_brdb

EXV Board Circuit C

XXXXXXXX

exv_brdc

AUX Board #1 Part Number

XXXXXXXX

aux_brd1

AUX Board #2 Part Number

XXXXXXXX

aux_brd2

AUX Board #3 Part Number

XXXXXXXX

aux_brd3

AUX Board #4 Part Number

XXXXXXXX

aux_brd4

AUX Board #5 Part Number

XXXXXXXX

aux_brd5

EMM NRCP2 Board

XXXXXXXX

emm_nrcp

Reclaim NRCP2 Board

XXXXXXXX

rec_nrcp

TCPM Board Comp A

XXXXXXXX

cpa_vers

Must Trip Amps

0-600

amps

cpa_mtam

S1 Config Switch (8 to 1)

00000000

0

cpa_s1_m

TCPM Board Comp B

nnnn

cpb_vers

Must Trip Amps

0-600

amps

cpb_mtam

S1 Config Switch (8 to 1)

00000000

0

cpb_s1_m

TCPM Board Comp C

XXXXXXXX

cpc_vers

Must Trip Amps

0-600

amps

cpc_mtam

S1 Config Switch (8 to 1)

00000000

0

cpc_s1_m

CUR_PHASE

Current Phase 1 Comp A

0-600

amps

cpa_cur1

Current Phase 2 Comp A

0-600

amps

cpa_cur2

Current Phase 3 Comp A

0-600

amps

cpa_cur3

Current Phase 1 Comp B

0-600

amps

cpb_cur1

Current Phase 2 Comp B

0-600

amps

cpb_cur2

Current Phase 3 Comp B

0-600

amps

cpb_cur3

Current Phase 1 Comp C

0-600

amps

cpc_cur1

Current Phase 2 Comp C

0-600

amps

cpc_cur2

Current Phase 3 Comp C

0-600

amps

cpc_cur3

DEFROSTM*

CIR A DEFROST CONTROL
Exchanger Frost Factor

0-100

%

frost_a

Next Sequence Allowed in

nnn

minutes

def_se_a

Defrost Active?

True/False

mode[19]

Defrost Temperature

±nnn.n

°F

DEFRT_A

Defrost Duration

nnn

minutes

defr_dua

Fan Sequence Started ?

n

def_fa_a

Override State

nn

over_d_a

Mean SST Calculation

±nnn.n

°F

sst_dm_a

Delta: OAT - Mean SST

±nnn.n

^F

delt_a

Reference Delta

±nnn.n

^F

delt_r_a

Delta - Reference Delta

±nnn.n

°F

del_v_a

Frost Integrator Gain

n.n

fr_int_a

Defrost Fan Start Cal A

0.00

psi

def_ca_a

Defrost Fan Offset Cal A

0.00

psi

def_of_a

CIR B DEFROST CONTROL
Exchanger Frost Factor

0-100

%

frost_b

Next Sequence Allowed in

nnn

minutes

def_se_b

Defrost Active?

True/False

mode[20]

Defrost Temperature

±nnn.n

°F

DEFRT_B

Defrost Duration

nnn

minutes

defr_dub

Fan Sequence Started?

n

def_fa_b

Override State

nn

over_d_b

Mean SST calculation

±nnn.n

°F

sst_dm_b

Delta: OAT - Mean SST

±nnn.n

^F

delt_b

Reference Delta

±nnn.n

^F

delt_r_b

Delta - Reference Delta

±nnn.n

^F

del_v_b

Frost Integrator Gain

n.n

fr_int_b

Defrost Fan Start Cal B

0.00

psi

def_ca_b

Defrost Fan Offset Cal B

0.00

psi

def_of_b