Carrier AQUAFORCE 30XW150-400 User Manual

Page 30

Advertising
background image

30

between the master and the slave remains less than the Lead/

Lag Balance Delta, the chiller designated as the lead will

remain the lead chiller. The Lead/Lag changeover between the

master and the slave chiller due to hour balance will occur dur-

ing chiller operating odd days, such as day 1, day 3, and day 5

of the month, at 12:00 a.m. If a lead chiller is not designated,

the master chiller will always be designated the lead chiller.

The dual chiller control algorithm has the ability to delay

the start of the lag chiller in two ways. The Lead Pulldown

Time parameter (Lead Pulldown Type, LPUL) is a one-time

time delay initiated after starting the lead chiller, before

checking whether to start an additional chiller. This time delay

gives the lead chiller a chance to remove the heat that the

chilled water loop picked up while being inactive during an un-

occupied period. The second time delay, Lead/Lag Delay (Lag

Start Timer, LLDY) is a time delay imposed between the last

stage of the lead chiller and the start of the lag chiller. This pre-

vents enabling the lag chiller until the lead/lag delay timer has

expired.

A quicker start of the lag chiller can be accomplished by

configuring the Start if Error Higher parameter (Start if Error

Higher, LL.ER). If the difference between the common leav-

ing water temperature and the set point is greater than the con-

figured value, then the lag chiller will start.

A minimum on time for the lag chiller can be programmed

with the Lag Minimum Running Time configuration (Lag

Minimum Running Time, LAG.M). This parameter causes

the control to run the lag chiller for the programmed minimum

on time. The Lag Unit Pump Select (Lag Unit Pump Control,

LAGP) can be configured such that the pump can be on or off

while the chiller is off. This parameter is only active in Parallel

Chiller Operation.

For units with a Touch Pilot display, two additional steps

must be completed to start the machine. On the master chiller,

the Master Control Type must be configured for the start con-

trol defined in the Machine Control configuration. To start the

machines, the master chiller must be started with the Start/Stop

button and Master Mode selected. The slave chiller must be

started with the CCN Mode selected.

Each application, Parallel and Series, are described sepa-

rately below.
DUAL CHILLER CONTROL FOR PARALLEL APPLI-

CATIONS — To configure the master chiller for parallel

applications using the Touch Pilot display, see Table 24. To

configure the master chiller for parallel applications using the

Navigator display, see Table 25. A power cycle is required for

the values to take effect.

To configure the slave chiller for parallel applications using

the Touch Pilot display, see Table 26. To configure the slave

chiller for parallel applications using the Navigator display, see

Table 27.