Table 49 — Alarm Codes (cont)

LEGEND

PREFIX

CODE

SUFFIX

CODE

ALARM

NUMBER

ALARM DESCRIPTION

REASON FOR ALARM

ACTION TAKEN

BY CONTROL

RESET

TYPE

PROBABLE CAUSE

P

40

108

Circuit A — Repeated low
suction temp overrides

Multiple capacity

overrides due to low satu-
rated suction temperature

Circuit shut down

Automatic

Inaccurate

transducer, faulty EXV,

low refrigerant charge,

plugged or restricted

liquid line filter drier.

41

109

Circuit B — Repeated low
suction temp overrides

43

111

Low entering water tempera-
ture in heating

Not supported

73

112

Condenser pump #1 default

None

Manual

Faulty contacts, wiring

error or low control

voltage. Configuration

error.

74

113

Condenser pump #2 default

78

114

Circuit A High Discharge
Temperature

Discharge gas tempera-

ture is higher than 212 F

for more than 90 seconds

Circuit shut down

Manual

Faulty transducer/high

pressure switch, low/

restricted condenser

flow

79

115

Circuit B High Discharge
Temperature

81

117

Circuit A Low Economizer
Pressure

The economizer pressure
is below the suction pres-

sure more than 14.5 psi

for more than 10 seconds

Circuit shut down

Manual

Faulty transducer,

faulty main base board,

faulty wiring, closed

suction service valve,

faulty EXV

82

118

Circuit B Low Economizer
Pressure

87

120

Circuit A Slide Valve Control
Unverifiable

If 100% load current is

less than 1.1 times of

30% load current, or for

1 minute when active

cooling setpoint is

greater than 32 F.

None

Manual

Slide valve stuck, inac-

curate initial current

reading

88

121

Circuit B Slide Valve Control
Unverifiable

90

123

Cooler flow switch set point
configuration failure

None Manual

Configuration

error

91

124

Cooler flow switch failure

Flow switch open

Unit shut down

Manual if unit

is running,

automatic
otherwise

Faulty flow switch, low

cooler flow, faulty

wiring, faulty cooler

pump, faulty main base

board

Sr

nn

128

Service maintenance alert
Number # nn

Field programmed

elapsed time has expired

for maintenance time

None

Manual

Maintenance required

A1, B1

01

132-01,

133-01

Compressor Motor tempera-
ture too high

Compressor temperature

higher than 232 F for

more than 90 seconds

Circuit shut down

Manual

Economizer EXV fail-

ure (350,400 only),

faulty CPM board,

low refrigerant charge

02

132-02,

133-02

Compressor Motor tempera-
ture out of range

Compressor temperature

reading out of the range of

–40 F to 245 F

Circuit shut down

Manual

Faulty thermistor, faulty

wiring, faulty CPM

board

03

132-03,

133-03

Compressor High pressure
switch protection

HPS input on CPM board

open

Circuit shut down

Manual, press

reset button on

HPS

Loss of condenser air

flow, operation beyond

compressor envelope,

faulty high pressure

switch, faulty wiring,

faulty CPM board

04

132-04,

133-04

Compressor Over current

CPM board detects high

motor current compared

with MTA setting

Circuit shut down

Manual

Operating beyond

compressor envelope,
incorrect configuration

05

132-05,

133-05

Compressor Locked rotor

CPM board detects locked

rotor current compared

with MTA setting

Circuit shut down

Manual

Compressor motor fail-

ure, unloader slide

valve failure, compres-

sor mechanical failure

06

132-06,

133-06

Compressor Phase loss L1

CPM board detects cur-

rent unbalance greater

than 65% for more than

1 second

Circuit shut down

Manual

Blown fuse, wiring

error, loose terminals

07

132-07,

133-07

Compressor Phase loss L2

08

132-08,

133-08

Compressor Phase loss L3

09

132-09,

133-09

Compressor Low current
alarm

CPM detects motor cur-

rent less than a certain

percentage of the MTA

setting, compressor not

operating

Circuit shut down

Manual

Power supply discon-

nected, blown fuse,

wiring error, contact

deenergized, faulty

current toroid high

pressure switch trip.

CCN

Carrier Comfort Network

®

MLV

Minimum Load Valve

CPM

Compressor Protection Module

MOP

Maximum Operating Pressure

EMM

Energy Management Module

MTA

Must Trip Amps

EWT

Entering Water Temperature

SST

Saturated Suction Temperature

EXV

Electronic Expansion Valve

UL

Underwriters Laboratories

HPS

High Pressure Switch