Chilled water fluid type selection – Carrier AQUAFORCE 30XW150-400 User Manual

Page 27

Advertising
background image

27

To configure this option while using a Navigator display:

Dual Switch — When Set Point Select (Setpoint Select,

SP.SE) is configured to 4 (Dual Setp Sw), the unit’s active set

point is based on Cooling Set Point 1 (Cooling Setpoint 1,

CSP.1) when the Dual Set Point switch contact is open and

Cooling Set Point 2 (Cooling Setpoint 2, CSP.2) when it is

closed.

To configure this option while using a Touch Pilot display:

To change this value, a Control Point Force must be applied.

When configured correctly, Setpoint Control will indicate

Setp Sw.

To configure this option while using a Navigator display:

Chilled Water Fluid Type Selection —

The chilled

water fluid must be configured. The fluid type must be config-

ured to obtain the proper leaving water set point control range

and freeze protection. The Cooler Fluid Type (Cooler Fluid

Type, FLUD) can be set to water or brine.
FRESH WATER — Configure the unit for Cooler Fluid Type

(Cooler Fluid Type, FLUD) to water for units without brine or

glycol installed in the chilled water loop. The factory default

fluid type is fresh water. Use this option for fresh water sys-

tems. This will allow for a water temperature set point of 38 to

60 F (3.3 to 15.5 C). With water as the selection, the Freeze

Point is fixed at 34 F (1.1 C).

To configure this option with the Touch Pilot display:

To configure this option with the Navigator display:

BRINE OR GLYCOL OPERATION — Configure the unit

for Cooler Fluid Type (Cooler Fluid Type, FLUD) to brine for

brine or glycol chilled water loops. This option will allow for a

set point temperature range of 14 to 60 F (–10.0 to 15.5 C).

Before configuring this selection, confirm that a suitable anti-

freeze has been added and is at a sufficient concentration to

protect the loop. Additionally, the Brine Freeze Set Point

(Brine Freeze Setpoint, LOSP) must be set for proper freeze

protection operation. Set the Brine Freeze Set Point to the burst

protection provided by the glycol concentration. This value

will be Freeze Point for the fluid.

To configure this option with the Touch Pilot display:

To configure this option with the Navigator display:

ITEM ITEM EXPANSION

PATH

VALUE

SP.SE Setpoint Select

Operating Modes

SLCT 4-20 mA Setp

DISPLAY NAME

PATH

LINE

NO.

VALUE

Setpoint Select

Status

GENUNIT

25

4 (Dual
Setpoint Switch)

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE Setpoint Select

Operating Modes

SLCT

Dual
Setp Sw

DISPLAY

NAME

PATH

LINE

NO.

VALUE

Cooler
Fluid Type

Main Menu

Service

SERVICE1

1

1 = Water

ITEM

ITEM EXPANSION

PATH

VALUE

FLUD

Cooler Fluid Type

Configuration

SERV

Water

DISPLAY

NAME

PATH

LINE

NO.

VALUE

Cooler Fluid
Type

Main Menu

Service

SERVICE1

1

2 = Brine

Brine Freeze
Setpoint

Main Menu

Service

SERVICE1

3

Dependent on
fluid concentration

ITEM ITEM EXPANSION

PATH

VALUE

FLUD Cooler Fluid Type

Configuration

SERV Brine

LOSP

Brine Freeze
Setpoint

Configuration

SERV

Dependent on
fluid concentration


Fig. 18 — 4 to 20 mA Set Point Control

0

10

20

30

40

50

60

70

80

90

10

12

14

16

18

20

mA Signal

S

et Point

Min LWT, Cooler Fluid Type = 1, FLUD=Brine

Min LWT, Cooler Fluid Type = 1, FLUD=Water

0

2

4

6

8

Max LWT

A30-4830