Enable-off-remote contact switch (sw1), Emergency on/off switch (sw2), Energy management module (emm) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 16: Caution

Advertising
background image

16

Enable-Off-Remote Contact Switch (SW1) —

This switch is installed in all units and provides the owner and

service person with a local means of enabling or disabling the

machine. It is a 3-position switch and it is used to control the

chiller. When switched to the Enable position, the chiller will

be under its own control. When switched to the Off position,

the chiller will shut down. When switched to the Remote Con-

tact position, a field-installed dry contact can be used to start

the chiller. The contacts must be capable of handling a 24-vac,

50-mA load. In the Enable and Remote Contact (dry contacts

closed) positions, the chiller is allowed to operate and respond

to the scheduling configuration, CCN configuration, and set

point data.

For units with a Touch Pilot™ display, the position of the

Enable/Off/Remote contact switch is ignored except when the

Remote Mode operating type is selected. Refer to the Machine

Control Methods section on page 20 for more details.

Emergency On/Off Switch (SW2) —

This switch is

installed in all units. The Emergency On/Off switch should

only be used when it is required to shut the chiller off immedi-

ately. Power to all modules is interrupted when this switch is

off and all outputs from these modules will be turned off.

Energy Management Module (EMM) —

The EMM

is available as a factory-installed option or as a field-installed

accessory. See Fig. 12. The EMM receives 4 to 20 mA inputs

for the temperature reset, cooling set point and demand limit

functions. The EMM also receives the switch inputs for the

field-installed second stage 2-step demand limit and ice done

functions. The EMM communicates the status of all inputs

with the MBB, and the MBB adjusts the control point, capacity

limit, and other functions according to the inputs received. See

Table 9.

CAUTION

Care should be taken when interfacing with other manufac-

turer’s control systems due to possible power supply differ-

ences, full wave bridge versus half wave rectification,

which could lead to equipment damage. The two different

power supplies cannot be mixed. ComfortLink™ controls

use half wave rectification. A signal isolation device should

be utilized if incorporating a full wave bridge rectifier sig-

nal generating device is used.

Fig. 12 — Energy Management Module

221

221

221

221

100K

100K

100K

100K

100K

CH

17

CH

17

CH

16

CH

CH

18

CH

19

CH

20

CH

22

CH

21

CH

23

24 V

A

C

12 11

CH 11

b

CH 12

CH 1

3

CH 14

CH 15

CH

1

CH

2

CH

3

CH

4

CH 5

CH 6

CH 7

SIO LEN

+ G -

+ G -

SIO LEN

J8

J7B

J7A

J6

J5

J4

J3

J2B

J2A

J1

J9A

J9B

a30-4911

Advertising