APPENDIX F — GLOBAL TIME SCHEDULE CONFIGURATION FOR i-Vu

®

DEVICE

AND CSM CONTROLLER

The following is intended to assist a Carrier technician in

configuring a 30XW chiller so either the i-Vu

®

4.0 or 4.2 de-

vice, CCN Global Schedule Master, or a CSM controller can

Start and Stop the chiller. The 30XW chiller has unique table

naming convention for its Time Schedules that are different

than what is used today in CCN. The five steps outlined in the

procedures below must be followed in order to have the i-Vu

device and CCN products control the chiller.

Step 1 — Chiller Configuration

1. Make sure the chiller is shut down and that the Emergen-

cy On/Off Switch (SW2) is in the Off Position and the

Enable-Off-Remote (SW1) is in the Disable position.

2. Next, UPLOAD the chiller to assure the configuration is

current.
NOTE: This must be done in both NSTV and CVIEW.

3. Change the chiller’s Time Schedule Table Name from

OCCyP0xx to OCCPC0xx. See descriptions below.

LOCAL AND NETWORK TIME SCHEDULE

DESCRIPTIONS
OCCPC01S — The i-Vu 4.2 device will write to this Time

Schedule Table.
OCC2P02S — This is for Dual Setpoint Control and MUST

be Configured for 24/7 Occupied when the i-Vu device is writ-

ing to OCCPC01S.
OCCPC65E — Used with the i-Vu device or another CCN

Global Schedule Master with Single Setpoint Control.
OCC2P02E — This will only be used with Dual Setpoint Con-

trol. This is not applicable in this application.
TIME SCHEDULE TABLE NAME CHANGE
NSTV — When using NSTV to edit a Time Schedule Name,

the process is the same for both Local (S) or Network (E) Time

Schedules.

1. Highlight the chiller, then (at the top menu bar) click on

Configure

Names…

2. When the dialog box opens, scroll down to find the four

time schedules (as seen in Fig. A for Local Schedule or

Fig. B for Network Time Schedule). Highlight the desired

Time Schedule to edit.

3. At the bottom where it says New name, double click on

OCC1P01x and rename it with OCCPC01x click Save

click OK.

4. Download the new configuration to the chiller.
5. Cycle power to the MBB (main base board) using SW2

emergency stop.

CVIEW — If using CVIEW to edit a Time Schedule Name,

the process is the same for both Local (S) or Network (E) Time

Schedules.

1. Highlight the chiller and click Configure Table Names.
2. When the dialog box opens, scroll down to find the six

OCC tables.
NOTE: Only the "S" and "E" Schedules are editable.

3. Highlight the Time Schedule OCC1P01x then click Mod-

ify…

4. In the new dialog box, rename the schedule OCCPC01x

(as seen in Fig. C for Local Schedule or Fig. D for Net-

work Time Schedule) then click OK to close this dialog

box.

5. Click Close to close the Table Names dialog box.
6. Download the new configuration to the chiller.
7. Cycle power to the MBB (main base board) using SW2

emergency stop.

Fig. A — NTSV Table Name (Local Schedule)

A30-4851

Fig. B — NTSV Table Name (Network Schedule)

30-4852

Fig. C — CVIEW Table Name (Local Schedule)

-4853

Fig. D — CVIEW Table Name (Network Schedule)

0-4854