Table 15 — Configuring the Schedule with

Touch Pilot Display

Holiday Schedule — For the Touch Pilot display, the control

allows up to 16 holiday periods. All holidays are entered with

numerical values. To configure, first change the month (Holi-

day Start Month), then the day (Holiday Start Day), then the

duration (Holiday Duration) of the holiday period in days. If a

holiday in included in one of the Occupied Time Periods of the

schedule, the machine will follow that operating condition for

the holiday. In the following examples, the holidays July 4 and

December 25-26 are programmed for Holiday 1 and Holiday 2,

respectively. To configure these holidays with the Touch Pilot

display, see Table 16. To configure Holidays with the Naviga-

tor display, check the H (holiday) schedule on the Schedule

screen and program in the desired occupied times. See Fig. 16.

Table 16 — Programming Holiday Schedules with

Touch Pilot Display

Timed Override — With the Touch Pilot display only, each

time schedule can be overridden to keep the chiller in an

Occupied mode (Timed Override Hours) for 1, 2, 3 or 4 hours

on a one-time basis. To configure this option for the Touch

Pilot display:

If configured for a timed override, the override can be can-

celled by changing the Timed Override Hours to 0.
CCN Global Time Schedule — A CCN global schedule can

be used if desired. The schedule number can be set anywhere

from 65 to 99 for operation under a CCN global schedule. The

30XW chillers can be configured to follow a CCN Global

Time Schedule broadcast by another system element. The

ComfortVIEW™ Network Manager’s Configure and Modify

commands or the Service Tool’s Modify/Names function must

be used to change the number of the Occupancy Equipment

Part Table Name (OCC1P01E) to the Global Schedule Num-

ber. The Schedule Number can be set from 65 to 99

(OCC1P65E to OCC1P99E).

The Occupancy Supervisory Part table name (OCC1P01S)

number must be changed to configure the unit to broadcast a

Global Time Schedule. The Schedule Number can be set from

65 to 99 (OCC1P65S to OCC1P99S). When OCC1PxxS is set

to a value greater than 64, an occupancy flag is broadcast over

the CCN every time it transitions from occupied to unoccupied

or vice-versa. By configuring their appropriate Time Schedule

decisions to the same number, other devices on the network can

follow this same schedule. The Enable/Off/Remote Contact

must be in the Enable position or the Remote Contact position

with the contacts closed for the unit to operate. The Unit Run

Status (STAT) will indicate the current status of the machine

(OFF, RUNNING, STOPPING or DELAY), depending on the

schedule. The unit Occupied status (OCC) will indicate the

current occupied schedule according to the schedule, either NO

or YES. The Status Unit Control Type (CTRL) will be LOCAL

OFF when the switch is Off. The Status Unit Control Type will

be CCN when the Enable/Off/Remote Contact switch input is

On.

Refer to Appendix F for more detailed instructions regard-

ing global schedules and the i-Vu

®

device.

CCN Mode — To allow machine control by CCN commands,

press the Start/Stop button on the Touch Pilot™ display. The

Equipment Start screen will be displayed. Select CCN Mode.

The unit will be controlled by a CCN command to the CCN

Chiller Start/Stop variable. An external CCN device, such as

Chillervisor, controls the On/Off state of the machine. When

controlled by a Chillervisor, it is recommended that the Auto

Start When SM Lost configuration be set to Yes. In the event

of a loss of communication with the network, the machine will

start and be controlled locally.

Careful evaluation of chilled water plant control should be

reviewed. In the event local control is established, be sure that

all pumps, valves, and other devices are capable of operating

properly. The control will ignore the position of Enable/Off/

Remote Contact switch. The Run Status variable will indicate

the current status of the machine — OFF, RUNNING, DELAY,

or READY. The Control Type variable will change to CCN.

The Operating Type variable will change to CCN.

For dual chiller control applications, the slave chiller must

be enabled using the CCN Mode button.
Remote Mode — To allow machine to start and stop via a

remote contact closure, press the Start/Stop button on the

Touch Pilot display. The Equipment Start screen will be dis-

played. Select Remote Mode. The unit will be controlled by the

Enable/Off/Remote Contact switch (SW1). Switching the En-

able/Off/Remote Contact switch to the Enable or Remote

Contact position (external contacts closed) will force the unit

into an occupied state. In this mode, all CCN network force

DISPLAY NAME

PATH

LINE NO.

VALUE

Period 1 DOW (MTWTFSSH)

Config\

OCCDEFCS\

OCC1P01S

or OCC1P02S

2

10000000

Occupied from

3

00:00

Occupied to

4

03:00

Period 2 DOW (MTWTFSSH)

5

11000000

Occupied from

6

07:00

Occupied to

7

18:00

Period 3 DOW (MTWTFSSH)

8

00100000

Occupied from

9

07:00

Occupied to

10

21:30

Period 4 DOW (MTWTFSSH)

11

00011000

Occupied from

12

07:00

Occupied to

13

17:00

Period 5 DOW (MTWTFSSH)

14

00000100

Occupied from

15

07:00

Occupied to

16

12:00

DISPLAY NAME

PATH

LINE NO.

VALUE

Holiday Start Month

Config\HOLIDAY\HOLDY_01

1

7

Start Day

2

4

Duration (days)

3

1

Holiday Start Month

Config\HOLIDAY\HOLDY_02

1

12

Start Day

2

25

Duration (days)

3

2

DISPLAY NAME

PATH

LINE

NO.

VALUE

Timed Override
Hours

Config\OCCDEFCS\

OCC1P01S or OCC1P02S

1

Range: 0 to 4

Default: 0

Fig. 16 — Chiller Schedule Screen