APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

UNITS

RANGE

COMMENT

DEFAULT

CCN

TABLE

CCN

POINT

PAGE NO.

UNIT

UNIT CONFIGURATION

TYPE

Unit Type

3 = Water-Cooled
4 = Heat Machine

Air cooled

FACTORY

unit_typ

TONS

Unit Size

XXX

0 to 1800
(nominal size)

FACTORY

unitsize

VAR.A

Nb Fan on Varifan Cir A

X

0-8

Not supported.

0: No low ambient
temperature head
pressure control
1:low ambient
temperature head
pressure control

FACTORY

varfan_a

VAR.B

Nb Fan on Varifan Cir B

X

0-8

Not supported.

0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control

FACTORY

varfan_b

VAR.C

Nb Fan on Varifan Cir C

X

0-8

Not supported.

0: No low ambient
temperature head
pressure control
1: low ambient
temperature head
pressure control

FACTORY

varfan_c

VOLT

Power Supply Voltage

XXX (volt)

200-690

Acceptable values
200, 230, 380, 460,
and 575

FACTORY

voltage

60HZ

60 Hz Frequency

NO/YES

YES

FACTORY

freq_60H

STAR

Soft Starter Select

NO/YES

softstar

Y.D.

Wye Delta T Start Select

NO/YES

wye_delt

MTA.A

Must Trip Amps Cir A

XXX (amps)

0 to 1500

cpa_mtac

R.MT.A Read Must Trip Amps A

XXX (amps)

0 to 1500

cpa_mtam

MTA.B

Must Trip Amps Cir B

XXX (amps)

0 to 1500

cpb_mtac

R.MT.B Read Must Trip Amps B

XXX (amps)

0 to 1500

cpb_mtam

MTA.C

Must Trip Amps Cir C

XXX (amps)

0 to 1500

Not supported.

cpc_mtac

R.MT.C Read Must Trip Amps C

XXX (amps)

0 to 1500

Not supported.

cpb_mtam

C.SW.A S1 Config Switch Cir A

XXX (amps)

0 to 255

cpa_s1_c

R.CSA

Read S1 Config Switch A

XXX (amps)

0 to 255

cpa_s1_m

C.SW.B S1 Config Switch Cir B

XXX (amps)

0 to 255

cpb_s1_c

R.CSB

Read S1 Config Switch B

XXX (amps)

0 to 255

cpb_s1_m

C.SW.C S1 Config Switch Cir C

XXX (amps)

0 to 255

Not supported.

cpc_s1_c

R.CSC

Read S1 Config Switch C

XXX (amps)

0 to 255

Not supported.

cpc_s1_m

RECL

Heat Reclaim Select

NO/YES

Not supported.

NO

FACTORY

recl_opt

BOIL

Boiler Command Select

NO/YES

Not supported.

NO

FACTORY

ehs_sel

EMM

EMM Module Installed

NO/YES

NO

FACTORY

emm_nrcp

PAS.E

Password Enable

ENBL/DSBL

FACTORY

pass_enb

PASS

Factory Password

XXX

1 to 0150

0111

FACTORY

fac_pass

CO.HT

Cooler Heater Select

NO/YES

Not supported.

heat_sel

CON.V

Condenser Valve Select

NO/YES

NO

cond_val

46, 76

HGBP

Hot Gas Bypass Select

NO/YES

Not supported.

NO

FACTORY

hgbp_sel

29, 76

MCHX

MCHX Exchanger Select

NO/YES

Not supported.

NO

FACTORY

mchx_sel

HI.TI

High Tiers Display Select

NO/YES

highdisp

H.KIT

Hydronic Kit Selection

NO/YES

NO

PA.NB

Cooler Pass Number

1-3

2

VLT

VLT Fan Drive Select

Not supported.

NONE

RPM

VLT Fan Drive RPM

Not supported.

0

H.CON

High Condensing Select

NO/YES

NO

SERV

SERVICE CONFIGURATIONS

FLUD

Cooler Fluid Type

Water
Brine

Water

SERVICE1

flui_typ

27, 43, 45, 55

CFLU

Condenser Fluid Type

WATER
BRINE

cond_typ

MOP

EXV MOP Setpoint

XX.X
(deg F/deg C)

40-60 F
(4.4-15.6 C)

62.0

SERVICE1

mop_sp

HP.TH

High Pressure Threshold

XXX.X (psi/kPa) 250-280 psi

(1724-1930 kPa)

290

SERVICE1

hp_th

SHP.A

Cir A Superheat Setp

XX.X (

F/C)

3-14 F
(1.7-7.8 C)

14.4

SERVICE1

sh_sp_a

SHP.B

Cir B Superheat Setp

XX.X (

F/C)

3-14 F
(1.7-7.8 C)

14.4

SERVICE1

sh_sp_b

SHP.C

Cir C Superheat Setp

XX.X (

F/C)

3-14 F
(1.7-7.8 C)

14.4

SERVICE1

sh_sp_c

HTR

Cooler Heater DT Setp

XX.X (

F/C)

0.5-9 F
(0.3-5.0 C)

2.0
38.0

SERVICE1

heatersp

EWTO

Entering Water Control

NO/YES

NO

SERVICE1

ewt_opt

25

AU.SM

Auto Start When SM Lost

NO/YES

NO

SERVICE1

auto_sm

25

LLWT

Brine Minimum Fluid Temp

XX.X
(deg F/deg C)

–20-38 F
(–28.9-3.3 C)

Not supported.

LOSP

Brine Freeze Setpoint

XX.X
(deg F/deg C)

–20-50 F
(–20-10 C)

34

SERVICE1

lowestsp

27, 43-45, 55

FL.SP

Brine Flow Switch Setp

0-60

Not supported.

1

SERVICE

flow_sp

HD.PG

Varifan Proportion Gain

XX.X

–10-10

Not supported.

2.0

SERVICE1

hd_pg

46

HD.DG

Varifan Derivative Gain

XX.X

–10-10

Not supported.

0.4

SERVICE1

hd_dg

46

HD.IG

Varifan Integral Gain

XX.X

–10-10

Not supported.

0.2

SERVICE1

hd_ig

46

F.LOA

Fast Load Select

0-4

0

fastload

AVFA

Fan A Drive Attach

NO/YES

Not supported.

NO

AVFB

Fan B Drive Attach

NO/YES

Not supported.

NO

AVFC

Fan C Drive Attach

NO/YES

Not supported.

NO

EWT.S

EWT Probe on Cir A Side

NO/YES

YES

ewt_cirA

MAXL

Max Condenser LWT 45DC

NO/YES

NO

max_clwt