APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)

MODE — CONFIGURATION (cont)

ITEM

EXPANSION

UNITS

RANGE

COMMENT

DEFAULT

CCN TABLE

CCN POINT

PAGE NO.

OPTN

OPTIONS CONFIGURATION

CCNA

CCN Address

XXX

1-239

1

N/A

CCNA

CCNB

CCN Bus Number

XXX

0-239

0

N/A

CCNB

BAUD

CCN Baud Rate

2400
4800
9600
19200
38400

9600

N/A

BAUD

LOAD

Loading Sequence Select

Equal
Staged

EQUAL

USER

lead_cir

29

LLCS

Lead/Lag Circuit Select

Automatic
Cir A Leads
Cir B Leads
Cir C Leads

AUTOMATIC

USER

seq_typ

29, 55

RL.S

Ramp Load Select

ENBL/DSBL

DSBL

USER

ramp_sel

35

DELY

Minutes Off Time

XX (Minutes)

1 to 15

1

USER

off_on_d

29

ICE.M

Ice Mode Enable

ENBL/DSBL

DSBL

USER

ice_cnfg

41

HPUM

Condenser Pumps Sequence

X

No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual

Not supported.

NO PUMP

hpum_seq

47

PUMP

Cooler Pumps Sequence

No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual

NO PUMP

USER

pump_seq

28, 47

ROT.P

Pump Rotation Delay

XXXX (hours)

24 to 3000

Not supported.

48

USER

pump_del

28, 55

PM.PS

Periodic Pump Start

NO-YES

Not supported.

NO

USER

pump_per

28, 55

P.SBY

Stop Pump In Standby

NO-YES

Not supported.

NO

USER

pump_sby

P.LOC

Flow Checked if Pmp Off

NO-YES

Not supported.

YES

USER

pump_loc

28

LS.ST

Night Low Noise Start

XX.XX

00.00-23.59

00.00

USER

nh_start

LS.ND

Night Low Noise End

XX.XX

00-00-23.59

00.00

USER

nh_end

LS.LT

Low Noise Capacity Lim

XXX (%)

0-100

100

USER

nh_limit

55

RV.AL

Reverse Alarms Relay

NO-YES

NO

USER

al_rever

OA.TH

Heat Mode OAT Threshold

XX.X
(deg F/deg C)

Not supported.

5 F

USER

heat_th

FREE

Free Cooling OAT Limit

XX.X
(deg F/deg C)

Not supported.

32.0

USER

free_oat

CUR.S

Current Limit Select

NO/YES

NO

curr_sel

39-41

CUR.F

Current Limit at 100%

XXXX

0 to 5000

2000

curr_ful

40-41

RSET

RESET, DEMAND LIMIT, MASTER/SLAVE

CRST

Cooling Reset Type

No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
Space Temp

NO RESET

USER

cr_sel

33, 36, 55

HRST

Heating Reset Type

No Reset
Out Air Temp
Delta T Temp
4-20 mA Input

Not supported.

NO RESET

USER

hr_sel

DMDC

Demand Limit Select

None
Switch
4-20 mA Input

NONE

USER

lim_sel

39-41, 55

DMMX

mA for 100% Demand Limit

XX.X (mA)

0.0

USER

lim_mx

40, 41

DMZE

mA for 0% Demand Limit

XX.X (mA)

0.0

USER

lim_ze

40, 41

MSSL

Master/Slave Select

Disable
Master
Slave

DISABLE

MST_SLV

ms_sel

32-35, 55

SLVA

Slave Address

XXX

1-236

2

MST_SLV

slv_addr

29, 32-35

LLBL

Lead/Lag Balance Select

Always Lead
Lag if Fail
Runtime Sel

Always
Lead

MST_SLV

ll_bal

29, 32-35,
54

LLBD

Lead/Lag Balance Delta

XXX (hours)

40-400

168

MST_SLV

ll_bal_d

29, 32-35

LLDY

Lead/Lag Delay

XX (minutes)

2-30

10

MST_SLV

lsrt_tim

30, 32-35,
54

LL.ER

Start if Error Higher

XX.X
(deg F/deg C)

3-18

4

MST_SLV

start_dt

30, 32-35

LAG.M

Lag Minimum Running Time

XXX
(min)

0-150

0

MST_SLV

lag_mini

30, 32-35

LAGP

Lag Unit Pump Select

OFF if U stp
ON if U stp

OFF if U stp

MST_SLV

lag_pump

30, 32-35,
54

LPUL

Lead Pulldown Time

XX (minutes)

0-60

0

MST_SLV

lead_pul

30, 32-35,
54

SERI

Chillers in Series

NO/YES

ll_serie

29, 32-35