Carrier AQUAFORCE 30XW150-400 User Manual
Page 62
62
Table 40 — EXV Modes and Submodes
Table 41 — Color Indicators when
Moisture is Present in Refrigerant
Liquid Line Service Valve — This valve is located immediately
ahead of filter drier, and has a
1
/
4
-in. access connection for field
charging. In combination with compressor discharge service
valve, each circuit can be pumped down into the high side for
servicing.
EXV TYPE AND CIRCUIT
TOUCH PILOT™ PATH
NAVIGATOR™ PATH
EXV, Circuit A
Main Menu
Status
QCK_TST1
Q_EXVA
Service Test Mode
QUIC
EXV.A
EXV, Circuit B
Main Menu
Status
QCK_TST1
Q_EXVB
Service Test Mode
QUIC
EXV.B
Economizer EXV, Circuit A
Main Menu
Status
QCK_TST1
Q_ECO_A
Service Test Mode
QUIC
ECO.A
Economizer EXV, Circuit B
Main Menu
Status
QCK_TST1
Q_ECO_B
Service Test Mode
QUIC
ECO.B
COLOR INDICATOR
R-134a,
75 F (24 C)
(ppm)
R-134a,
125 F (52 C)
(ppm)
Green — Dry
<30
<45
Yellow-green — Caution
30-100
45-170
Yellow — Wet
>100
>170
CLOSED
OPEN
CLOSED
OPEN
GASKET
OPEN VALVE IN QUICK TEST SUB-MODE BEFORE DISASSEMBLING
EF05BD271 NV 32.5mm
EF05BD331 NV 36mm
50Nm (36 ft-lb)+ 30°
27mm / 1
1
/
16
''
27mm / 1
1
/
16
''
DISASSEMBLY
ASSEMBLY
NOTES:
1. Push down on valve piston to close valve before assembling.
2. After valve is assembled close valve in Quick Test sub-mode or cycle power before opening service valve.
Fig. 44 — Disassembly and Assembly of EXV Motor
NOTE: Open valve in Quick Test sub-mode before disassembling.
A30-4072ef