Table 40 — EXV Modes and Submodes

Table 41 — Color Indicators when

Moisture is Present in Refrigerant

Liquid Line Service Valve — This valve is located immediately

ahead of filter drier, and has a

1

/

4

-in. access connection for field

charging. In combination with compressor discharge service

valve, each circuit can be pumped down into the high side for

servicing.

EXV TYPE AND CIRCUIT

TOUCH PILOT™ PATH

NAVIGATOR™ PATH

EXV, Circuit A

Main Menu

Status

QCK_TST1

Q_EXVA

Service Test Mode

QUIC

EXV.A

EXV, Circuit B

Main Menu

Status

QCK_TST1

Q_EXVB

Service Test Mode

QUIC

EXV.B

Economizer EXV, Circuit A

Main Menu

Status

QCK_TST1

Q_ECO_A

Service Test Mode

QUIC

ECO.A

Economizer EXV, Circuit B

Main Menu

Status

QCK_TST1

Q_ECO_B

Service Test Mode

QUIC

ECO.B

COLOR INDICATOR

R-134a,

75 F (24 C)

(ppm)

R-134a,

125 F (52 C)

(ppm)

Green — Dry

<30

<45

Yellow-green — Caution

30-100

45-170

Yellow — Wet

>100

>170

CLOSED

OPEN

CLOSED

OPEN

GASKET

OPEN VALVE IN QUICK TEST SUB-MODE BEFORE DISASSEMBLING

EF05BD271 NV 32.5mm
EF05BD331 NV 36mm

50Nm (36 ft-lb)+ 30°

27mm / 1

1

/

16

''

27mm / 1

1

/

16

''

DISASSEMBLY

ASSEMBLY

NOTES:

1. Push down on valve piston to close valve before assembling.
2. After valve is assembled close valve in Quick Test sub-mode or cycle power before opening service valve.

Fig. 44 — Disassembly and Assembly of EXV Motor

NOTE: Open valve in Quick Test sub-mode before disassembling.

A30-4072ef

Advertising