Oil Charge — When additional oil or a complete charge is

required it must meet the following specifications:
• Manufacturer. . . . . . . . . . . . . . . . . . . . . Emkarate RL220XL

• Oil Type. . . . . . . . . . . . . . . . . . . Inhibited polyolester-based

synthetic compressor lubricant for use with screw compressors.
• ISO Viscosity Grade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

Do not reuse drained oil or any oil that has been exposed to

the atmosphere.

Oil is available in the following quantities from your local

Carrier representative:

If unsure if there is low oil charge in the system, follow the

steps below:

1. If the unit shuts off repeatedly from a low oil level alert it

may be an indication of inadequate oil charge; however, it

could also indicate that the oil is not being recovered from

the low-side of the system.

2. Begin running the unit at full load for 1

1

/

2

hours. Use the

manual Test Mode feature of Service Test if the unit does

not normally run at full load.

NOTE: An adequate load must be available.

3. After running the unit for 1

1

/

2

hours at full load, allow the

unit to restart and run normally. If low oil alarms persist,

continue with the following steps.

4. Close the liquid line service valve and place a pressure

gage on top of the cooler. Enable the Service Test feature

and turn the Enable/Off/Remote switch to the enable po-

sition. Start the desired circuit by turning it on under the

TEST function: CP.A for compressor A, CP.B for com-

pressor B, or CP.C for compressor C.

5. When the compressor starts successfully observe the

cooler pressure when the pressure reads 10 psig

(68.9 kPa), turn the Emergency Switch (SW2) to the OFF

position. The compressor should stop.

6. Open the liquid line service valve and allow the unit to

restart normally. If low oil level alarms persist, continue

with the following steps.

7. If none of the previous steps were successful, the unit is

low on oil charge. Add oil to the oil separator using the

1

/

4

in. access fitting that the discharge pressure transducer

is mounted to.

8. To facilitate the oil charging process, ensure that the unit

is not running when adding oil. The system is under pres-

sure even when the unit is not running, so it is necessary

to use a suitable pump to add oil to the system.

9. Using a suitable pump, add

1

/

2

gal (1.9 l) of oil to the

system. Continue adding oil in

1

/

2

gal (1.9 l) increments

until the problem is resolved, up to a maximum of 1.5 gal

(5.7 l). If it is necessary to add factory oil charge levels to

the system contact your local Carrier representative.

Oil Filter Maintenance — Each circuit has one oil filter locat-

ed externally to the compressor. Oil line pressure drop is

monitored by the control. Oil line pressure drop is calculated

by subtracting oil pressure (OP) from discharge pressure (DP).

If the oil line pressure drop exceeds 30 psi (206.8 kPa) for

5 minutes the control will generate a High Oil Filter Pressure

Drop alert. The High Oil Filter Pressure Drop alert will

not shut down the compressor, but instead indicates that the

oil filter is dirty. If oil pressure line losses exceed 50 psi

(344.7 kPa) then the control will shut down the circuit on

Maximum Oil Filter Differential Pressure Failure.

Replacing the Oil Filter — Close the oil line ball valve locat-

ed in front of the oil filter. Connect a charging hose to the

1

/

4

-in.

access fitting port located downstream of the valve and bleed

off oil trapped between the service valve and the oil solenoid

valve. A quart of oil is typically what is removed during this

process. Remove the charging hose. Unscrew the nuts from

both ends of the oil filter and remove the oil filter. Remove the

protective caps from the new oil filter and install, being careful

not to lose or damage the new O-ring located on the new oil fil-

ter. Draw a vacuum at the Schrader port. Remove the charging

hose and open the oil line ball valve. Check both fittings for

leaks.

Cooler

SUCTION SERVICE VALVE — The suction service valve

is a factory-installed option for 30XW units. It is located in the

suction outlet of the cooler. The suction service valve is bolted

between the cooler outlet and the suction flange piping. The

suction service valve shaft has a locking device located on the

shaft to lock the valve in either a fully open position or a fully

closed position. The locking device must be pulled out prior to

moving the valve handle to a fully open or a fully closed posi-

tion. See Fig. 47A and 47B.

QUANTITY

TOTALINE PART NO.

1 Quart

P903-2325

1 Gallon

P903-2301

5 Gallon

P903-2305

CAUTION

Compressor oil is pressurized. Use proper safety precau-

tions when relieving pressure.

CLOSED AND UNLOCKED
SUCTION SERVICE VALVE

OPENED AND LOCKED
SUCTION SERVICE VALVE

Fig. 47A — Suction Service Valve Locking Device,

Closed and Unlocked

Fig. 47B — Suction Service Valve Locking Device,

Open and Locked

A30-4843