Table 50 — Master/Slave Alarm Code

LEGEND

Table 51 — Illegal Configuration Alarm Code

Cooler Pump Fault
Alarm 100 — Pump 1 Fault (P.32)

Alarm 101 — Pump 2 Fault (P.33)
Criteria for Trip — The criterion is tested whether the units are

ON or OFF. This alarm will be generated if the cooler pump

interlock opens. When starting the pump, the control must

read an open circuit for 3 consecutive reads. If the pump is

operating and the circuit opens, the alarm will be generated

immediately.
Action to be Taken — The pump and machine will be shut

down. If there is another pump available, the control will start

that pump, restart the machine and clear the alarm. If no other

pump is available, the unit will remain OFF.
Reset Method — Manual.
Possible Causes — If this condition is encountered, check the

following items:

• interlock wiring circuit

• control signal to the pump controller

• cooler pump contactor for proper operation

• control voltage for proper voltage (on 208-volt systems, be

sure the proper tap on TRAN1 is utilized)

Alarm 102 — Condenser Flow Switch Failure (P.15)
Criteria for Trip — The criteria are tested whether the unit is

ON or OFF. This alarm is generated if the lockout switch

(located in the Energy Management Module) is closed during

normal operation.
Action to be Taken — All compressors are shut down immedi-

ately without going through pumpdown, and unit is not

allowed to start.
Reset Method — Automatic, first occurrence in 24 hours.

Manual, if more than one occurrence in 24 hours.

Possible Causes — If this condition is encountered, check the

following items:

• chilled water flow switch operation

• water flow. Be sure all water isolation valves are open and

check water strainer for a restriction

• interlock wiring circuit

• power supply to the pump

• control signal to the pump controller

• condenser water pump operation

• condenser pump contactor for proper operation
Reclaim Operation Failure
Alarm 103 — Circuit A (P.34)

Alarm 104 — Circuit B (P.35)
NOTE: Alarms 103 and 104 are not used or supported. If this

condition is encountered, confirm machine configuration.
High Condensing Temperature — Out of Compressor

Envelope
Alarm 105 — Circuit A (P.37)

Alarm 106 — Circuit B (P.38)
Criteria for Trip — The criterion is tested when the circuit is

ON. This alarm will be tripped if the circuit capacity is reduced

more than 8 times in 30 minutes due to high discharge gas tem-

peratures. If no override occurs in a 30-minute period, the

counter is reset.
Action to be Taken — The affected circuit will be shut down.
Reset Method — Automatic, after 30 minutes. If the alarm is

cleared via the Manual method, the counter will be reset to

zero.
Possible Causes — If this condition is encountered, check the

following items:

• Maximum Condensing Temperature (MCT) for the proper

setting

• noncondensables in the refrigerant circuit

• low condenser water flow

• refrigerant charge (overcharged)

• condenser tubes fouled

• discharge service valve to be sure that it is open. Check the

discharge pressure transducer for accuracy

• unit configuration

MC

ERROR

CODE

MASTER

SLAVE

DESCRIPTION

01

X

X

The master or slave water pump is not configured while the control of the lag unit pump is required
(lag_pump = 1)

02

X

Master and slave units have the same network address.

03

X

There is no slave configured at the slave address

04

X

Slave pump_seq incorrect configuration

05

X

There is a conflict between the master and the slave LWT option: the master is configured for EWT control
while the slave is configured for LWT control.

06

X

There is a conflict between the master and the slave LWT option: the master is configured for LWT control
while the slave is configured for EWT control.

07

X

There is a conflict between the master and the slave pump option: the master is configured for lag pump
control while the slave is not configured for lag pump control.

08

X

There is a conflict between the master and the slave pump option: the master is not configured for lag pump
control while the slave is configured for lag pump control.

09

X

X

The slave chiller is in local or remote control (chilstat = 3)

10

X

X

The slave chiller is down due to fault (chilstat = 5)

11

X

The master chiller operating type is not Master: master_oper_typ

12

X

X

No communication with slave.

13

X

Master and slave heat cool status are not the same.

EWT — Entering Water Temperature
LWT — Leaving Water Temperature

FC

ERROR

CODE

DESCRIPTION

01

Unit size is unknown.

02

Reclaim option selected for Heat Pump machine.

03

Hot Gas Bypass configured for a Heat Pump machine.