Carrier AQUAFORCE 30XW150-400 User Manual

Page 47

Advertising
background image

47

6. Fill the chiller fluid circuit with clean water (with recom-

mended inhibitor added) or other non-corrosive fluid to

be cooled. Bleed all air out of high points of system. If

unit is exposed to temperatures below 32 F (0° C), suffi-

cient inhibited propylene glycol or other suitable corro-

sion inhibited antifreeze should be added to the chiller

water and condenser water circuit to prevent possible

freeze-up. The chilled water loop must be cleaned before

the unit is connected. To set the maintenance time for

cleaning and inspecting loop strainers, go to Water Filter

Ctrl (days), W.FIL. Values for this item are counted as

days. Refer to the system pump package literature for

specific internal inspection/cleaning requirements.

7. Check tightness of all electrical connections.
8. Verify power supply phase sequence. The phase sequence

should be A-B-C for proper compressor rotation.

START-UP

Actual Start-Up —

Actual start-up should be done only

under supervision of a qualified refrigeration technician.

1. Be sure all discharge, oil, and suction valves (if equipped)

and liquid line service valves are open.

2. Using the unit control, set leaving-fluid set point (Cool-

ing Setpoint 1, CSP.1). No cooling range adjustment is

necessary.

3. If optional control functions or accessories are being

used, the unit must be properly configured. Refer to

Configuration Options section for details.

4. Start the chilled fluid and condenser pumps, if unit is not

configured for pump control. (Cooler Pumps Sequence,

PUMP=0; Condenser Pump Sequence, HPUM = No)

5. Complete the Start-Up Checklist to verify all components

are operating properly.

6. Check the cooler flow switch for proper operation. En-

sure that the flow switch input indicates closed when the

pump is on and open when the pump is off.

7. Turn Enable/Off/Remote contact switch to Enable position.
8. Allow unit to operate and confirm that everything is

functioning properly. Check to see that leaving fluid

temperature agrees with leaving set point Control Point

(Control Point, CTPT).

Operating Limitations

TEMPERATURES — Unit operating temperature limits are

listed in Table 35.
Low Condenser Water Temperature Operation — For con-

denser entering water temperatures between 33 F (0.6 C) and

65 F (18.3 F), field installed accessory head pressure control

valve is required. Contact your Carrier representative for

details.

Table 35 — Temperature Limits for Standard Units

LEGEND

*Temperature limit for high condensing/heat reclaim option units are

140 F (60 C).

†For sustained operation, EWT should not exceed 85 F (29.4 C).

**Unit requires brine modification for operation below this

temperature.

VOLTAGE
Main Power Supply — Minimum and maximum acceptable

supply voltages are listed in the Installation Instructions.
Unbalanced 3-Phase Supply Voltage — Never operate a motor

where a phase imbalance between phases is greater than 2%.

To determine percent voltage imbalance:

The maximum voltage deviation is the largest difference

between a voltage measurement across 2 legs and the average

across all 3 legs.

Example: Supply voltage is 240-3-60.
AB = 243v
BC = 236v
AC = 238v

1. Determine average voltage:

2. Determine maximum deviation from average voltage:

(AB) 243 – 239 = 4 v

(BC) 239 – 236 = 3 v

(AC) 239 – 238 = 1 v
Maximum deviation is 4 v.

3. Determine percent voltage imbalance:

= 1.7%

This voltage imbalance is satisfactory as it is below the

maximum allowable of 2%.

MINIMUM FLUID LOOP VOLUME — To obtain proper

temperature control, loop fluid volume must be at least 3 gal-

lons per ton (3.25 L per kW) of chiller nominal capacity for air

conditioning and at least 6 gallons per ton (6.5 L per kW) for

CAUTION

Do not manually operate contactors. Serious damage to the

machine may result.

CAUTION

Brine duty application (below 40 F [4.4 C] LCWT) for

chiller normally requires factory modification. Contact a

Carrier Representative for details regarding specific

applications. Operation below 40 F (4.4 C) LCWT with-

out modification can result in compressor failure.

TEMPERATURE

F

C

Maximum Condenser EWT

110

43.3

Minimum Condenser EWT

65

18.3

Maximum Condenser LWT*

118

47.8

Maximum Cooler EWT†

70

21.1

Maximum Cooler LWT

60

15.6

Minimum Cooler LWT**

40

4.4

EWT

Entering Fluid (Water) Temperature

LWT

Leaving Fluid (Water) Temperature

% Voltage Imbalance = 100 x

max voltage deviation from

avg voltage

average voltage

Average voltage =

243+236+238

3

=

717
3

= 239

% Voltage Imbalance = 100 x

4

239

IMPORTANT: If the supply voltage phase imbal-

ance is more than 2%, contact the local electric

utility company immediately. Do not operate unit

until imbalance condition is corrected.

Advertising