Appendix c — ccn tables (cont), Status display tables (cont) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 121

Advertising
background image

121

APPENDIX C — CCN TABLES (cont)

STATUS DISPLAY TABLES (cont)

*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.

*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.

*Yes = service test function enable.

†0 = capacity frozen (unchanged).

1 = capacity increase.
2 = capacity decrease.

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

QCK_TST1

Quick Test Enable

no/Yes

Q_TSTRQ

forcible

Circuit A EXV Position

0 - 100

%

Q_EXVA

forcible

Circuit B EXV Position

0 - 100

%

Q_EXVB

forcible

Circuit C EXV Position

0 - 100

%

Q_EXVC

forcible

Cir A Economizer EXV Pos

0 - 100

%

Q_ECO_A

forcible

Cir B Economizer EXV Pos

0 - 100

%

Q_ECO_B

forcible

Cir C Economizer EXV Pos

0 - 100

%

Q_ECO_C

forcible

Circuit A Fan Stages

0-10

Q_FAN_A

forcible

Circuit B Fan Stages

0-10

Q_FAN_B

forcible

Circuit C Fan Stages

0-10

Q_FAN_C

forcible

Circuit A Head Press Speed

0 - 100

%

Q_VFANA

forcible

Circuit B Head Press Speed

0 - 100

%

Q_VFANB

forcible

Circuit C Head Press Speed

0 - 100

%

Q_VFANC

forcible

Circuit A Oil Heater

Off/On

Q_HT_A

forcible

Circuit A Oil Solenoid

Off/On

Q_OILS_A

forcible

Circuit A Slide Valve 1

Off/On

Q_SLI_1A

forcible

Circuit A Slide Valve 2

Off/On

Q_SLI_2A

forcible

Cir A Heater Ball Valve

Off/On

Q_BVL_A

forcible

Cir A Hot Gas Bypass

Off/On

Q_HGBP_A

forcible

Cir A DGT Cool Solenoid

Off/On

Q_CDGT_B

forcible

Circuit B Oil Heater

Off/On

Q_HT_B

forcible

Circuit B Oil Solenoid

Off/On

Q_OILS_B

forcible

Circuit B Slide Valve 1

Off/On

Q_SLI_1B

forcible

Circuit B Slide Valve 2

Off/On

Q_SLI_2B

forcible

Cir A Heater Ball Valve

Off/On

Q_BVL_B

forcible

Cir B Hot Gas Bypass

Off/On

Q_HGBP_B

forcible

Cir B DGT Cool Solenoid

Off/On

Q_CDGT_B

forcible

Circuit C Oil Heater

Off/On

Q_HT_C

forcible

Circuit C Oil Solenoid

Off/On

Q_OILS_C

forcible

Circuit C Slide Valve 1

Off/On

Q_SLI_1C

forcible

Circuit C Slide Valve 2

Off/On

Q_SLI_2C

forcible

Cir C Heater Ball Valve

Off/On

Q_BVL_C

forcible

Cir C Hot Gas Bypass

Off/On

Q_HGBP_C

forcible

Cooler Heater Output

Off/On

Q_CL_HT

forcible

Water Exchanger Pump 1

Off/On

Q_PMP1

forcible

Water Exchanger Pump 2

Off/On

Q_PMP2

forcible

Condenser Pump 1

Off/On

Q_HPMP1

forcible

Condenser Pump 2*

Off/On

Q_HPMP2

forcible

Chiller Ready Output

Off/On

Q_READY

forcible

Chiller Running Output

Off/On

Q_RUN

forcible

Cir A Running Output

Off/On

Q_RUN_A

forcible

Cir B Running Output

Off/On

Q_RUN_B

forcible

Cir C Running Output*

Off/On

Q_RUN_C

forcible

Chiller Capacity in 0-10v

0 – 10.0

volt

Q_CATO

forcible

Customer Shutdown Out

Off/On

Q_SHUT

forcible

Alarm Relay Output

Off/On

Q_ALARM

forcible

Alert Relay Output

Off/On

Q_ALERT

forcible

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

QCK_TST2*

Quick Test Enable

no/Yes

Q_TSTRQ

forcible

Air Cond Enter Valve A

Off/On

Q_HREA_A

forcible

Air Cond Leaving Valv A

Off/On

Q_HRLA_A

forcible

Water Cond Enter Valv A

Off/On

Q_HREW_A

forcible

Water Cond Leav Valve A

Off/On

Q_HRLW_A

forcible

Air Cond Enter Valve B

Off/On

Q_HREA_B

forcible

Air Cond Leaving Valv B

Off/On

Q_HRLA_B

forcible

Water Cond Enter Valv B

Off/On

Q_HREW_B

forcible

Water Cond Leav Valve B

Off/On

Q_HRLW_B

forcible

HR Condenser Heater

Off/On

Q_CD_HT

forcible

4 way Valve Circuit A

Off/On

Q_RV_A

forcible

4 way Valve Circuit B

Off/On

Q_RV_B

forcible

Free Cooling Heater

On/Off

Q_FC_HTR

forcible

Free Cool A EXV Position

0 - 100

%

Q_FCEXVA

forcible

Free Cool B EXV Position

0 - 100

%

Q_FCEXVB

forcible

Free Cool A Ball Valve

Off/On

Q_FCBVL_A

forcible

Free Cool B Ball Valve

Off/On

Q_FCBVL_B

forcible

TABLE

DISPLAY NAME

RANGE

UNITS

POINT NAME

WRITE STATUS

SERV_TST

Service Test Enable*

no/Yes

Q_STREQ

forcible

Compressor A Output

Off/On

Q_CPA

forcible

Slide Valve Capacity A

0 - 2†

Q_SLIA

forcible

Compressor B Output

Off/On

Q_CPB

forcible

Slide Valve Capacity B

0 - 2†

Q_SLIB

forcible

Compressor C Output

Off/On

Q_CPC

forcible

Slide Valve Capacity C

0 - 2†

Q_SLIC

forcible