Carrier AQUAFORCE 30XW150-400 User Manual

Page 14

Advertising
background image

14

Table 6 — EXV1 Board Inputs and Outputs (30XW150-325)

Table 7 — EXV1,2 Board Inputs and Outputs* (30XW350,400)

*“X” denotes the circuit: 1 = Circuit A; 2 = Circuit B.

DESCRIPTION

INPUT/OUTPUT

I/O TYPE

DISPLAY MODULE POINT NAME

CONNECTION POINT

Pin

Notation

Power (24 vac supply)

EXVA-J1

11

24 vac

12

Ground

Local Equipment Network

EXVA-J4

1

RS485 Port (D+)

2

RS485 Port (Gnd)

3

RS485 Port (D–)

Circuit A Suction Gas Thermistor

SGTA

5k Thermistor

Compressor Suction Temp, SGT.A

EXVA-J3

TH

A

Circuit B Suction Gas Thermistor

SGTB

5k Thermistor

Compressor Suction Temp, SGT.B

EXVA-J3

TH

B

Circuit A EXV

EXV-A

Stepper Motor

EXV Position, EXV.A

EXVA-J2A

1

2

3

4

Circuit B EXV

(size 325 only)

EXV-B

Stepper Motor

EXV Position, EXV.B

EXVA-J2B

1

2

3

4

DESCRIPTION

INPUT/OUTPUT

I/O TYPE

DISPLAY MODULE POINT NAME

CONNECTION POINT

Pin

Notation

Power (24 vac supply)

EXVX-J1

11

24 vac

12

Ground

Local Equipment Network

EXVX-J4

1

RS485 Port (D+)

2

RS485 Port (Gnd)

3

RS485 Port (D–)

Circuit X Suction Gas Thermistor

SGT X

5k Thermistor

Compressor Suction Temp, SGT.X

EXVX-J3

TH

A

Circuit X Economizer Gas Thermistor

ECT X

5k Thermistor

Economizer Gas Temp, ECT.X

EXVX-J3

TH

B

Circuit X EXV

EXV-X

Stepper Motor

EXV Position, EXV.X

EXVX-J2A

1

2

3

4

Circuit X Economizer EXV

ECEXV-X

Stepper Motor

Cir X Economizer EXV Pos, ECO.X

EXVX-J2A

1

2

3

4

Advertising