Appendix c — ccn tables (cont), Configuration tables (cont) – Carrier AQUAFORCE 30XW150-400 User Manual

Page 126

Advertising
background image

126

APPENDIX C — CCN TABLES (cont)

CONFIGURATION TABLES (cont)

*Not supported.
†Only condenser pump sequence 1 is supported.

NOTES:
1. Flow checked if pump off needed when a command is sent to the primary

pump to prevent cooler from freezing in winter conditions. Command will
set the cooler flow switch to closed while the controls stop the cooler
pump. The controls may then generate an alarm. If this decision is active,
the cooler flow switch is not checked when the cooler pump is stopped.

2. If cooling reset select set point has been selected the set point based on

4-20mA input signal through ComfortLink™ control, then a 4-20 mA reset

function shall be ignored. Configuration 3 (4-20mA Control) and 4 (Space
Temperature) shall require an Energy Management Module.

3. Configuration 2 (4-20mA Control) shall require an Energy Management

Module. Configuration 1 Switch Demand limit provides 3 step demand limit
if an Energy Management Module is present. Otherwise, only one step is
allowed.

4. Reverse Alarms Relay configuration will be deenergized when an alarm

and alert relay is present and will be energized when no alarm is present.

TABLE

DISPLAY NAME

RANGE

DEFAULT

UNITS

POINT NAME

USER

Circuit Loading Sequence

0-3
0=Auto,
1=A Lead
2=B Lead,
3 =C Lead

0

lead_cir

Staged Loading Sequence

No/Yes

No

seq_typ

Ramp Loading Select

No/Yes

No

ramp_sel

Unit Off to On Delay

1-15

1

min

off_on_d

Condenser Pumps Sequence

0-4†

0

hpumpseq

Cooler Pumps Sequence

0-4
0=No Pump
1=One Pump Only
2=Two Pumps Auto
3=Pump#1 Manual
4=Pump#2 Manual

0

cpumpseq

Pump Auto Rotation Delay

24-3000

48

hours

pump_del

Pump Sticking Protection

No/Yes

No

pump_per

Stop Pump During Standby

No/Yes

No

pump_sby

Flow Checked if Pump Off

No/Yes

No

pump_loc

Auto Changeover Select*

No/Yes

No

auto_sel

Cooling Reset Select

0-4

0

cr_sel

Heating Reset Select*

0-4
1 =OAT*,
0=None
2=Delta T,
3=4-20mA Control
4=Space Temp

0

hr_sel

Demand Limit Type Select

0-2
0=None
1=Switch Control
2=4-20mA Control

0

lim_sel

mA For 100% Demand Limit

0-20

0

ma

lim_mx

mA For 0% Demand Limit

0-20

10

ma

lim_ze

Current Limit Select

No/Yes

No

curr_sel

Current Limit at 100%

0 to 2000

2000

amps

curr_ful

Heating OAT Threshold*

-4-32

5

°F

heat_th

Free Cooling Delta T Th*

14.4-27

18

°F

free_dt

Full Load Timeout

20-300

30

min

fc_tmout

HSM Both Command Select

No/Yes

No

both_sel

NIGHT CONTROL

Start Hour

00:00-24:00

00:00

nh_start

End Hour

00:00-24:00

00:00

nh_end

Capacity Limit

0-100

100

%

nh_limit

Ice Mode Enable

No/Yes

No

ice_cnfg

Reverse Alarms Relay

No/Yes

No

al_rever

Cooler pump off in heat

No/Yes

No

stopheat

Cond pump off in cool

No/Yes

No

stopcool