Table 53 — Testing Circuit A Oil Solenoid

LEGEND FOR FIG. 53

MODE

(Red LED)

SUB-MODE

KEYPAD

ENTRY

ITEM

DISPLAY

EXPANSION

VALUE

DESCRIPTION

(Units)

COMMENT

SERVICE TEST

Service Test Mode

TEST

Manual Sequence

QUIC

Q.REQ

PASS WORD

Password may be required

0111

Each

will lock in the next

digit. If 0111 is not the password,

use the arrow keys to change the

password digit and press

when correct.

Q.REQ

Returns to the original field

OFF

OFF

OFF will flash

ON

The Enable/Off/Remote Contact
switch must be in the OFF
position.

Q.REQ

EXV.A

Press 15 times.

OLS.A

Oil Solenoid cir.A

OFF

OFF

OFF will flash

ON

ON

OLS.A will turn on.

ON

1 will flash

OFF

OFF

OLS.A will turn off.

ALM

Isolation

FIOP

Factory-Installed Option

ALT

Alert

HGBP — Hot Gas Bypass

CB

Circuit Breaker

LWT

Leaving Water Temperature

CDFS

Condenser Flow Switch

MBB

Main Base Board

CPM

Compressor Protection Module

MLV

Minimum Load Valve

CPMP

Condenser Pump Relay

PL

Plug

CWFS

Chilled Water Flow Switch

PMP

Pump

DPT

Discharge Pressure and Temperature

SGT

Saturated Gas Temperature

ECEXV — Economizer Electronic Expansion Valve

SHD

Loadshed

ECT

Entering Cooler Temperature

SPT

Suction Pressure Transducer

EMM

Energy Management Module

TB

Terminal Block

EXV

Electronic Expansion Valve