START-UP CHECKLIST FOR 30XW LIQUID CHILLERS

A. PROJECT INFORMATION

Job Name ________________________________________________________________________________________
Address __________________________________________________________________________________________
City ________________________________ State ________________________ Zip ___________________________
Installing Contractor ________________________________________________________________________________
Sales Office _______________________________________________________________________________________
Start-up Performed By ______________________________________________________________________________

Design Information

Unit

Model _______________________________________ Serial ______________________________________

Compressors

Compressor A

Model _______________________________________ Serial ______________________________________

Compressor B

Model _______________________________________ Serial ______________________________________

Evaporator

Model _______________________________________ Serial ______________________________________

Condenser

Model _______________________________________ Serial ______________________________________

B. PRELIMINARY EQUIPMENT CHECK (This section to be completed by installing contractor)

1. Is there any physical damage?

 Yes

 No

Will this prevent start-up?

 Yes

 No

Description

___________________________________________________________________________________________
___________________________________________________________________________________________

2. Unit is installed level as per the installation instructions.

 Yes

 No

3. Power supply agrees with the unit nameplate.

 Yes

 No

4. Correct control voltage ________vac.

 Yes

 No

5. Electrical power wiring is installed properly.

 Yes

 No

6. Unit is properly grounded.

 Yes

 No

7. Electrical circuit protection has been sized and installed properly.

 Yes

 No

8. All terminals are tight.

 Yes

 No

9. All plug assemblies are tight.

 Yes

 No

10. All cables, thermistors and transducers have been inspected for cross wires.

 Yes

 No

11. All thermistors are fully inserted into wells.

 Yes

 No

12. Relief valve vent piping per local codes.

 Yes

 No

13. Mechanical room temperature maintained above 50 F (10 C).

 Yes

 No

Chilled Water System Check

1. All chilled water valves are open.

 Yes

 No

2. All piping is connected properly.

 Yes

 No

3. All air has been purged from the system.

 Yes

 No

4. Chilled water pump is operating with the correct rotation.

 Yes

 No

5. Chilled water pump starter interlocked with chiller.

 Yes

 No

6. Chilled water flow switch operational.

 Yes

 No

7. Inlet piping to evaporator includes a 20 mesh strainer within 10 ft.

 Yes

 No

8. Water loop volume greater than 3 gal/ton for air conditioning

or 6 gal/ton for process cooling and low ambient operation.

 Yes

 No

9. Proper loop freeze protection provided to ____

F (C) for brine applications.

 Yes

 No

Antifreeze type__________________ Concentration _____%.

 Yes

 No

10. Outdoor piping wrapped with electric heater tape.

 Yes

 No

CAPACITY

EWT

LWT

FLUID TYPE

FLOW RATE

P.D.

Evaporator
Condenser