Record configuration information – Carrier AQUAFORCE 30XW150-400 User Manual

Page 145

Advertising
background image

CL-5

Record Configuration Information

*Not supported.

TOUCH PILOT™

DESCRIPTION

NAVIGATOR

ITEM

NAVIGATOR™

SUBMODE

RANGE

DEFAULT

ENTRY

Cooling Setpoint 1

CSP.1

Set Point

COOL

XXX.X

44.0° F

Cooling Setpoint 2

CSP.2

Set Point

COOL

XXX.X

44.0° F

Cooling Ice Setpoint

CSP.3

Set Point

COOL

XXX.X

44.0° F

Current No Reset Value (Cooling)

CRV1

Set Point

COOL

XXX.X

0

Current Full Reset Value (Cooling)

CRV2

Set Point

COOL

XXX.X

0

Delta T No Reset Value (Cooling)

CRT1

Set Point

COOL

XXX.X

0

Delta T Full Reset Value (Cooling)

CRT2

Set Point

COOL

XXX.X

0

OAT No Reset Value (Cooling)

CRO1

Set Point

COOL

XXX.X

14.0° F

OAT Full Reset Value (Cooling)

CRO2

Set Point

COOL

XXX.X

14.0° F

Space T No Reset Value

CRS1

Set Point

COOL

XXX.X

14.0° F

Space T Full Reset Value

CRS2

Set Point

COOL

XXX.X

14.0° F

Cooling Reset Deg. Value

DGRC

Set Point

COOL

XX.X

0

Cool Changeover Setpoint

CAUT

Set Point

COOL

XXX.X

75° F

Cooling Ramp Loading

CRMP

Set Point

COOL

X.X

1.0

Heating Setpoint 1

HSP.1

Set Point

HEAT

XXX.X

100.0° F

Heating Setpoint 2

HSP.2

Set Point

HEAT

XXX.X

100.0° F

Current No Reset Value (Heating)

HRV1

Set Point

HEAT

XXX.X

0

Current Full Reset Value (Heating)

HRV2

Set Point

HEAT

XXX.X

0

Delta T No Reset Value (Heating)

HRT1

Set Point

HEAT

XXX.X

0

Delta T Full Reset Value (Heating)

HRT2

Set Point

HEAT

XXX.X

0

OAT No Reset Value (Heating)

HRO1

Set Point

HEAT

XXX.X

14.0° F

OAT Full Reset Value (Heating)

HRO2

Set Point

HEAT

XXX.X

14.0° F

Heating Reset Deg. Value

DGRH

Set Point

HEAT

XX.X

0

Heating Changeover Setpoint

HAUT

Set Point

HEAT

XX.X

64.0° F

Heat Ramp Loading

HRMP

Set Point

HEAT

X.X

1.0

Switch Limit Setpoint 1

DLS1

Set Point

MISC

XXX

100

Switch Limit Setpoint 2

DLS2

Set Point

MISC

XXX

100

Switch Limit Setpoint 3

DLS3

Set Point

MISC

XXX

100

Water Val Condensing Stp

W.SCT

Set Point

MISC

XXX.X

95.0° F

None (I/O Button)

OPER

Operating Modes

SLCT

X

Setpoint Select

SP.SE

Operating Modes

SLCT

X

Heal/Cool Select

HC.SE

Operating Modes

SLCT

X

COOLING