Carrier AQUAFORCE 30XW150-400 User Manual

Page 23

Advertising
background image

23

commands, except the Emergency Stop Command will be

ignored. The Run Status variable will indicate the current sta-

tus of the machine (OFF, RUNNING, DELAY, or READY),

depending on the position of the Remote/Off/Enable Switch

closure. The Chiller Occupied? variable will change to YES.

The Control Type variable will change to Remote. The Oper-

ating Type variable will change to Remote.
Master Mode — To activate Dual Chiller Control, each ma-

chine must be individually configured for Dual Chiller Control.

To operate the machines in Dual Chiller Mode, one machine

must be designated as the master unit and one machine as the

slave unit. On the master unit, press the Start/Stop button on the

Touch Pilot display. The Equipment Start screen will be dis-

played. Select Master Mode. Failure to start the Master unit in

this manner will cause both machines to operate in local mode.

The Master Unit Control can be done locally, remotely or

through CCN commands per the master/slave configuration

(Master Control Type). The control will ignore the position of

Enable/Off/Remote Contact switch if the Master Control

Type is configured for Local Control or CCN Control. The

Run Status variable, Chiller Occupied? variable, and Con-

trol Type variable will change based on the Master Control

Type configured above and the Machine On/Off Control de-

fined above. The Operating Type variable will change to

Master.
To Turn Machine Off — To turn the machine off, press the

Start/Stop button on the Touch Pilot display. See Fig. 17. The

machine will shut down. While the unit is in Local Off, it will

remain shut down and ignore all CCN commands as well as

the position of Enable/Off/Remote Contact switch. The Run

Status variable, indicating the current status of the machine,

will change to OFF. The Chiller Occupied? variable will

change to NO. The Control Type variable will indicate

Local. The Operating Type variable will change to L-OFF

(Local Off).

NAVIGATOR™ DISPLAY MACHINE CONTROL — Ma-

chine On/Off control with the Navigator display is determined

by the configuration of the Operating Type Control (OPER).

Options to control the machine locally via a switch, from a lo-

cal Time Schedule, or via a Carrier Comfort Network

®

com-

mand are offered. See Table 17.

The schedules consist of 8 user-configurable occupied time

periods. The control supports time schedules for local control,

remote control, and ice building. These time periods can be

flagged to be in effect or not in effect on each day of the week.

The day begins at 00.00 and ends at 24.00. The machine is in

unoccupied mode unless a scheduled time period is in effect. If

an occupied period is to extend past midnight, the occupied

period must end at 24:00 hours (midnight) and a new occupied

period must be programmed to begin at 00:00 hours.

In the following example, a early morning pulldown time

period is scheduled for Monday morning from 12:00 AM to

3:00 AM. The occupied period starts at 7:00 AM, Monday

through Saturday. The occupied time ends at 6:00 PM on Mon-

day and Tuesday, 9:30 PM on Wednesday, 5:00 PM on Thurs-

day and Friday, and 12:00 PM on Saturday.
NOTE: This schedule was designed to illustrate the program-

ming of the schedule function and is not intended as a recom-

mended schedule for chiller operation.
Switch Control — In the Switch Control operating type, the

Enable/Off/Remote Contact switch controls the machine local-

ly. All models are factory configured with Operating Type

Control (OPER) set to SWITCH CTRL (Switch Control).

With SWITCH CTRL, switching the Enable/Off/Remote

Contact switch to the Enable or Remote Contact position (ex-

ternal contacts closed) will put the chiller in an occupied state.

The Unit Run Status (STAT) will indicate the current status of

the machine and will change from OFF to RUNNING or

DELAY. The unit Occupied Status (OCC) will change from

NO to YES. The Status Unit Control Type (CTRL) will change

from LOCAL OFF when the switch is Off to LOCAL ON

when in the Enable position or in the Remote Contact position

with external contacts closed.

Table 17 — Navigator Start/Stop Control

Fig. 17 — Equipment Stop Screen

ITEM

ITEM EXPANSION

PATH

VALUE

OPER

Operating Control
Type

Operating
Modes

SLCT

OPER

SWITCH
CTRL

CONTROL

METHOD

(OPER)

ACTIVE

OPERATING

TYPE

REMOTE/OFF/ENABLE

SWITCH

REMOTE ON/OFF

SWITCH

TIME SCHEDULE 1

CCN CHILLER

START/STOP

(CHIL_S_S)

EMERGENCY

STOP

(EMSTOP)

ALARM

REMOTE

LOCKOUT

SWITCH

UNIT

STATUS

All

Local Off

Off

Off

Remote

Open

Off

Enable

Off

Yes

Off

Closed

Off

Switch

Control

Local On

Enable

Disable

On

Remote

Closed

Disable

On

Time

Schedule

Local

Schedule

Enable

Occupied

Disable

On

Remote

Closed

Occupied

Disable

On

Unoccupied

Disable

Off

CCN

Control

CCN

Remote

Closed

Enable

Disable

On

Remote

Closed

Disable

Disable

Off

Enable

Enable

Disable

On

Enable

Disable

Disable

Off