APPENDIX B — NAVIGATOR™ DISPLAY TABLES

MODE — RUN STATUS

*As data in all of these categories can exceed 9999 the following display strategy is used:
From 0-9999 display as 4 digits.
From 9999-99999 display xx.xK
From 99900-999999 display as xxxK.

ITEM

EXPANSION

UNITS

RANGE

COMMENT

WRITE

STATUS

CCN TABLE

CCN POINT

PAGE

NO.

VIEW

AUTO DISPLAY

EWT

Entering Fluid Temp

XXXX.X
(deg F/deg C)

0-100

STATEGEN

COOL_EWT

44

LWT

Leaving Fluid Temp

XXX.X
(deg F/deg C)

0-100

STATEGEN

COOL_LWT

44

SETP

Active Setpoint

XXX.X
(deg F/deg C)

0-100

GENUNIT

SP

35, 55

CTPT

Control Point

XXX.X
(deg F/deg C)

0-100

GENUNIT

CTRL_PNT

35

STAT

Unit Run Status

Off
Running
Stopping
Delay

GENUNIT

STATUS

22-25

OCC

Occupied

NO/YES

GENUNIT

CHIL_OCC

22-25

CTRL

Status Unit Control Type

Local Off
Local On
CCN
Remote

GENUNIT

ctr_type

22-25

CAP

Percent Total Capacity

XXX (%)

0-100

GENUNIT

CAP_T

CAP. A

Percent Capacity Cir A

XXX (%)

0-100

GENUNIT

CAPA_T

CAP. B

Percent Capacity Cir B

XXX (%)

0-100

GENUNIT

CAPB_T

CAP. C

Percent Capacity Cir C

XXX (%)

0-100

GENUNIT

CAPC_T

CAP. S

Capacity Indicator

XX

0-32

MAINT

OVER_CAP

43

LIM

Active Demand Limit Val

XXX (%)

0-100

GENUNIT

DEM-LIM

CURR

Actual Chiller Current

XXX (amps)

0-4000

GENUNIT

TOT_CURR

CUR.L

Chiller Current Limit

XXX (amps)

0-4000

GENUNIT

CURR_LIM

ALRM

Alarm State

0=Normal
1=Partial
2=Shutdown

GENUNIT

ALM

68

EMGY

Emergency Stop

DSBL/ENBL

GENUNIT

EMSTOP

CH.SS

CCN Chiller Start Stop

DSBL/ENBL

GENUNIT

CHILL_S_S

HC.ST

Heat Cool Status

0=Cooling
1=Heating
2=Standby

Heating and
Standby not
supported.

GENUNIT

HEATCOOL

45

RC.ST

Reclaim Select Status

NO/YES

Not supported.

GENUNIT

reclaim_sel

TIME

Time of Day

XX.XX

00:00-23:59

N/A

TIME

MNTH

Month of Year

1=January
2=February
3=March
4=April
6=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December

N/A

moy

DATE

Day of Month

XX

1-31

N/A

dom

YEAR

Year of Century

XX

00-99

N/A

yoc

RUN

MACHINE STARTS/HOURS

HRS.U

Machine Operating Hours

XXXX (hours)

0-999000*

forcible

hr_mach

STR.U

Machine Starts

XXXX

0-9999*

forcible

STRTHOUR

st_mach

HR.P1

Water Pump 1 Run Hours

XXXX (hours)

0-999000*

Not supported.

forcible

FANHOURS

hr_cpum1

HR.P2

Water Pump 2 Run Hours

XXXX (hours)

0-999000*

Not supported.

forcible

FANHOURS

hr_cpum2

HR.P3

Condenser Pump 1 Hours

XXXX (hours)

0-999999*

Not supported.

forcible

FANHOURS

hr_hpump1

HOUR

COMPRESSOR RUN HOURS

HR.A

Compressor A Run Hours

XXXX (hours)

0-999000*

forcible

STRTHOUR

hr_cp_a

HR.B

Compressor B Run Hours

XXXX (hours)

0-999000*

forcible

STRTHOUR

hr_cp_b

HR.C

Compressor C Run Hours

XXXX (hours)

0-999000*

forcible

STRTHOUR

hr_cp_c

STRT

COMPRESSOR STARTS

ST.A

Compressor A Starts

XXXX

0-999000*

forcible

STRTHOUR

st_cp_a

ST.B

Compressor B Starts

XXXX

0-999000*

forcible

STRTHOUR

st_cp_b

ST.C

Compressor C Starts

XXXX

0-999000*

forcible

STRTHOUR

st_cp_c