EXV TROUBLESHOOTING PROCEDURE — There are

two different economizer EXVs. Both of the economizer

EXVs have a total of 2785 steps. There are three different main

EXVs, which all have a total of 4260 steps. The EXV motor

moves at 150 steps per second. Commanding the valve to

either 0% or 100% will add an additional 160 steps to the

move, to ensure the valve is open or closed completely.

Follow the steps below to diagnose and correct EXV

problems. Check EXV motor operation first. Switch the

Enable/Off/Remote (EOR) Contact switch to the Off position.

Check the appropriate circuit EXV, Circuit A EXV % Open

(Circuit A EXV Position, EXV.A) or Circuit B EXV % Open

(Circuit B EXV Position, EXV.B). The current value of 0 will

be displayed. Increase the EXV position to select 100% valve

position. The actuator should be felt moving through the EXV.

To close the valve, select 0%. The actuator should knock when

it reaches the bottom of its stroke. See Table 40 for a list of

EXV modes and submodes.

If the valve is not working properly, continue with the fol-

lowing test procedure:

Check the 8-position DIP switch on the board for the proper

address (Fig. 10). Check the EXV output signals at appropriate

terminals on the EXV module. For 30XW150,325 units, con-

nect the positive test lead to EXV-J2A terminal 5 for Circuit A

and to EXV-J2B terminal 5 for Circuit B.

For 30XW175,200,350,400 units connect positive test lead

to EXV(X)-J2A terminal 5 for EXV(X) and EXV(X)-J2B ter-

minal 5 for Economizer EXV(X). Using the Service Test pro-

cedure on page 83, move the valve output under test to 100%.

DO NOT short meter leads together or pin 5 to any other pin,

as board damage will occur. During the next several seconds,

carefully connect the negative test lead to pins 1,2,3 and 4 in

succession. Digital voltmeters will average this signal and

display approximately 6 vdc. If the output remains at a constant

voltage other than 6 vdc or shows 0 volts, remove the connec-

tor to the valve and recheck.

Select 0% to close the valve.

NOTE: When the valve is stationary, the output from the EXV

board is 12-vdc.

See Tables 6 and 7. If a problem still exists, replace the

EXV board. If the reading is correct, the expansion valve and

EXV wiring should be checked. Check the EXV connector and

interconnecting wiring.

1. Check color-coding and wire connections. Make sure

they are connected to the correct terminals at the EXV

board and EXV plug and that the cables are not crossed.

2. Check for continuity and tight connection at all pin

terminals.

Check the resistance of the EXV motor windings. For

30XW150,325 units remove the EXV module plug EXV-J2A

for Circuit A EXV and EXV-J2B for Circuit B EXV. For

30XW175,200,350,400 units remove the EXV module plug

EXV(X)-J2A for main EXV and EXV(X)-J2B for economizer

EXV. Check the resistance of the two windings between pins 1

and 3 for one winding and pins 2 and 4 for the other winding.

The resistance should be 52 ohms (± 5.2 ohms). Also check

pins 1-4 for any shorts to ground.
Inspecting/Opening Electronic Expansion Valves

To check the physical operation of an EXV, the following

steps must be performed.

1. Close the liquid line service valve of the circuit to be

checked. Put the Enable/Off/Remote Contact (EOR)

switch in the Off position. Enter the Service Test mode

and change Service Test Enable, T.REQ from OFF to

ON. A password may be required. Switch the EOR

switch to the Enable position. Under the COMP sub-

mode, enable one of the compressors (CP.xn) for the cir-

cuit. Let compressor run until gage on suction pressure

port reads 10 psig (68.9 kPa). Turn the compressor off.

The compressor will turn off. Immediately after the com-

pressor shuts off, manually close the actuated ball valve

(ABV). If the unit is equipped with suction service valves

and economizer service valves, close both valves. Clos-

ing the valves will minimize the amount of charge that

will have to be removed from the system after pump

down.

2. Remove any remaining refrigerant from the system low

side using proper recovering techniques. The economizer

assembly has a

1

/

4

-in. access connection which can be

used to remove charge from the inlet of the EXVs. Turn

off the line voltage power supply to the compressors.

3. The expansion valve motor is hermetically sealed inside

the top portion of the valve. See Fig. 43. Disconnect the

EXV plug. Carefully unscrew the motor portion from the

body of the valve. The EXV operator will come out with

the motor portion of the device. Reconnect the EXV plug.

4. Enter the appropriate EXV test step under the (QUIC)

Service Test mode Locate the desired item Circuit A

EXV Position, EXV.A or Circuit B EXV Position,

EXV.B. Change the position to 100%. Observe the opera-

tion of the lead screw. See Fig. 43. The motor should be

turning, raising the operator closer to the motor. Motor

actuator movement should be smooth and uniform from

fully closed to fully open position. Select 0% and check

open to closed operation. If the valve is properly connect-

ed to the processor and receiving correct signals, yet does

not operate as described above, the sealed motor portion

of the valve should be replaced.

Installing EXV Motor

If re-installing the motor, be sure to use a new gasket in the

assembly. See Fig. 44. It is easier to install the motor assembly

with the piston in the fully closed position. Insert the motor into

the body of the EXV. Tighten the motor to the body to 36 ft-lb

(50 N-m) and then tighten the valve another 30 degrees.
Moisture Liquid Indicator — Clear flow of liquid refrigerant

indicates sufficient charge in system. Bubbles in the sight glass

indicate undercharged system or presence of noncondensables.

Moisture in system, measured in parts per million (ppm),

changes color of indicator. See Table 41. Change filter drier at

first sign of moisture in system.

Filter Drier — Whenever moisture-liquid indicator shows

presence of moisture, replace filter drier(s). There is one filter

drier assembly on each circuit with two cores. Refer to the Car-

rier Standard Service Techniques Manual, Chapter 1, Refriger-

ants, for details on servicing filter driers.

IMPORTANT: Obtain replacement gaskets before

opening EXV. Do not re-use gaskets.

CAUTION

Ensure refrigerant is removed from both the inlet and outlet

of EXV assemblies. Equipment damage could result.

IMPORTANT: Obtain replacement gasket before

opening EXV. Do not re-use gaskets.

IMPORTANT: Unit must be in operation at least

12 hours before moisture indicator can give an accu-

rate reading.
With unit running, indicating element must be in con-

tact with liquid refrigerant to give true reading.