CCN Control — With CCN Operating Type control, the ma-

chine operates under CCN control as long as the Enable/Off/

Remote Contact Switch is in the Enable or Remote Contact

position (external contacts closed.) To operate under this

Operating Control, OPER must be set to CCN CONTROL. An

external CCN device, such as Chillervisor, controls the On/Off

state of the machine. When controlled by a Chillervisor, it is

recommended that the Auto Start When SM Lost (AU.SM) be

set to Yes.

Careful evaluation of Chilled Water Plant control should be

reviewed. In the event Local Control is established, be sure that

all pumps, valves, and other devices are capable of operating

properly. In the event of a loss of communication with the net-

work, the machine will start and be controlled locally. The

CCN device forces the variable CHIL_S_S to control the chill-

er. The Unit Run Status (STAT) will indicate the current status

of the machine (OFF, RUNNING, STOPPING or DELAY),

depending on the CCN command. The unit Occupied status

(OCC) will indicate the current occupied state according to the

CCN command and will be displayed as either NO or YES.

The Status Unit Control Type (CTRL) will be LOCAL OFF

when the Enable/Off/Remote Contact switch is Off. The Status

Unit Control Type will be CCN when the Enable/Off/Remote

Contact switch input is Closed and the CHIL_S_S variable is

Stop or Start.

For Dual Chiller Control applications, the Slave Chiller

must be enabled using the CCN CONTROL option.

Entering Fluid Control Option —

The factory de-

fault for the chilled water fluid set point is controlling to the

leaving water temperature. An option to configure the machine

for entering water control is available. The control operation

remains the same except the control point is focused on the

entering water temperature, rather than the leaving water tem-

perature when configured.

To configure this option for the Touch Pilot™ display:

To configure this option for the Navigator™ display:

Cooling Set Point Selection —

Several options for

controlling the Leaving Chilled Water Set Point are offered and

are configured by the Cooling Set Point Select (Setpoint Se-

lect, SP.SE) variable. In addition to the Cooling Set Point Se-

lect, Ice Mode Enable discussed later in this book, and Heat

Cool Select (Heat/Cool Select, HC.SE) variables also have a

role in determining the set point of the machine. All units are

shipped from the factory with the Heat Cool Select set to 0.

All default set points are based on Leaving Water Control

(Entering Fluid Control, EWTO) set to No. Values must be

confirmed for the individual set points. Limits for the set points

are listed in the configurations noted below.

To configure these options for the Touch Pilot display, see

Table 20A. To configure these options for the Navigator dis-

play, see Table 20B.

Table 20A — Cooling Set Point Selection

with Touch Pilot Display

Table 20B — Cooling Set Point Selection

with Navigator Display

In all cases, there are limits on what values are allowed for

each set point. These values depend on the Cooler Fluid Type

and the Brine Freeze Set point, discussed later. See Table 21.

Table 21 — Configuration Set Point Limits

*The minimum set point for Medium Temperature Brine applications

is related to the Brine Freeze Point. The set point is limited to be no
less than the Brine Freeze Point +5° F (2.8° C).

The Setpoint Select configuration can be set to five different

control options: Set Point Occupancy, Set Point 1, Set Point 2,

4-20 mA Input, and Dual Switch.

SET POINT OCCUPANCY — Set Point Occupancy is the

default configuration for the Setpoint Select variable. When

Setpoint Select (Setpoint Select, SP.SE) is configured to 0

(Setpoint Occ), the unit’s active set point is based on Cooling

Set Point 1 (Cooling Setpoint 1, CSP.1) during the occupied

period while operating under Time Schedule 1 (SCH1). If the

Time Schedule 2 (SCH2) is in use, the unit’s active set point is

based on Cooling Set Point 1 (Cooling Setpoint 1, CSP.1) dur-

ing the occupied period and Cooling Set Point 2 (Cooling Set-

point 2, CSP.2) during the unoccupied period. See Tables 22

and 23.

To configure this option while using a Touch Pilot display:

To change this value, a Control Point Force must be applied.

When configured correctly, Setpoint Control (Setpoint Con-

trol, SP.SE) will indicate Auto.

To configure this option while using a Navigator display:

ITEM

ITEM EXPANSION

PATH

VALUE

OPER

Operating Control
Type

Operating
Modes

SLCT

OPER

CCN
CONTROL

AU.SM

Auto Start when
SM Lost

Configuration

SERV

YES

DISPLAY NAME

PATH

LINE

NO.

VALUE

Entering Fluid
Control

Service\
SERVICE1

5

No = Leaving Water Control
Yes = Entering Water Control

ITEM

ITEM EXPANSION

PATH

VALUE

EWTO

Entering Water
Control

Configuration

SERV

No = Leaving
Water Control
Yes = Entering
Water Control

DISPLAY NAME

PATH

LINE NO.

VALUE

Cooling Setpoint 1

Setpoint

2

Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)

Cooling Setpoint 2

Setpoint

3

Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)

Cooling Ice Setpoint

Setpoint

4

Range: -20 to 32 F
(–28.9 to 0 C)
Default: 44 F (6.6 C)

ITEM

ITEM EXPANSION

PATH

VALUE

CSP.1 Cooling Setpoint 1

Setpoints

COOL

Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)

CSP.2 Cooling Setpoint 2

Setpoints

COOL

Range: 14 to 70 F
(–10.0 to 21.1 C)
Default: 44 F (6.6 C)

CSP.3 Ice Setpoint

Setpoints

COOL

Range: -20 to 32 F
(–28.9 to 0 C)
Default: 44 F (6.6 C)

SET POINT LIMITS

COOLER FLUID TYPE

(COOLER FLUID TYPE, FLUD)

1, Water

2, Brine

Minimum *

38 F (3.3 C)

14 F (–10.0 C)

Maximum

60 F (15.5 C)

CAUTION

Brine duty application (below 40 F [4.4 C] LCWT) for

chiller normally requires factory modification. Contact a

Carrier Representative for details regarding specific

applications. Operation below 40 F (4.4 C) LCWT with-

out modification can result in compressor failure.

DISPLAY NAME

PATH

LINE NO.

VALUE

Setpoint select

Status

GENUNIT

25

0 (Setpoint Occupied)

ITEM

ITEM EXPANSION

PATH

VALUE

SP.SE

Setpoint Select

Operating Modes

SLCT

Setpoint Occ