APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)

LEGEND

TOUCH PILOT DESCRIPTION

TOUCH PILOT

POINT NAME

TOUCH PILOT PATH

LINE

READ/

WRITE

CCN TABLE NAME

Motor Temperature
Circuit A

CP_TMP_A

MAIN MENU\Status\CIRCA_AN

9

RO

Status Display Tables\CIRCA_AN

Circuit B

CP_TMP_B

MAIN MENU\Status\CIRCB_AN

9

RO

Status Display Tables\CIRCB_AN

Circuit C

CP_TMP_C

MAIN MENU\Status\CIRCC_AN

9

RO

Status Display Tables\CIRCC_AN

Next Sequence Allowed in
Circuit A

def_se_a

MAIN MENU\Maint\DEFROSTM

20

RO

Maintenance Display Tables\DEFROSTM

Circuit B

def_se_b

MAIN MENU\Maint\DEFROSTM

20

RO

Maintenance Display Tables\DEFROSTM

Oil Heater
Circuit A

Q_HT_A

MAIN MENU\Status\QCK_TST1

15

RW

Status Display Tables\QCK_TST1

Circuit B

Q_HT_B

MAIN MENU\Status\QCK_TST1

22

RW

Status Display Tables\QCK_TST1

Circuit C

Q_HT_C

MAIN MENU\Status\QCK_TST1

29

RW

Status Display Tables\QCK_TST1

Oil Heater Output
Circuit A

OIL_HT_A

MAIN MENU\Status\CIRCA_D

5

RO

Status Display Tables\CIRCA_D

Circuit B

OIL_HT_B

MAIN MENU\Status\CIRCB_D

5

RO

Status Display Tables\CIRCB_D

Circuit C

OIL_HT_C

MAIN MENU\Status\CIRCC_D

5

RO

Status Display Tables\CIRCC_D

Oil Level Input
Circuit A

OIL_L_A

MAIN MENU\Status\CIRCA_D

7

RO

Status Display Tables\CIRCA_D

Circuit B

OIL_L_B

MAIN MENU\Status\CIRCB_D

7

RO

Status Display Tables\CIRCB_D

Circuit C

OIL_L_C

MAIN MENU\Status\CIRCC_D

7

RO

Status Display Tables\CIRCC_D

Oil Pressure
Circuit A

OP_A

MAIN MENU\Status\CIRCA_AN

6

RO

Status Display Tables\CIRCA_AN

Circuit B

OP_B

MAIN MENU\Status\CIRCB_AN

6

RO

Status Display Tables\CIRCB_AN

Circuit C

OP_C

MAIN MENU\Status\CIRCC_AN

6

RO

Status Display Tables\CIRCC_AN

Oil Pressure Difference
Circuit A

DOP_A

MAIN MENU\Status\CIRCA_AN

7

RO

Status Display Tables\CIRCA_AN

Circuit B

DOP_B

MAIN MENU\Status\CIRCB_AN

7

RO

Status Display Tables\CIRCB_AN

Circuit C

DOP_C

MAIN MENU\Status\CIRCC_AN

7

RO

Status Display Tables\CIRCC_AN

Oil Solenoid
Circuit A

Q_OILS_A

MAIN MENU\Status\QCK_TST1

16

RW

Status Display Tables\QCK_TST1

Circuit B

Q_OILS_B

MAIN MENU\Status\QCK_TST1

23

RW

Status Display Tables\QCK_TST1

Circuit C

Q_OILS_C

MAIN MENU\Status\QCK_TST1

30

RW

Status Display Tables\QCK_TST1

Oil Solenoid Output
Circuit A

OIL_SL_A

MAIN MENU\Status\CIRCA_D

6

RO

Status Display Tables\CIRCA_D

Circuit B

OIL_SL_B

MAIN MENU\Status\CIRCB_D

6

RO

Status Display Tables\CIRCB_D

Circuit C

OIL_SL_C

MAIN MENU\Status\CIRCC_D

6

RO

Status Display Tables\CIRCC_D

Optimal Fan Count
Circuit A

fancop_a

MAIN MENU\Maint\FANCTRL

4

RO

Maintenance Display Tables\FANCTRL

Circuit B

fancop_b

MAIN MENU\Maint\FANCTRL

8

RO

Maintenance Display Tables\FANCTRL

Circuit C

fancop_c

MAIN MENU\Maint\FANCTRL

12

RO

Maintenance Display Tables\FANCTRL

Override State
Circuit A

over_d_a

MAIN MENU\Maint\DEFROSTM

8

RO

Maintenance Display Tables\DEFROSTM

Circuit B

over_d_b

MAIN MENU\Maint\DEFROSTM

25

RO

Maintenance Display Tables\DEFROSTM

Percent Total Capacity
Circuit A

CAPA_T

MAIN MENU\Status\CIRCA_AN

2

RO

Status Display Tables\CIRCA_AN

Circuit B

CAPB_T

MAIN MENU\Status\CIRCB_AN

2

RO

Status Display Tables\CIRCB_AN

Circuit C

CAPC_T

MAIN MENU\Status\CIRCC_AN

2

RO

Status Display Tables\CIRCC_AN

Pump Differential Press.
Circuit A

fc_dp_a

MAIN MENU\Status\FREECOOL

19

RO

Status Display Tables\FREECOOL

Circuit B

fc_dp_b

MAIN MENU\Status\FREECOOL

29

RO

Status Display Tables\FREECOOL

Circuit C

fc_dp_c

MAIN MENU\Status\FREECOOL

39

RO

Status Display Tables\FREECOOL

Pump Inlet Pressure
Circuit A

fc_inp_a

MAIN MENU\Status\FREECOOL

17

RO

Status Display Tables\FREECOOL

Circuit B

fc_inp_b

MAIN MENU\Status\FREECOOL

27

RO

Status Display Tables\FREECOOL

RO — Read Only