In the following example, 2-step demand limit based on

capacity is desired with the first switch closure limiting the

capacity to 60%. The second switch closure is to limit the

capacity to 40%. Demand Limit Switch 1 is 60% and Demand

Limit Switch 2 is 40%.

Switch Controlled (Current Based) — If using 2-step de-

mand limit control, an energy management module must be

installed. One-step demand limit control does not require the

energy management module. Four parameters for 1-step switch

control must be configured. For 2-step control, five parameters

must be configured. The parameters are: the type of Demand

Limit Selection (Demand Limit Type Select, DMDC), the

setting for Switch Limit Set Point 1 (Switch Limit Setpoint 1,

DLS1), the setting for Switch Limit Set Point 2 (Switch Limit

Setpoint 2, DLS2), the Current Limit Select (Current Limit

Select, CUR.S), and the Compressor Current limit at 100%

signal, (Current Limit at 100%, CUR.F).

To configure this option with the Touch Pilot display:

To configure this option with the Navigator™ display:

EXTERNALLY POWERED (4 to 20 mA) CAPACITY

BASED DEMAND LIMIT — The energy management

module is required for 4 to 20 mA demand limit control. An

externally powered 4 to 20 mA signal must be connected to

TB6-1 and TB6-2. To configure demand limit for 4 to 20 mA

control based on unit capacity, four parameters must be config-

ured. The parameters are: the type of Demand Limit Selection

(Demand Limit Type Select, DMDC), the current at which

100% capacity limit takes place (mA For 100% Demand

Limit, DMMX), the current at which 0% capacity limit takes

place (mA For 0% Demand Limit, DMZE), and the Current

Limit Selection (Current Limit Select, CUR.S).

To configure this option with the Touch Pilot™ display:

To configure this option with the Navigator display:

In the following example, a 4 mA signal is Demand Limit

100% and a 20 mA Demand Limit signal is 0%. The 4 to

20 mA signal is connected to TB6-1 and TB6-2. The demand

limit is a linear interpolation between the two values entered. In

Fig. 24, if the machine receives a 12 mA signal, the machine

controls will limit the capacity to 50%.
EXTERNALLY POWERED (4 to 20 mA) CURRENT

BASED DEMAND LIMIT — The energy management

module is required for 4 to 20 mA demand limit control. An

externally powered 4 to 20 mA signal must be connected to

TB6-1 and TB6-2. To configure demand limit for 4 to 20 mA

control based on compressor current, five parameters must be

configured. The parameters are: the type of Demand Limit

Selection (Demand Limit Type Select, DMDC), the current at

which 100% capacity limit takes place (mA For 100%

Demand Limit, DMMX), the current at which 0% capacity

limit takes place (mA For 0% Demand Limit, DMZE), the

Current Limit Selection (Current Limit Select, CUR.S), and

the Compressor Current limit at 100% signal (Current Limit

at 100%, CUR.F).

To configure this option with the Touch Pilot display:

TOUCH PILOT DISPLAY

NAVIGATOR DISPLAY

Display Name

Value

Item

Value

Demand Limit Type Select

1

DMDC

SWITCH

Switch Limit Setpoint 1

60%

DSL1

60%

Switch Limit Setpoint 2

40%

DSL2

40%

Current Limit Select

No

CUR.S

NO

DISPLAY NAME

PATH

LINE

NO.

VALUE

Demand Limit
Type Select

Config

USER

24

1 (Switch Control)
Default = 0
(None)

Switch Limit
Setpoint 1

Setpoints

SETPOINT

33

Default = 100%

Switch Limit
Setpoint 2

Setpoints

SETPOINT

34

(Not required
for 1-Step)
Default = 100%

Current Limit
Select

Config

USER

30

Yes
Default = No

Current Limit
at 100%

Config

USER

31

Default =
2000.0 Amps

ITEM

ITEM EXPANSION

PATH

VALUE

DMDC

Demand Limit
Select

Configuration

RSET

SWITCH
Default =
NONE

DSL1

Switch Limit
Setpoint 1

Setpoints

MISC

Default =
100%

DSL2

Switch Limit
Setpoint 2

Setpoints

MISC

(Not required
for 1-Step)
Default =
100%

CUR.S

Current Limit
Select

Configuration

OPTN

NO
Default: NO

CUR.F

Current Limit
at 100%

Configuration

OPTN

Default =
2000

CAUTION

Care should be taken when interfacing with other control

systems due to possible power supply differences such as a

full wave bridge versus a half wave rectification. Connec-

tion of control devices with different power supplies may

result in permanent damage. ComfortLink™ controls

incorporate power supplies with half wave rectification. A

signal isolation device should be utilized if the signal gen-

erator incorporates a full wave bridge rectifier.

DISPLAY NAME

PATH

LINE NO.

VALUE

Demand Limit
Type Select

Config

USER

24

2 (4-20mA Control)
Default = 0 (None)

mA For 100%
Demand Limit

Config

USER

28

Default = 0.0 mA

mA For 0%
Demand Limit

Config

USER

29

Default = 10.0 mA

Current Limit
Select

Config

USER

30

No
Default = No

ITEM

ITEM EXPANSION

PATH

VALUE

DMDC

Demand Limit
Select

Configuration

RSET

4-20MA INPUT
Default = NONE

DMMX

mA for 100%
Demand Lim

Configuration

RSET

Default =
0.0 mA

DMZE

mA for 0%
Demand Limit

Configuration

RSET

Default =
10.0 mA

CUR.S

Current Limit
Select

Configuration

OPTN

NO
Default: NO

DISPLAY NAME

PATH

LINE NO.

VALUE

Demand Limit
Type Select

Config

USER

24

2 (4-20mA Control)
Default = 0 (None)

mA For 100%
Demand Limit

Config

USER

28

Default = 0.0 mA

mA For 0%
Demand Limit

Config

USER

29

Default = 10.0 mA

Current Limit
Select

Config

USER

30

Yes
Default = No

Current Limit
at 100%

Config

USER

31

Default = 2000.0 Amps