CONTENTS (cont)

Cooler

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

• SUCTION SERVICE VALVE

• LOW FLUID TEMPERATURE

• LOSS OF FLUID FLOW PROTECTION

• TUBE PLUGGING

• RETUBING

• TIGHTENING COOLER HEAD BOLTS

• INSPECTING/CLEANING HEAT EXHANGERS

• WATER TREATMENT

• CHILLED WATER FLOW SWITCH
Refrigerant Circuit

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

• LEAK TESTING

• REFRIGERANT CHARGE
Safety Devices

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

• COMPRESSOR PROTECTION

• COOLER PROTECTION
Relief Devices

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

• PRESSURE RELIEF VALVES
MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Recommended Maintenance Schedule

. . . . . . . . . . 67

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . 67-85

Alarms and Alerts

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

• DIAGNOSTIC ALARM CODES AND POSSIBLE

CAUSES

Service Test

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

APPENDIX A — TOUCH PILOT™

DISPLAY TABLES

. . . . . . . . . . . . . . . . . . . . . . . . . . 86-104

APPENDIX B — NAVIGATOR™ DISPLAY

TABLES

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105-117

APPENDIX C — CCN TABLES

. . . . . . . . . . . . . . 118-132

APPENDIX D — 30XW150-400 CPM

DIP SWITCH ADDRESSES

. . . . . . . . . . . . . . . . 133,134

APPENDIX E — PIPING AND

INSTRUMENTATION

. . . . . . . . . . . . . . . . . . . . . . 135, 136

APPENDIX F — GLOBAL TIME SCHEDULE

CONFIGURATION FOR i-Vu

®

DEVICE AND CSM

CONTROLLER

. . . . . . . . . . . . . . . . . . . . . . . . . . . 137-139

INDEX

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140

START-UP CHECKLIST

FOR 30XW LIQUID CHILLERS

. . . . . . . .CL-1 to CL-7

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be

hazardous due to system pressures, electrical components, and

equipment location. Only trained, qualified installers and ser-

vice technicians should install, start up, and service this equip-

ment. When working on this equipment, observe precautions in

the literature, on tags, stickers, and labels attached to the equip-

ment, and any other safety precautions that apply. Follow all

safety codes. Wear safety glasses and work gloves. Use care in

handling, rigging, and setting this equipment, and in handling

all electrical components.

WARNING

Electrical shock can cause personal injury and death. Shut

off all power to this equipment during installation and ser-

vice. There may be more than one disconnect switch. Tag

all disconnect locations to alert others not to restore power

until work is completed.

WARNING

DO NOT VENT refrigerant relief valves within a building.

Outlet from relief valves must be vented in accordance

with the latest edition of ANSI/ASHRAE (American

National Standards Institute/American Society of Heating,

Refrigerating and Air Conditioning Engineers) 15 (Safety

Code for Mechanical Refrigeration). The accumulation of

refrigerant in an enclosed space can displace oxygen and

cause asphyxiation. Provide adequate ventilation in

enclosed or low overhead areas. Inhalation of high concen-

trations of vapor is harmful and may cause heart irregulari-

ties, unconsciousness or death. Misuse can be fatal. Vapor

is heavier than air and reduces the amount of oxygen avail-

able for breathing. Product causes eye and skin irritation.

Decomposition products are hazardous.

WARNING

DO NOT attempt to unbraze factory joints when servicing

this equipment. Compressor oil is flammable and there is

no way to detect how much oil may be in any of the refrig-

erant lines. Cut lines with a tubing cutter as required when

performing service. Use a pan to catch any oil that may

come out of the lines and as a gage for how much oil to add

to system. DO NOT re-use compressor oil.

CAUTION

This unit uses a microprocessor-based electronic control

system. Do not use jumpers or other tools to short out

components, or to bypass or otherwise depart from rec-

ommended procedures. Any short-to-ground of the con-

trol board or accompanying wiring may destroy the

electronic modules or electrical components.

CAUTION

To prevent potential damage to heat exchanger tubes,

always run fluid through heat exchanger when adding or

removing refrigerant charge. Use appropriate antifreeze

solutions in evaporator and condenser fluid loops to pre-

vent the freezing of heat exchangers or interconnecting pip-

ing when the equipment is exposed to temperatures below

32 F (0° C). Proof of flow switch is factory installed on all

models. Do NOT remove power from this chiller during

winter shut down periods without taking precaution to

remove all water from heat exchangers. Failure to properly

protect the system from freezing may constitute abuse and

may void warranty.

CAUTION

Compressors require specific rotation. Swap any two

incoming power leads to correct compressor rotation.